PanelSimulator Academy

Fire Alarm Interface and Life Safety, lesson 7 of 10

Delayed and controlled exits

The Access Control course introduced two exceptions to instant free egress in one table row each. Here they get a full lesson. You will see exactly what a delayed exit does second by second, what a controlled exit asks of the staff, and the list of conditions that must all be met before either one is legal.

About 15 minutes. Read "The fire alarm relay" first, and "Getting out: egress and life safety" in the Access Control course.

Push the bar and wait

Drag the slider to move time forward from the moment someone pushes the bar. Then change the conditions.

Push until alarmsounds. Door opensin 15 seconds. exit door, from inside 15 What the lock is doing bar held alarm at the door, counting down released seconds since the bar was pushed
door
sounder at the door
time left

The everyday picture

Think of the emergency brake handle on a train. Anyone may pull it. But it is behind a cover, it makes a great deal of noise, and everyone looks at the person who pulled it. Nobody uses it to get off at a convenient spot.

A delayed exit works on the same feeling. The door will open for anyone, every time. It just costs fifteen noisy seconds, which is enough to stop a shoplifter and nowhere near enough to endanger a person in a real emergency, because in a real emergency the delay is cancelled.

A controlled exit is closer to a hospital ward where a nurse walks a confused patient to the door. The door does not open for the patient alone. The safety comes from trained people who are always there and can always open it.

Three kinds of exit

Free egressDelayed egressControlled egress
Who can open itAnyone, at onceAnyone, after a short delayStaff, at once. Others only with staff.
Typical reasonThe normal ruleTheft from stockrooms, wandering in some care settingsPatients who would come to harm outside, infant security
On fire alarm or sprinkler flowNo changeDelay cancelled, door freeDoors unlock, with narrow exceptions set by code
On loss of powerNo changeDoor freeDoors unlock, with the same exceptions
Where allowedEverywhereOnly in certain kinds of buildingMainly health care and similar units

Both exceptions are called special locking arrangements. Each is permitted only in certain uses of building, the lists differ between the building code and the Life Safety Code, and they change between editions. Places where crowds gather are commonly excluded from delayed egress. The first question is always whether your kind of building may have one at all, and only the authority having jurisdiction can answer it.

Delayed egress in depth

A delayed egress lock is usually a special magnetic lock or a special push bar with a timer and a sounder built in. Use the tool at the top to follow one cycle.

  1. A person pushes the bar or the door. Nothing happens for a moment. This short window, up to about 3 seconds, stops an accidental bump from starting the cycle.
  2. If they keep pushing, the lock begins an irreversible process. A loud sounder starts at the door. From here the door will release whether or not anyone is still pushing.
  3. After 15 seconds the lock releases. The person walks out.
  4. The lock stays released until someone resets it by hand at the door. It does not quietly relock.

The codes surround this with conditions. The wording below is general. The exact figures are in the edition your city has adopted.

ConditionWhy it is there
The building is protected throughout by sprinklers, or by a detection system, as the code specifiesA fire will be caught early enough for the delay not to matter
The lock releases at once when the sprinklers or the fire detection operateNo delay in a real fire
The lock releases at once on loss of power to itA dead lock must never be a locked lock
The cycle starts with a modest push, around 15 pounds, held for no more than about 3 secondsA frightened or frail person can start it
The delay is 15 seconds. Up to 30 only where the authority approves it.Long enough to deter, short enough to survive
A sounder operates near the doorStaff are alerted, and the person knows something is happening
A sign on the door explains what to doA stranger can work it without special knowledge
Relocking is by hand onlySomeone must come to the door and look
Emergency lighting covers the doorThe sign can be read in a power cut
A person leaving normally meets no more than one such delay, with limited exceptionsDelays must not add up along the route

The sign's wording is laid down in the code: in substance, "Push until alarm sounds. Door can be opened in 15 seconds." Its letter size and position are specified too. Use the sign supplied with the listed lock.

Check yourself

Someone starts the cycle on a delayed exit, then lets go and walks away after 5 seconds. What does the door do?

Controlled egress in depth

In a memory care unit, a locked psychiatric ward or a maternity unit, the people at risk are the occupants themselves. A patient with dementia who walks out in winter may die. An infant may be carried off. Free egress, and even a 15-second delay, would fail the very people the building exists for.

Controlled egress lets these doors stay locked in the direction of exit. In exchange the codes typically require:

  • Staff who can unlock every door, readily and at all times. By a key or code that each of them carries, a card, or a release switch at a staffed station.
  • Automatic unlocking when the sprinklers or fire detection operate and when power fails. Certain units, such as psychiatric wards and infant security areas, may be excused from this in some codes, because unlocking would itself be dangerous. Then the staff procedure carries the whole load.
  • A building protected by sprinklers and a detection system as specified.
  • A written emergency plan, with staff trained and drilled to move patients.
  • A clinical or safety reason for locking, recorded by the facility.

Wander-alert systems belong here too. A patient wears a small tag, and a door locks as the tag comes near. To the code that is a locking arrangement on an exit like any other, and it must meet the same conditions.

