PanelSimulator Academy

Perimeter Protection, lesson 8 of 8

Designing a perimeter

You now have the parts: fences, gates, vehicle barriers, sensors and lights, and the weather that tests them all. This last lesson puts them together. It gives you a method for working from the boundary inward to the building, and one sum that tells you whether the layers add up to enough.

About 14 minutes. Read the rest of this course first.

Build a perimeter in layers

Switch measures on and off. The plan, the jobs covered and the comments all follow.

public road site is 600 by 300 feet gate Building generator and fuel bends slow the approach bollards
  • Mark and channel
  • Delay at the edge
  • Detect at the edge
  • See what tripped, at night
  • Stop vehicles
  • Delay near the asset

    The everyday picture

    Think about how a bank looks after its cash. There is a parking lot that anyone can enter. There is a lobby with cameras and staff who notice who comes in. There is a counter that customers stay behind. And behind that, there is a vault. Nobody tries to make the parking lot as strong as the vault.

    Each layer is smaller than the one outside it, and each can be stronger because it is smaller. Each one also has people or sensors that notice when it is crossed. A site's perimeter is the parking lot and the lobby. It works when it is designed as the outer part of that whole arrangement, not as a wall on its own.

    The layers and their jobs

    LayerMain jobsTypical measures
    Beyond the lineSee people comingTrimmed planting, open sightlines, radar on large sites
    The boundaryMark, deter, channel, detectFence, signs, gates, fence sensor, lighting, cameras
    The yardExpose, slow vehicles, give timeClear zone, lighting, bollards and road layout, patrols
    The building shellDelay, detect againSolid doors and locks, door contacts, glass protection, access control
    The assetStrong, short delayLocked room, cage, safe, inner fence around outdoor plant

    Two ideas hold the layers together.

    Defense in depth means an intruder must get past several layers in turn, each one noticed. No single layer has to be perfect.

    Balanced protection means each layer is about equally hard to cross all the way round. A strong front gate beside a rear fence with a gap under it is unbalanced: the gap sets the strength of the whole layer. Money spent making the strong part stronger is wasted until the weak part is fixed.

    The way a site is laid out also does security work before any equipment is bought. Low planting and open fences let neighbors and passers-by see in. A clear change from public sidewalk to private path tells people where they stand. One obvious visitor entrance means a stranger anywhere else stands out. Designers call this crime prevention through environmental design.

    A method in eight steps

    1. Name the assets and the adversary. What would hurt to lose, and which row of the table in lesson 1 are you designing against? Write both down.
    2. Get the response time. Who comes, from where, and how many minutes after an alarm? Every later choice depends on this number.
    3. Walk the line and draw it. Mark slopes, ditches, culverts, trees, neighbors' buildings, and every place people or vehicles cross today.
    4. Fix the entrances first. Use as few as the site can work with. Each one needs a vehicle gate chosen as in lesson 3, a separate walk gate, a way to identify people, and a plan for the busiest ten minutes of the day.
    5. Choose the barrier for each stretch. Lesson 2 for people, lesson 4 wherever a vehicle could reach something that matters. Keep a clear zone on both sides where you can.
    6. Add detection and a way to see. Pick sensors for this site's ground, weather and wildlife, as in lessons 5 and 7. Divide them into zones, give each zone a camera view, and light it as in lesson 6.
    7. Check the clock. Add up the delay after first detection and compare it with the response time. The next section shows how. If it falls short, add delay near the asset or move detection outward.
    8. Plan for upkeep and rules. Who walks the fence, tests the zones, mows the clear zone and replaces lamps? What do zoning, the fire department and the exit rules require? A design nobody maintains lasts one season.

    Check yourself

    A site has an excellent front fence and gate, and a rear boundary that is a low hedge. Which idea has been broken?

    Check the clock

    Lesson 1 said that delay only counts after detection. Here is that idea as a sum. List the layers from the outside in, with the time each one costs an intruder. Mark where the first reliable detection happens. Add up everything after that point. If the total is longer than the response time, the responders arrive first.

    The delay figures must be ones you can defend: test ratings for doors, cages and safes, the customer's own standards, or advice from a specialist. The numbers below are placeholders to show the method.

    Does the delay cover the response?

    All times in seconds. Detection is counted at the start of the chosen layer.

    delay after detection
    response time

    Green: delay after detection, against the full width as the response time.

    Try moving the first detection from the fence to the building door and watch the total fall. Then put it back and add time at the room or cage. Those are the two levers a designer has: detect earlier, or delay more near the asset.

    Power and data at the edge

    Equipment at the boundary is far from the building, and getting power and a network connection to it often costs more than the equipment.

