Fire Alarm Interface and Life Safety, lesson 5 of 10
Stairwells and re-entry
A stairwell is the protected way down and out. Security often wants its doors locked from the stair side, so that people cannot wander from floor to floor. This lesson explains why those doors must be able to unlock in an emergency, why they must stay latched while they do, and which lock achieves both.
Five floors and a stair, seen from the side
Pick a situation, then play or step through. The square on each stair door shows the stair side: red is locked, green is free.
The everyday picture
Think of the emergency lane on a highway. You may pull into it at any time, with no gate and no ticket. But a lane you could never leave again would be a trap. If the road ahead is blocked, you need a way back off it.
A stairwell is the building's emergency lane. Getting into it must always be easy. And if the way down is blocked, by smoke, by a crowd or by a door that will not open at the bottom, people need a way back out of the stair onto a floor. Going back onto a floor from the stair is called re-entry.
A door with two sides
A stair door is really two different doors, depending on where you stand.
| From the floor, into the stair | From the stair, onto the floor | |
|---|---|---|
| What it is | The way out. An exit route. | The way back in. Re-entry. |
| On a normal day | Always opens with one motion. No card, ever. | May be locked for security in many buildings, where the code permits |
| In a fire alarm | Unchanged. It already opens. | Must unlock, where it is allowed to be locked at all |
| The latch | Stays latched the whole time. It is a fire door protecting the stair from smoke. | |
The stair itself is a fire-rated shaft, and its doors are fire doors like those in the last lesson: self-closing and positively latched. So the task is a subtle one. In an alarm the door must become unlocked without becoming unlatched. The lever on the stair side comes alive, and the latch keeps holding the door shut until someone turns that lever.
Two doors are different from the rest. The door at the bottom that leads from the stair to the street, the exit discharge, must always open from inside. And the door to the roof follows its own rules, which vary by place.
Why re-entry matters
Stairs fill with smoke more often than people expect. A single door propped open on the fire floor is enough. People coming down from above then walk into it.
In October 2003, a fire broke out in a high-rise office building in Chicago. People who had entered a stair met smoke, tried to go back onto the floors and found the doors locked from the stair side. Six of them died in the stairwell. Rules on stair door locking were tightened in many places afterward.
There are everyday reasons too. Someone with a heart condition cannot manage twenty flights. A wheelchair user waits on a landing for help. Firefighters climbing up need to get onto the fire floor from the stair.
Check yourself
When the fire alarm unlocks a stair door from the stair side, what should happen to the latch?
What the codes generally allow
The building code and the Life Safety Code each have their own wording, and the answer depends on the height and use of the building and on the edition your city has adopted. In broad terms you will meet three arrangements.
- Never locked. Every stair door opens from both sides at all times. This is the simplest and is always acceptable to the fire side. Security manages it with door alarms and cameras.
- Locked, with automatic unlocking. Stair-side levers are locked in normal times. All of them unlock together, without unlatching, on a signal from the fire alarm system or from a switch at the fire command center, and on loss of power. This is the usual arrangement in tall buildings with access control.
- Selected re-entry. Some codes let certain floors stay locked if others at set intervals are always open and signs in the stair say where. The conditions are detailed and local.
Tall buildings may also need a telephone or other two-way communication in the stair at set intervals when doors are locked. Short buildings sometimes get an easier rule. Do not choose among these yourself. Put the question to the authority having jurisdiction with a list of the stair doors, and build what they approve.
The right lock
The requirement "unlock but stay latched, and unlock when power fails" rules out most of the hardware you know.
| Hardware | Stays latched? | Unlocks without power? | For a stair door needing re-entry |
|---|---|---|---|
| Fail-safe electrified lock, fire-rated | Yes | Yes, the stair-side lever goes free | The usual choice |
| Fail-safe electrified trim on a fire-rated exit device | Yes | Yes | The usual choice where the door has a push bar |
| Fail-secure electrified lock or strike | Yes | No, it stays locked | Does not give re-entry |
| Fail-safe electric strike | No, the keeper swings free | Yes | The door is no longer latched, so it does not suit a fire door |
| Magnetic lock alone | No latch at all | Yes | Does not suit a fire door |
The Access Control lesson "Electric locks" said that a stair door is the place where the safe answer is fail-safe. Now you can see why. The fail-safe electrified lock keeps its latch in the frame at all times. Power holds the stair-side lever rigid. Remove the power, by the fire alarm relay, by the command center switch or by a power cut, and the lever turns freely.
