PanelSimulator Academy

System Design and Integration, lesson 5 of 12

Integration

Lesson 4 decided where the system's thinking will live. Most buildings have several systems, and good ones can still leave an operator hunting through four screens at 2 a.m. Integration means making an event in one system cause useful action in the others. This lesson shows which links are worth having, the ways to make them, and the one kind of link that must never depend on software.

About 15 minutes. Read lesson 4, Choosing an architecture, first.

One event, four systems

Pick a situation, then play or step through.

shared software rear door 5 camera 12 motion sensor intercom Access controldoors and cards Videocameras, recording Intrusionsensors, arming Intercomcalls at doors Operator

The everyday picture

When someone calls for an ambulance, the dispatcher does not ask the caller to phone the hospital, then the fire crew, then the police. One call starts several things at once: the nearest crew is alerted, the address appears on their screen, and the hospital is warned.

Each of those services could work alone, and each is good at its own job. What saves minutes is that one event sets the right things moving in the others, and one person sees the whole picture.

That is integration. It does not make any single system better. It removes the time a person spends carrying information from one screen to another.

What integration is for

Hold every proposed link against three purposes. If it serves none, it is decoration.

  • Faster understanding. The alarm arrives with its video already on screen, so the operator knows in seconds whether it is a thief or a delivery driver.
  • Fewer steps for people. A valid card in the morning turns off the alarm for that area. Nobody has to remember a code, and false alarms fall.
  • Better records. The door event and the video of it are tied together, so that next week's search takes one click, not an hour.

Integration begins with requirements, as lesson 1 taught. "The systems shall be integrated" is not a requirement. "When a controlled door is forced, live video of that door appears at the security desk within 5 seconds" is one. It can be tested with a stopwatch.

Pairs that earn their keep

When this happensThis followsWhy it is worth having
A door is forced or held openThe nearest camera appears, and the recording is markedThe operator sees the cause at once.
A card is denied three times at one doorThe camera at that door appearsTells a forgotten card from someone trying doors.
The first valid card of the dayThe intrusion system disarms that areaEnds the morning false alarm.
The intrusion system is armedAccess is limited to a short list of peopleStops someone walking into an armed area.
Someone presses the intercomThe door's camera appears beside the callThe person answering sees who they are talking to before releasing the door.
An intrusion sensor tripsCameras in that zone are shown, and their video is sent with the alarmMonitoring staff can confirm a real event, which many police departments now expect before they respond.

Every row is a cause in one system and an effect in another. Written out as a grid, with causes down the side and effects across the top, this is a cause and effect matrix. It is the main design document for integration. You will build one below.

Check yourself

Which of these is a testable integration requirement?

Four ways to join systems

There are four common methods. They run from simple and limited to powerful and demanding.

MethodHow it worksGood forWeak point
Wired contactA relay on one system closes a pair of wires into an input on the other.One simple signal: "alarm", "armed", "release". Works between any two makers, and without a network.Carries no detail. Ten signals need ten pairs of wire.
Software linkThe two systems exchange messages over the network through a published interface, often called an API, or a driver written by one maker for the other.Rich detail: which door, which person, which camera.Tied to particular versions. An update on one side can break it.
Unified platformOne software product built to do access, video and more together.One screen, one list of names, one company to call.You take that maker's strengths and weaknesses in every part.
Layer on topA separate program gathers events from many systems and guides the operator through a response.Large sites with many systems from different makers and a staffed control room.Costly to set up and to keep current.

Open standards help at the device level. There are published standards that let cameras from one maker work with recorders from another, and readers from one maker with controllers from another. They rarely cover the links between whole systems, so ask each maker for a written list of what their link does, and with which versions it has been tested.

Do not look down on the wired contact. For a single signal it is cheap, easy to test with a meter, and still works when the network is down.

The line you do not cross

Some links exist for convenience. Others exist to keep people alive. They are built differently.

The fire alarm system is the clearest case. As Access Control lesson 7, Getting out, explained, locks on an exit route generally must release when the fire alarm sounds. That release is made with a direct wired connection from the fire alarm system to the lock power, so that it works when the network, the server and the access software are all down. It is not left to a message between two programs.

  • Life-safety actions are hard-wired and fail in the safe direction. Losing the signal releases the door.
  • The fire alarm system is not yours to modify. Any connection to it is made by, or with, the fire alarm contractor, using the method the authority having jurisdiction accepts.
  • Security software may listen. It is fine for the security screen to show that the fire alarm is active and to bring up cameras. It must never be the only path, and it must never be able to silence, delay or override the fire alarm.
  • No integration may lock people in. An intrusion alarm or a lockdown can stop entry. Free exit stays.

Build a cause and effect matrix

Tick the effects you want for each cause, and read the review underneath. Try a few choices you suspect are wrong.

When this happens, what should follow?

