PanelSimulator Academy

Fire Alarm Interface and Life Safety, lesson 4 of 10

Door holders and closing on alarm

So far the fire alarm has opened things. Here it does the opposite. Some doors stand open all day for convenience and must swing shut by themselves the moment there is a fire. This lesson explains how that is done safely, and what it means for the readers, locks and door contacts you fit on the same doors.

About 13 minutes. Read "The fire alarm relay" first, and "The door itself: frames, closers, hinges" in the Access Control course.

A pair of corridor fire doors, seen from above

Pick a situation, then play or step through.

Fire alarm relay magnetic holder wedge smoke detector corridor, seen from above door frame doors held open

The everyday picture

Think of the doors between the cars of a train, or the heavy door of a walk-in freezer. They are there to keep two spaces apart. But people pass through all day carrying things, and a door that must be pushed open every time soon gets propped with a box.

A propped door is no door at all. So the better answer is a door that stays open politely until the one moment it matters, then closes by itself without anyone having to remember. That is what a door holder tied to the fire alarm does.

What a fire door is for

A building is divided into compartments by fire-rated walls and floors. The idea is to keep fire and smoke in the compartment where they start for long enough that everyone else can leave. Smoke is the main killer, and it travels fast along corridors and up stairs.

Every opening in such a wall needs a fire door: a door, frame and hardware tested together and carrying a metal or printed label on the hinge edge. To do its job in a fire, the door must be two things:

  • Self-closing. A door closer shuts it every time, without help.
  • Positively latched. A latch bolt holds it in the frame so that heat and pressure cannot push it open. The trade calls this positive latching.

Some cross-corridor doors are smoke doors that need to close but not latch. The label and the door schedule say which is which. You do not have to rate doors yourself, but you must notice the label before you touch one.

Ways to hold a door open

MethodHow it worksAcceptable on a fire door?
Wall or floor magnetic holderAn electromagnet on the wall grips a steel plate on the door. Cut the power and the closer shuts the door.Yes, when listed for the purpose and released by the fire alarm or a nearby smoke detector
Closer with built-in electric hold-openThe closer body or its track holds the door at a set angle while powered.Yes, on the same conditions
Closer with its own smoke detectorOne unit above the door holds, senses smoke and releases without outside wiring.Yes, where the authority accepts it. Common in older buildings.
Mechanical hold-open arm, kick-down stop, hook, wedgeSomething physical keeps the door open until a person removes it.No. Nothing releases it in a fire.

A magnetic door holder looks like a magnetic lock's little cousin, and the difference is worth knowing. A magnetic lock holds with 600 pounds or more because its job is to resist a person. A door holder holds with something like 25 to 40 pounds, just enough to beat the closer. Anyone can pull the door off it by hand, which is the manual way to close the door. The current is small too, often a few hundredths of an amp at 24 volts. Check the data sheet.

What makes the holder let go

The holder is powered through a contact that the fire alarm system controls, in the same closed-at-rest way as the lock release in the last lesson. Three things drop the door:

  • Smoke detection. Either detectors placed near the doors for this purpose, or the building's general alarm, as the fire alarm design decides.
  • Loss of power. The magnet is fail-safe by nature. No power, no hold.
  • A person pulling the door.

The fire alarm designer decides which detectors release which doors. In some buildings a detector on either side of the opening closes only that pair. In others, any alarm closes every held door in the building. As always, it is written in the sequence of operations.

Who wires the holders? Usually the fire alarm contractor or the electrician, with power from a supply meant for the job. If the work is offered to you, take it only by written agreement, with listed parts, and with the release contact provided by the fire alarm contractor. Never feed a holder from a spare output so that it "just stays on".

Check yourself

The power to a wall magnetic holder fails on an ordinary afternoon. What does the fire door do?

Where security meets these doors

Held-open doors and access control often share an opening. A corridor door might stand open in office hours and be a card-controlled door at night. Four points come up again and again.

PointThe problemThe usual answer
Door contactA door on a holder is open for hours. The access system reports "door held open" all day.Put the door on a schedule that expects it open in those hours, or use the holder's state as a reason to quiet the alarm.
Night modeSecurity wants the door closed and locked after hours.A timed contact, in series with the fire alarm contact, drops the holder at closing time. The fire alarm contact still comes first.
After releaseThe door closes in an alarm. Is anyone now stuck behind it?The way out must be free by a lever or push bar. Check each direction that is an exit route.
Locks on the doorElectric locks, strikes and cut-outs can spoil the door's rating.Use hardware listed for fire doors, and do not drill or cut a labeled door or frame beyond what its listing allows.

The night-mode row deserves care. Your timer may cut holder power so the doors close in the evening. It must never be able to supply power around the fire alarm contact. Wire the two contacts in a row, so that either one opening drops the door.