The power for these locks passes through the fire alarm release exactly as lesson 3 described. The lock, the power transfer hinge and any door preparation must suit the door's fire label, so they are ordered with the door or fitted by people qualified to work on labeled doors.
What security gives up, and gets back
Fail-safe means the stair doors unlock in a power cut. Security dislikes that, with reason. The usual measures are:
- A battery on the lock power supply, so that a short power cut changes nothing. The fire alarm release still works through it.
- A door contact on every stair door, with alarms for a door forced or held open.
- A camera on the landings that matter.
- A clear event on the security screen, "stair doors released", so staff know to watch the stairs until the panel is reset.
Would this stair door do?
Six stair doors, your call
Each building is required to give re-entry on fire alarm. Decide whether the door as described would do, then read why.
Three examples
Simple: the three-story office
A small office building has two stairs. The tenant on the top floor wants the stair doors locked from the stair side. You ask the authority having jurisdiction, and they approve it on the condition that the doors unlock on fire alarm and power loss. Six fire-rated fail-safe locks go in, fed from one supply with a battery and a fire alarm relay. At the test, every stair-side lever goes free at once and every door is still latched.
Medium: the strike that passed for years
You take over a building where the stair doors have fail-safe electric strikes. On alarm the strikes release and the doors can be pushed open from the stair, so re-entry "works" and nobody questioned it.
But with the strike released, the latch is no longer held. In a fire, pressure can push the door open and let smoke into the stair. You report it to the owner in writing. The repair is new latching hardware listed for the door, and because these are labeled fire doors, the owner brings in the door supplier and the authority having jurisdiction.
Advanced: the tenant floors in a tower
A thirty-story tower has a different tenant on almost every floor. Each wants its stair doors locked. The base building design locks every stair-side lever with a fail-safe lock and releases them three ways: by the fire alarm, by a switch at the fire command center in the lobby, and by loss of power.
A new tenant's own security contractor then adds a second, fail-secure lock on its floor's stair doors "for after hours". That floor no longer gives re-entry, and nobody at the command center knows. It is found at the yearly test, when one door stays locked. Every tenant fit-out in a building like this needs the same review as the base building, and the test must touch every door.
From the field
- Test from inside the stair. Stand on the landing with the door closed behind you, have the alarm triggered, and try the lever. Then check the door is still latched by pushing it without turning the lever.
- Count the doors twice. Basement levels, the roof door and doors to mechanical floors are the ones left off lists.
- Carry a radio or a second person. A technician locked in a stair during a test is a tired old joke that still happens.
- Check the closers. Stair pressure fans can hold a door slightly open or make it slam. A door that does not latch defeats the whole stair.
- Read the signs in the stair. Floor numbers and re-entry signs are part of the approved arrangement. Do not cover them with your equipment.
Common mistakes
- Fitting fail-secure locks on stair doors because "stairs are a security risk".
- Using a fail-safe strike or a magnetic lock, which unlocks the door by unlatching it.
- Releasing the stair doors through controller software and not through lock power.
- Adding a second lock or bolt to a stair door after the building was approved.
- Putting any lock on the stair's exit door to the street that could stop people leaving.
Summary
- Into the stair is always free. Back onto a floor may be locked only where the code allows, and then it must unlock in an emergency.
- Re-entry saves people who meet smoke or a blocked exit in the stair.
- Stair doors are fire doors. They unlock without unlatching.
- A fire-rated fail-safe electrified lock, released through lock power, is the usual hardware.
- Which arrangement a building may use is decided by the authority having jurisdiction, not by the installer or the tenant.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Explain the difference between unlocked and unlatched.
Show answer
Exercise 2. In the third situation at the top, the people from floors 4 and 5 are standing above the smoke with every door locked. Name two things in the building's design that should have prevented it.
Show answer
Exercise 3. A building's stair doors have fail-safe locks with a four-hour battery on the supply. The mains fail for one hour with no fire alarm. Are the stair doors locked or unlocked from the stair side?
Show answer
Exercise 4 (think, don't memorize). A tenant on the ninth floor has had thefts by people coming in from the stair. They ask you to "do something about the stair doors". What do you propose, and what do you refuse?