Networking for Security, lesson 10 of 12
Fiber
Copper network cable stops at 328 feet, and it carries lightning and electrical noise as readily as it carries data. A strand of glass thinner than a hair has neither problem. This lesson explains how fiber works, which kind to choose, and the simple sum that tells you whether a link will work before you install it.
Spend the light budget
A link has a fixed budget of light to lose on the way. The glass, every connector and every splice each take a little. Change the run and see what is left.
The everyday picture
Two people at opposite ends of a long, dark hallway can signal each other with flashlights. Line the hallway with mirrors and the light keeps bouncing along, even around gentle corners. Blink the flashlight very fast and you can send a great deal of information.
A fiber is that mirrored hallway, shrunk to a thread of glass. A tiny laser or light at one end blinks on and off, up to billions of times a second. The glass guides the light to the far end, where a sensor turns the blinks back into data.
Two things dim the light on the way: the length of the hallway, and every doorway it has to pass through. On a fiber, the doorways are connectors and splices. Much of this lesson is about keeping enough light arriving.
Why light beats copper
- Distance. Copper network cable is limited to 328 feet. Fiber links run from hundreds of feet to many miles.
- No electricity in the cable. Glass does not conduct. A lightning strike near a copper cable between two buildings can destroy the equipment at both ends. A fiber carries nothing but light, so a surge has no path.
- No electrical noise. Motors, elevators and power cables do not disturb light. Fiber can share a route that would ruin a copper link.
- Capacity. The same strands that carry 1 gigabit today can usually carry 10 gigabits later by changing only the modules at each end.
The price is that fiber carries no power. A camera at the far end of a fiber still needs electricity from somewhere, because Power over Ethernet travels only on copper.
Two kinds of fiber
Every fiber has a core, the central glass that carries the light, wrapped in a second layer of glass called the cladding, which reflects the light back in. The size of the core gives two families. Sizes are measured in microns. A micron is a thousandth of a millimeter, and a human hair is roughly 70 microns across.
| Multimode | Single-mode | |
|---|---|---|
| Core size | 50 microns (62.5 in older cable) | About 9 microns |
| How light travels | Along many paths at once, which smears the signal over distance | Along one path, so the signal stays sharp |
| Typical reach at 1 gigabit | About 1,800 feet | About 6 miles with common modules, and far more with long-range ones |
| Typical reach at 10 gigabit | About 1,000 to 1,300 feet on current grades | About 6 miles with common modules |
| Usual jacket color indoors | Aqua for current grades, orange for older ones | Yellow |
| Where it fits | Inside one building, between wiring closets | Between buildings, across a campus, and anything long |
Multimode cable is sold in grades named OM1 to OM5, and newer grades reach further. Single-mode grades are named OS1 and OS2. The reach figures above are typical and depend on the grade and the module, so read the module's data sheet for the pair you are buying.
The two kinds do not mix. A multimode module on single-mode glass, or the reverse, gives a link that fails or flickers. Many installers now choose single-mode for everything outdoors, since the cable costs about the same and it will never run out of distance.
Check yourself
A camera sits at the end of 1,500 feet of fiber. What does the fiber not deliver to it?
The parts at each end
- Two strands. Most links use a pair of strands, one for each direction. The sender at one end must meet the receiver at the other, so the pair crosses over once along the way. If a new link will not come up, swapping the two connectors at one end is the first thing to try.
- The module. A switch does not make light by itself. A small plug-in part called an SFP module slides into a slot on the switch and holds the laser and the sensor. Modules are made for one fiber type, one speed and one distance class. The two ends of a link must match.
- The media converter. A small box with a copper port on one side and a fiber port on the other. It lets a device with only a copper port, such as a camera, sit at the end of a fiber. It needs its own power.
- Connectors. The common one today is the LC, a small square plug usually clipped together in pairs. Older installations use the larger square SC and the round, twist-on ST. Connectors also come with two styles of polished tip, normally color-coded blue and green. The two styles must never be plugged into each other.
- The patch panel. The outdoor or riser cable ends in a small enclosure where each strand is given a connector. Short patch cords then run from the panel to the module, so the permanent cable is never handled day to day.
Loss and the budget
Light is lost along the way, and the loss is measured in decibels, written dB. You only need to add them up. Each module pair has a power budget: the most loss the link can stand between sender and receiver. It is printed in the module's data sheet.
For planning, industry cabling standards give allowances like these. Good work loses less, so they are safe figures to design with. Use the figures in your cable's data sheet if they differ.
| Part | Planning allowance |
|---|---|
| Multimode fiber | About 1 dB for each 1,000 feet |
| Single-mode fiber | About 0.3 dB for each 1,000 feet |
| Each pair of mated connectors | 0.75 dB |
| Each splice | 0.3 dB |
Take 900 feet of multimode with a patch panel at each end. The glass loses 0.9 dB and the two connector pairs lose 2 × 0.75 = 1.5 dB, for a total of 2.4 dB. With modules that have a 7.5 dB budget, 5.1 dB is left over. That leftover is the margin. Aim for at least 3 dB, because connectors get dirty, cables get moved and lasers dim a little with age.