Check a door

Describe a fire door and see what is wrong with it

    Three examples

    Simple: the school corridor

    A school has pairs of doors across its main corridor, held open by wall magnets so that classes can move freely. When a detector operates, the fire alarm relay opens, the magnets let go and the closers bring both leaves shut. Children can still push through them on the way out, and the doors close again behind each group. Nothing of yours is on these doors, but you run a cable past one. You keep it clear of the swing and you do not fix anything to the door or its frame.

    Medium: the alarm that cried all day

    An office suite door stands open on a holder from 8 a.m. to 6 p.m. and is card-controlled at night. The security desk gets a "door held open" alarm every morning at 8:01 and has learned to ignore that door entirely.

    An alarm that is always ignored protects nothing. You set the door to an unlocked schedule for office hours, so the system expects it to be open. At 6 p.m. a timed contact drops the holder, the door closes and latches, and from then on a held-open alarm means something.

    Advanced: the lab that wanted both

    A laboratory corridor has fire doors on holders. The lab manager wants them open in the day, locked with card access at night, and locked at once if a security alarm is raised.

    The design uses a fire-rated electrified lock with a free inside lever, so egress is always mechanical. The holder circuit runs through three contacts in a row: the fire alarm relay, the night timer and a lockdown output from the access system. Any one of them opening lets the closer shut the door. None of them can keep the holder on by itself. The fire alarm contractor provides and tests their contact, and the authority having jurisdiction sees the drawing before anything is ordered, because the door is rated and on an exit route.

    From the field

    • Look for the label first. It is on the hinge edge of the door and inside the frame. If it is there, treat every hole as a question for someone else.
    • Watch the door close from fully open. It should shut and latch without a slam and without stopping short. A door that does not latch from the holder position has a closer or latch problem.
    • Paired doors need to close in order. Where one leaf overlaps the other, a small device called a coordinator makes the right leaf wait. If it is bent or missing, the pair jams open.
    • Mind the floor. New carpet, a mat or a cable cover under a held-open door can stop it closing. Report it.
    • Expect yearly inspection. Fire door assemblies are generally required to be inspected and tested on a regular schedule. Your hardware will be looked at then too.

    Common mistakes

    • Wedging a fire door, or leaving the customer's wedge in place while you work and after you leave.
    • Feeding a door holder from a supply that the fire alarm cannot interrupt.
    • Using a magnetic lock as a door holder, or a door holder as a lock.
    • Cutting an unrated strike or a cable hole into a labeled door or frame.
    • Leaving a held-open alarm that sounds all day, so the door is ignored.
    • Forgetting to check that people can still get out once the doors have closed.

    Summary

    • Fire doors must close by themselves and, in most cases, latch. Held open by anything that cannot release, they are useless.
    • A listed magnetic holder or closer hold-open keeps the door open and releases on smoke detection, power loss or a pull by hand.
    • The fire alarm contractor provides the release contact, and the fire alarm design decides which detectors close which doors.
    • Security can add its own reasons to close a door, in series, but can never keep a holder powered against the fire alarm.
    • After the doors close, every exit direction must still open with one motion.

    Exercises

    Answer each one yourself first, then open the answer.

    Exercise 1. Name the two things a fire door must do by itself in a fire.

    Show answer
    Close, which the door closer does, and latch, which the latch bolt does. Together they keep the door shut against heat and pressure. Some smoke doors only need to close.

    Exercise 2. In the fourth situation at the top, one leaf is wedged. What does the alarm achieve at that opening?

    Show answer
    Very little. The holders release and one leaf closes, but the wedged leaf stays open and smoke passes into the rest of the corridor. The fire alarm did its part. The wedge defeated it.

    Exercise 3. A night timer and the fire alarm relay both control one door holder. Should their contacts be wired in a row, one after the other, or side by side?

    Show answer
    In a row, which is called series. Then either contact opening removes power from the holder. Side by side, which is called parallel, the timer contact could keep the holder powered while the fire alarm contact is open, and the door would stay open in a fire.

    Exercise 4 (think, don't memorize). A clinic asks you to fit a magnetic lock at the top of a held-open corridor fire door, so that it can be "held open in the day and locked at night with one device". What do you say?

    Show answer
    That one magnet cannot do both jobs, and neither job would be done properly. A holder is on the wall and releases to let the door close. A magnetic lock is on the frame and holds the door shut, and it gives no latching, so the fire door would not be positively latched. It would also make the exit depend on electricity. Suggest keeping the listed holder, and locking the door at night with fire-rated latching hardware that leaves the exit side free. Because the door is rated and on an exit route, the authority having jurisdiction should see the plan.