Notice what replaces the hardware guarantee: people. A controlled exit is safe only while the unit is staffed as planned. That is the facility's promise to the authority, and it is why you never offer this arrangement to an ordinary office or shop.

How they are wired

Everything in lesson 3 applies, with more at stake.

  • The fire alarm relay removes power from the lock directly. On a delayed exit that cancels the delay. The fire alarm contractor programs which signals operate it, usually sprinkler waterflow and detection.
  • The lock is fail-safe. Loss of power releases it.
  • Delay timing lives inside the listed lock, set by its own switches. Do not build a delay out of controller software and an ordinary magnetic lock. It would not be listed, and its timing would depend on the controller.
  • The access controller may release the door for authorized staff with a card, and may log the door's alarm output. Those are conveniences layered on top.
  • A reset key switch at the door relocks it after a cycle.

Is this proposal ready?

Checklist for a delayed exit

Tick what is true for the door you have in mind. Every line must be ticked before the proposal goes anywhere.

Three examples

Simple: the stockroom door

A furniture store loses stock through its rear exit. The building has sprinklers throughout. The authority having jurisdiction confirms that this kind of store may use delayed egress and approves one door. A listed delayed egress bar is fitted with its sign, a 15-second delay and a release from the fire alarm. Staff learn that the sounder means "go and look", and that the door must be reset with a key afterward.

Medium: thirty seconds, please

The same store's manager asks for the delay to be set to 30 seconds, since the switch inside the lock allows it. You decline to change it. A 30-second delay is available only where the authority specifically approves it, and this approval says 15. Setting it higher would turn an approved door into a violation, and the sign on the door would then be untrue. If the store wants 30, it asks the authority, and the sign changes with the setting.

Advanced: the memory care wing

A care home is converting one wing for residents with dementia. The owner first asks you for "magnetic locks with a keypad on the inside". Fitted on that description alone, it would be an illegal locked exit.

Done properly, the owner's architect and the authority agree a controlled egress design. The wing is sprinklered. Each exit has a fail-safe lock released by the fire alarm and by power loss. Staff release doors with a code they all know and with a switch at the nurse station. The home writes the locking into its emergency plan and trains each shift. You install to that approved drawing, the fire alarm contractor provides the release, and the acceptance test is witnessed. Six months later a visitor complains that the code is posted beside the keypad. That is deliberate, and permitted there: residents cannot use it, and everyone else can.

From the field

  • Buy the listed assembly. A delayed egress lock is tested as a unit with its timer, sounder and sign. Use it as supplied.
  • Time it with a watch at handover. Push, count, and write the measured delay on the test sheet.
  • Test the cancel. Start a cycle, then have the fire alarm contractor trigger the release. The door must open at that instant.
  • Keep the approval letter in the cabinet. The next inspector will ask for it, and so will the next technician.
  • Teach the reset. A delayed door left released after a cycle is an open back door until someone turns the key.

Common mistakes

  • Fitting either arrangement because the customer asked, without approval for that building.
  • Making a home-made delay from a controller timer and a magnetic lock.
  • Setting 30 seconds because the switch allows it.
  • Leaving off the sign, or fitting it where the open door hides it.
  • Putting two delayed doors one after another on the same way out.
  • Calling a locked door "controlled egress" where no trained staff are present.

Summary

  • Delayed egress lets anyone out after a short, loud delay. Controlled egress lets staff decide, in units where leaving would harm the occupants.
  • Both are exceptions allowed only in certain buildings and only with approval.
  • A delayed exit starts an irreversible cycle, sounds at the door, releases in 15 seconds and is reset by hand.
  • Fire detection, sprinkler flow and loss of power release these locks at once, with narrow exceptions for some care units.
  • The delay belongs inside a listed lock. The fire alarm relay acts on lock power, as always.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. In the tool at the top, set an ordinary day and a 15-second delay. At roughly what time on the slider does the door release, and why is it not exactly 15?

Show answer
At about 18 seconds. The first 3 seconds or so are the window in which the push must be held before the cycle starts. The 15-second delay is counted from the start of the cycle. Real locks differ in how they treat that first window, so time yours with a watch.

Exercise 2. Give two events that cancel the delay on a delayed exit.

Show answer
Operation of the sprinkler system or fire detection system, through the fire alarm relay, and loss of power to the lock. Some designs also allow a release switch at a staffed location.

Exercise 3. What takes the place of free egress as the safeguard in a controlled egress unit?

Show answer
Trained staff who are always present and can unlock every door at once, backed by sprinklers, detection, automatic unlocking where required and a practiced emergency plan.

Exercise 4 (think, don't memorize). A day-care center for young children asks for a 15-second delayed exit on its front door so that toddlers cannot run into the parking lot. How do you handle it?

Show answer
The aim is sensible, but do not assume the answer. Whether delayed egress is allowed depends on how the code classes that building, and the rules for places with children differ between codes and editions. Ask the authority having jurisdiction first, in writing, describing the door and the building's sprinklers and alarm. If they refuse, look for other approved measures, such as a door alarm, hardware mounted at a height the code permits, or a fenced area outside the door. If they agree, fit a listed lock with every condition on the list met.