Fire Alarm Interface and Life Safety, lesson 6 of 10

Elevators in a fire

An elevator is the one place where three trades meet: fire alarm, elevator and security. In a fire the elevator stops serving passengers, goes to a safe floor and waits for firefighters. This lesson shows how that works and why the card reader in the car has no say in it.

About 13 minutes. Read "How a fire alarm system works" first, and "Gates, turnstiles and elevators" in the Access Control course.

Send the car home

Pick an event and watch the car, the lamp in the car and the card reader.

machine room floor 5floor 4 floor 3floor 2, alternate level floor 1, designated level lobby detector Inside the car 4 Firefighter lamp off Card reader choosing floors Fire service key off
mode
where the car goes
who controls it

The everyday picture

Think of a ski lift when a storm comes in. The operators do not let new riders on. They run every chair to the bottom station, let people off there, and stop the lift. After that it moves only for the rescue team, under their hands.

An elevator in a fire is handled the same way. It is taken out of public service, brought to a floor where people can walk outside, and parked with its doors open. From then on it answers only to firefighters.

Why elevators are taken away

The sign beside every call button says to use the stairs in a fire. There are solid reasons.

  • The shaft is a tall chimney. Smoke rises through it and can fill a car stopped between floors.
  • A call button on the fire floor can summon a car full of people and open its doors onto the fire.
  • Heat and water can stop the machinery and trap riders.
  • Firefighters need the cars to carry crews and equipment upward.

Some newer tall buildings have special elevators designed for evacuating occupants, with protected lobbies and their own rules. Those are engineered case by case. Everywhere else, the rule in this lesson applies.

Recall and firefighter service

The elevator rules in the United States come mainly from the elevator safety code, ASME A17.1, working together with the fire alarm code. They describe two stages, and the trade uses these names every day.

Phase I: emergency recallPhase II: in-car firefighter operation
Started byCertain smoke detectors, or a key switch in the main lobbyA firefighter turning a key switch inside the car
What the car doesIgnores all calls, travels without stopping to the recall floor, opens its doors and staysGoes only where the firefighter inside sends it. Doors open and close only while they hold the button.
Call buttons and card readersIgnoredIgnored
Ends whenThe fire alarm is reset and the key switch is returnedThe firefighter returns the car to the recall floor and removes the key

The floor the cars return to is the designated level, normally the floor with the main exit to the street. If the smoke is on that floor, sending people there would be the worst choice, so the cars go to an alternate level chosen in the design. Try both in the tool at the top.

Inside the car is a lamp shaped like a firefighter's helmet. It lights steadily during recall. If it flashes, smoke has been detected in the machine room or the shaft, and the car itself may not be safe to ride.

What starts a recall

This surprises many people. In most designs a general fire alarm does not recall the elevators. Only the detectors that protect the elevators do:

  • the smoke detector in each elevator lobby,
  • the detector in the machine room or control room,
  • the detector in the shaft, called the hoistway, where one is fitted.

A pull station at the far end of the fifth floor sounds the horns and releases the doors, but the elevators usually carry on until smoke reaches a lobby. The reasoning is that false recalls strand people, and the elevators are only dangerous once smoke is near them. Some buildings are set up differently, so read the sequence of operations.

The fire alarm panel passes these signals to the elevator controller through relay modules in the machine room, the same kind of dry contact as in lesson 3. There are separate signals for "go to the designated level", "go to the alternate level" and "flash the lamp".

You may also hear of shunt trip. Where sprinklers protect the machine room or shaft, a heat detector beside the sprinkler head can cut the elevator's main power just before water would reach the electrical gear. It is designed so that recall has normally finished first. It is entirely the business of the fire alarm, elevator and electrical trades.

Check yourself

The smoke detector in the main lobby on floor 1, the designated level, goes into alarm. Where do the cars go?

Where the access system fits

The Access Control course showed a card reader in the car that lights only the floor buttons a person is allowed to press. That arrangement works by the access controller closing contacts that the elevator controller reads. In fire service the elevator controller simply stops reading them.

So you do not program the fire behavior. The elevator does it. Your job is to make sure nothing you installed gets in the way, and to stay on your side of another demarcation point.

ItemWho does it
Smoke detectors, relay modules and the recall signalsFire alarm contractor
Elevator controller, its programming, key switches, the lamp, wiring in the shaft and the traveling cable to the carElevator contractor
Mounting the reader in the car and connecting it to spare wires in the traveling cableElevator contractor, or you under their direct supervision, as they require
Access controller, floor relays, and wiring to an interface terminal box in the machine roomSecurity installer
Connections from that terminal box into the elevator controllerElevator contractor

Elevators have their own inspector and their own permit. A car that has been altered without the elevator contractor can fail its inspection and be shut down. Treat the machine room as you treat the fire panel: you do not open the elevator controller.