Notice where the loss comes from. On most security jobs the connectors cost more light than the glass does. A link with too many patch points fails sooner than a link that is merely long. For multimode, remember that the distance limits in the earlier table apply as well, however good the loss sum looks.
Copper or fiber?
Decide what you would run for each job, then press your answer.
Six runs to choose a cable for
Handling fiber
- Never look into a fiber or a module. The light is infrared and invisible, and it can injure an eye. Treat every strand as lit.
- Respect the bend. Bend glass too tightly and light leaks out at the bend, or the strand cracks. A common rule is a bend no tighter than ten times the cable's diameter, and twenty times while it is being pulled. The cable's data sheet gives the real figure.
- Pull by the strength member. Fiber cable contains strong yarn made for pulling. Pulling on the jacket or the connectors stretches the glass.
- Keep the ends clean. The core is far smaller than a speck of dust. Inspect and clean every connector before plugging it in, and keep dust caps on anything unplugged.
- Choose how the ends are made. Cable can be ordered to length with connectors fitted at the factory, which suits small jobs. On larger jobs a technician joins factory-made tails to each strand with a fusion splicer, a tool that melts the glass together.
Three examples
Simple: a camera 600 feet down a warehouse
A camera is needed at the far end of a warehouse, 600 feet from the switch. Copper cannot reach. A factory-terminated multimode cable is pulled, with a media converter at the camera end and an SFP module in the switch. The loss is 0.6 dB of glass plus 1.5 dB of connectors, 2.1 dB against a 7.5 dB budget. The media converter and the camera are powered from an outlet at the camera end. The far end needs power, and somebody must remember that at the planning stage.
Medium: two buildings and a thunderstorm
A school joined its gym to the main building with 250 feet of outdoor copper cable. It was within the distance limit and worked for a year. After a summer storm, the switch ports at both ends were dead, along with two cameras.
The two buildings have separate electrical grounds, and a nearby strike drove a surge along the copper between them. The replacement is a six-strand single-mode cable in the same conduit. Two strands are used and four are spare. Nothing electrical now connects the buildings' networks, so the next storm has no path.
Advanced: a gate two miles away
A utility yard has a gate 10,500 feet from the control room, with three cameras, an intercom and a door controller. Single-mode fiber is the only sensible choice. The route passes through two handholes where cable reels are joined, so there are two splices, and a patch panel at each end.
The loss sum: 10.5 thousand feet × 0.3 = 3.15 dB of glass, 2 × 0.75 = 1.5 dB of connectors and 2 × 0.3 = 0.6 dB of splices. The total is 5.25 dB. The chosen modules have a 10 dB budget, leaving a margin of 4.75 dB. At the gate, a small PoE switch with an SFP slot sits in a heated enclosure with its own power supply and battery. After installation the contractor measures the real loss of every strand and hands over the results.
From the field
- Pull more strands than you need. Labor is most of the cost. Six or twelve strands cost little more than two, and a broken strand then means moving a patch cord instead of pulling new cable.
- Clean first, then suspect. A dirty connector is the commonest cause of a fiber link that has stopped working or has started dropping.
- Read the module's label. It gives the fiber type, speed and wavelength. Both ends should say the same thing.
- Test and keep the numbers. A light source and power meter measure the real loss of each strand. Record it at handover, so a later reading has something to be compared with.
- Label both ends of every strand. A panel of twelve identical connectors with no labels turns a five-minute job into an afternoon.
Common mistakes
- Forgetting that the far end still needs power.
- Mixing multimode and single-mode parts on one link.
- Running outdoor copper between buildings because the distance is under 328 feet.
- Kinking the cable around a tight corner or cinching it hard with cable ties.
- Plugging in connectors without cleaning them.
- Adding patch points for convenience without redoing the loss sum.
Summary
- Fiber carries data as light in glass. It goes far, ignores electrical noise and gives surges no path.
- Multimode suits runs inside a building. Single-mode suits long runs and links between buildings.
- A module in each switch, or a media converter, turns electrical signals into light. Both ends must match the fiber and each other.
- Add the loss of the glass, the connectors and the splices, and keep at least 3 dB of margin under the modules' budget.
- Fiber carries no power, dislikes tight bends and must be kept clean.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Which kind of fiber has the smaller core, and what does that buy you?
Show answer
Exercise 2. Work out the loss of 2,000 feet of single-mode fiber with four connector pairs and two splices, using the planning allowances.
Show answer
Exercise 3. That link uses modules with a 10 dB budget. What is the margin, and is it enough?
Show answer
Exercise 4 (think, don't memorize). A guard booth stands 200 feet from the main building, across a parking lot. A colleague says, "It is under 328 feet, so copper is fine." What would you run, and why?