    NeedUsual answerWatch for
    Data over long distancesFiber in buried conduitCopper network cable is limited to about 328 feet a run
    Power for devicesLow-voltage feeds from field cabinets, or power over the network cable from a switch in each cabinetVoltage drop on long runs, as Access Control lesson 9 showed
    No trench possiblePoint-to-point wireless links, solar with batteriesLine of sight, winter sun, and what happens on the third cloudy day
    ProtectionLocked cabinets inside the fence, tamper switches, surge protectionA cabinet reachable from outside the fence

    Plan the trench once. Put in spare conduits for the camera or gate that will be added in three years, because digging the same line twice is the most expensive mistake on a perimeter job.

    Three examples

    Simple: the builder's supply yard

    A lumber yard loses material over a 5-foot fence at night. The owner lives ten minutes away and is the response. The design is modest: raise the fence to 7 feet with a bottom wire, clear the pallets stacked against it, add a fence sensor in four zones with a camera on each, and light the line evenly. Alarms go to the owner's phone with a camera clip. Power tools and copper move into a locked steel container near the office, which supplies the delay that ten minutes needs.

    Medium: the school campus

    An elementary school has six buildings, playgrounds, and open paths that the public uses as a shortcut. The threat by day is a stranger walking in. By night it is vandalism.

    The design channels more than it blocks. A 6-foot fence with smooth tops closes the shortcut paths and encloses the playgrounds. During school hours, every gate but one is locked from outside and still opens freely from inside, and the open one leads only to the front office. Low planting keeps the office's view of the approach clear. After hours, cameras with analytics watch the courtyards, and lights come up when they trip. There are no barbed toppings and no vehicle barriers except bollards at the parent pick-up curb. The fire department reviews every gate.

    Advanced: the utility control building

    A utility's control building has a response time of 6 minutes, which is 360 seconds. The first design detects at the fence and counts 20 seconds to cross the yard, 60 for the building door and 120 for the equipment cage: 200 seconds after detection. That is 160 seconds short.

    The designer does not make the fence stronger, because fence delay would add only seconds. Instead the building door is replaced with a rated security door assembly good for 180 seconds, and the cage with a rated enclosure good for 240. The sum becomes 20 + 180 + 240 = 440 seconds, 80 more than the response needs. A second sensor of a different kind is added inside the fence so that the detection the whole sum depends on is harder to miss. Bends in the driveway and rated bollards keep vehicles away from the door.

    From the field

    • Draw the layers on one plan in different colors. Gaps show up at once: the stretch with no sensor, the door with no layer in front of it.
    • Walk the design at night before it is priced. Stand where each camera will go and look.
    • Ask operations what crosses the line every day. Deliveries, trash trucks, snow plows and landscapers all need a way in that does not involve propping a gate.
    • Agree a test with the customer. Decide who will walk-test each zone and time the response, and repeat it every year.
    • Leave room to grow. Spare conduit, spare fibers and spare cabinet space cost little on day one.

    Common mistakes

    • Designing the fence first and asking about the response time last.
    • Strengthening the layer that is already strongest.
    • Counting delay that comes before detection.
    • Forgetting power, data and trenching until the equipment is ordered.
    • Handing over a system with no plan for testing, mowing and repairs.

    Summary

    • Design from the boundary inward, in layers that get shorter and stronger.
    • Keep each layer balanced. Its weakest stretch is its strength.
    • Start with the asset, the adversary and the response time.
    • Add up the delay after first detection. It must exceed the response time.
    • When it falls short, detect earlier or add delay near the asset, and plan the upkeep that keeps it true.

    Exercises

    Answer each one yourself first, then open the answer.

    Exercise 1. What is the difference between defense in depth and balanced protection?

    Show answer
    Defense in depth is about having several layers, one inside another. Balanced protection is about one layer being equally hard to cross all the way round.

    Exercise 2. A site detects at the fence. After that, the yard takes 30 seconds, the building door 90 and a locked room 150. The response time is 5 minutes. Is that enough?

    Show answer
    30 + 90 + 150 = 270 seconds. Five minutes is 300 seconds. It falls 30 seconds short, so add delay at the room or door, or shorten the response.

    Exercise 3. In exercise 2, the fence sensor is removed and the first detection is the contact on the building door. What is the delay after detection now?

    Show answer
    Counting from the start of the door: 90 + 150 = 240 seconds. The yard's 30 seconds no longer count, and the intruder reaches the door unannounced.

    Exercise 4 (think, don't memorize). A food warehouse on 12 acres asks for "a full perimeter system". The budget covers either a sensor and cameras on the whole fence, or a sensor and cameras on the truck court side only, plus alarmed and reinforced dock doors and a locked cage for high-value goods. Police response is about 12 minutes. What do you recommend?

    Show answer
    Probably the second. With a 12-minute response, detection at the fence starts a clock that nothing on site can run out: a plain dock door and open shelves give a minute or two. The whole-fence option would tell the owner about a theft that still succeeds. The second option puts detection where vehicles can get close and adds real delay at the doors and the cage, so the sum after detection can approach 12 minutes. It leaves three sides with a fence only, which is unbalanced, so say so plainly, keep those sides in good repair and well lit, and plan to extend detection later using spare conduit laid now.