Three more points keep you out of trouble:

  • The elevator must ignore you in fire service. Ask the elevator contractor to confirm that card restrictions are bypassed in Phase I and Phase II, and test it.
  • Your failure must not strand the car. Decide with the customer what happens if the access controller dies: usually all floors become free, sometimes all floors lock. That is a security decision for normal times only.
  • Tell the controller. A spare contact that follows "fire service active" lets the access system log the event and stop reporting nonsense.

What will the car do?

Six events in a typical building

The designated level is floor 1 and the alternate level is floor 2. Choose what the elevators do, then read why.

Three examples

Simple: the reader that went dark

During a fire drill a tenant notices that the card reader in the elevator did nothing and every floor button was dead. They report a fault. There is none. The car was in recall, parked at the lobby with its doors open, and neither the reader nor the buttons count in that mode. You add a line to the handover notes so the next person is not surprised.

Medium: the locked-off floor

A law firm on the top floor wants its floor button to stay locked "under all conditions, including fire". You explain that this is not possible and not legal. In Phase II a firefighter with the key can take the car to any floor, and must be able to. What the firm can have is a locked lobby door between the elevator and its offices, with hardware that still lets people out. That door keeps strangers out on an ordinary day, and firefighters have their own means of entry.

Advanced: three trades and one traveling cable

A hospital adds card readers to four existing cars. The security contractor quotes the readers, the controllers and the cable to the machine room. Nobody has priced the wires in the traveling cable, the car panel cut-outs or the elevator contractor's time.

At the kickoff meeting the three trades agree a single drawing. The elevator contractor confirms spare shielded pairs in each traveling cable, cuts the car panels and lands the floor-select contacts in its controller. The fire alarm contractor confirms that recall is unchanged. You wire to a terminal box on the machine room wall and no further. The elevator inspector is told before work starts. On test day, each car is recalled by a lobby detector with a card held at the reader, to prove that the reader makes no difference.

From the field

  • Meet the elevator contractor before you quote. Their charges for a reader in a car often exceed yours.
  • Never enter the shaft or ride on top of a car. That work belongs to elevator mechanics only.
  • Ask for the recall floors in writing. Designated and alternate levels are on the fire alarm drawings. Mark them on yours.
  • Keep your equipment out of the machine room unless invited. Many jurisdictions limit what may be installed there to elevator equipment.
  • Watch the lobby detectors. Dust from your drilling in an elevator lobby can recall every car in the building.

Common mistakes

  • Promising a customer that a floor can stay locked off in fire service.
  • Wiring floor relays straight into the elevator controller without the elevator contractor.
  • Assuming any fire alarm recalls the elevators, and writing that into a security procedure.
  • Trying to make the access system start a recall for a security event.
  • Forgetting the elevator permit and inspection when planning the schedule.

Summary

  • In a fire, elevators leave public service, return to a safe floor and wait for firefighters.
  • Phase I recalls the car. Phase II gives it to the firefighter inside.
  • Recall is normally started by smoke detectors in elevator lobbies, the machine room and the shaft, not by every alarm.
  • The car goes to the designated level, or to the alternate level if the smoke is at the designated one.
  • Card readers and floor restrictions are ignored in fire service. The elevator contractor owns everything inside the elevator.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. What is the difference between Phase I and Phase II?

Show answer
Phase I is automatic recall: the car ignores calls, travels to the recall floor, opens its doors and stays. Phase II begins when a firefighter turns the key switch inside the car, and from then on the car moves only as that person commands.

Exercise 2. In the tool at the top, which event makes the firefighter lamp flash, and what does a flashing lamp tell the firefighters?

Show answer
Smoke in the machine room. A flashing lamp warns that the fire may be affecting the elevator's own equipment or shaft, so the car may stop working and should be used with great caution or not at all.

Exercise 3. A pull station is operated on floor 5 and the horns sound. A visitor then rides the elevator from floor 4 to floor 1. Is the elevator faulty?

Show answer
Probably not. In most designs only the detectors in elevator lobbies, the machine room and the shaft start a recall. The visitor should have used the stairs, as the signs say, but the elevator behaved as designed. Check the building's sequence of operations to be sure.

Exercise 4 (think, don't memorize). A security manager asks for a "lockdown" button that sends all elevators to the lobby and holds them there when a threat is reported. How do you respond?

Show answer
Do not build it from the fire recall inputs. Those belong to the fire alarm and elevator systems, and using them for a security event would confuse firefighters and may break the elevator's approval. Some elevator controllers offer a separate security or independent service input that parks cars. Whether that may be used, and how it behaves if a fire alarm arrives at the same time, is for the elevator contractor, the building owner and the authority having jurisdiction to settle. Your part would be one contact at the agreed terminal box, and fire service must still override it.