    The dull details that make it work

    • One clock. If the access system says 2:14:05 and the recorder says 2:16:40, the "matching" video shows an empty corridor. Set every server, recorder, controller and camera to take its time from the same time source on the network.
    • One set of names. "Door 5", "Rear exit" and "D-105" may be the same door in three systems. Use the door numbers from your survey in lesson 2 everywhere.
    • A map of what covers what. Somebody has to tell the software that camera 12 looks at door 5. That table is built by hand and must be updated when a camera is moved.
    • Versions written down. Record which versions the link was tested with. Before either side is updated, check that the link supports the new version, and test it again afterwards.
    • An owner. When the link fails, each maker tends to point at the other. Name one company or person responsible for the link itself.
    • A plan for when it breaks. Each system must still do its own job alone. This is the rule from lesson 4: keep deciding at the edge.

    Three examples

    Simple: two wires at a back door

    A small shop has an alarm panel and a separate recorder. The owner wants the recorder to mark its video whenever the alarm goes off, so that the right moment is easy to find. A spare relay on the alarm panel is wired to an alarm input on the recorder. Total cost: a length of two-conductor cable and half an hour.

    There is no software, no version to match and nothing to license. This is integration, and for one signal it is the right kind.

    Medium: the update that broke the link

    An office has 60 controlled doors and 45 cameras from two different makers, joined by a software link. A forced door brings up its camera. It works well for a year. Then the recorder's software is updated to fix a security flaw, and the next week an operator notices that alarms arrive with no video.

    Nothing was faulty. The link had been tested with the old version only. The fix took a day: a newer driver from the access maker. The lasting fix was procedural. The versions went into the handover documents, and the maintenance contract now says that every update is followed by forcing one door and watching for its camera.

    Advanced: the building that armed itself on the cleaner

    A five-floor office wanted the intrusion system on each floor to arm automatically when the last person badged out, and to disarm on the first valid card. It worked on paper. In the first month the third floor armed three times with a cleaner still inside, who had come up the stairs behind a colleague and never presented a card.

    The integration was doing exactly what it was told. The count of people was wrong, because people do not always badge. The redesign kept automatic disarming, which is safe. Automatic arming was replaced with a prompt at the reader beside each floor's exit: the last person out presents a card twice to arm, and a sounder gives 60 seconds' warning on the floor. The lesson is general. An automatic action that depends on people behaving perfectly needs a way for a person to confirm it.

    From the field

    • Ask to see the link working between the exact products and versions proposed, before the order. "Compatible" on a brochure can mean one feature out of ten.
    • Check license costs. Many links are sold per door, per camera or per connection, and renewed yearly.
    • Test every row of the matrix at handover, with the customer watching, and sign each one off.
    • Start with three or four links. Add more only when operators ask for them.
    • Unplug the link on purpose and confirm that doors, recording and alarms all carry on alone.

    Common mistakes

    • Writing "integrated" in a proposal without saying what causes what.
    • Making fire alarm door release depend on a software message.
    • Linking so many events that the operator's screen never stops moving, and is ignored.
    • Letting any alarm unlock doors, or any automation block free exit.
    • Leaving clocks unsynchronized, so that events and video do not line up.
    • Updating one system without checking the link, and without testing afterwards.

    Summary

    • Integration makes an event in one system cause useful action in another, and gives the operator one picture.
    • Write each link as a testable requirement, and collect them in a cause and effect matrix.
    • Join systems by wired contact, software link, unified platform or a layer on top, choosing the simplest that does the job.
    • Life-safety links are hard-wired, fail safe and agreed with the authority. Software may listen, never control.
    • Shared clocks, shared names, recorded versions and a named owner keep the links alive.

    Exercises

    Answer each one yourself first, then open the answer.

    Exercise 1. In the scene at the top, compare "Four separate systems" with "Integrated" for the forced door. What exactly did the operator have to do by hand in the first case?

    Show answer
    Read the door name on the access screen, work out which of 40 cameras covers that door, switch to the video program, find that camera and wind back to 2:14. In the integrated case the software did all of that, and the operator's time went on deciding what to do.

    Exercise 2. A customer needs the alarm panel to tell the access system one thing only: "the building is armed". Which of the four methods would you choose, and why?

    Show answer
    A wired contact. It is one yes-or-no signal, so a relay output on the alarm panel into an input on the access controller does the job. It needs no license, works between any two makers, and can be tested with a meter.

    Exercise 3. An alarm event is logged at 3:02:10. The linked video starts at 3:02:10 on the recorder but shows nothing happening. Thirty seconds later on the same recording, a person walks through the door. What is the likely cause and the fix?

    Show answer
    The two systems' clocks differ by about 30 seconds. Set both, and the cameras and controllers, to take their time from the same network time source, then test again.

    Exercise 4 (think, don't memorize). A school asks for a "lockdown button" that locks every door in the building at once. What questions do you ask before designing it?

    Show answer
    What is the button meant to stop: entry from outside, or movement inside? Who may press it, and from where? How is it cancelled, and by whom? What happens to people in corridors, and can emergency responders still get in? Most important, every door must still open freely from the inside, and the fire alarm release must still work, so the design goes to the authority having jurisdiction and to the fire alarm contractor before anything is ordered. Then write it as a row in the matrix with a test, and plan a drill. A lockdown that has never been tested with real people is a guess.