Fire Alarm Interface and Life Safety, lesson 3 of 10

The fire alarm relay

One small relay and two wires join the fire alarm system to your door locks. It is the simplest circuit in the building and the one you can least afford to get wrong. This lesson shows what the relay is, who owns each side of it, and how to wire your side so that every fault ends with the door free.

About 14 minutes. Read "How a fire alarm system works" first, and "Power supplies and batteries" in the Access Control course.

Follow the relay circuit

Pick a situation, then play or step through.

fire alarm contractor's side security installer's side contact closed at rest loop from the fire panel Relay module contact at rest agreed terminals two-wire cable Lock power supply fire alarminput output on Lock held

The everyday picture

Think of the guard on a paper shredder or a food mixer. A small switch sits under the lid. While the lid is closed, the switch is pressed and the motor may run. Lift the lid, and the motor stops. Pull the switch's wire off, and the motor also stops.

The designer chose that on purpose. The machine runs only while a complete circuit says "all is well". Anything that interrupts the circuit, whether the lid, a loose wire or a broken switch, gives the safe result.

The fire alarm relay works the same way. Your locks are allowed to hold only while a closed circuit from the fire alarm says "no alarm". Break that circuit for any reason and the doors go free.

The parts of the link

A relay is a switch worked by electricity. The "Electric locks" lesson in the Access Control course showed one inside the controller. This one belongs to the fire alarm system. It is usually a small addressable relay module on the fire alarm loop, placed close to the equipment it controls. The fire code calls what it does an emergency control function.

The module offers a dry contact: a pair of terminals that are either joined or not, carrying no voltage of their own. Your equipment supplies the small current that passes through them. This keeps the two systems electrically separate. No power crosses from one to the other, and a short circuit on your side cannot disturb the fire alarm loop.

PartWho provides and wires itNotes
Relay module and its loop wiringFire alarm contractorListed fire alarm equipment. Its wiring back to the panel is watched for faults.
Program that decides which alarms operate itFire alarm contractorWritten down in the sequence of operations.
Contact terminalsThe demarcation pointAgree which terminals, and who lands the wires on them. Many fire alarm contractors insist on doing it.
Two-wire cable to the lock power supplySecurity installerKeep it short, in its own cable, and out of harm's way.
Lock power supply with a fire alarm inputSecurity installerListed for access control use, with a release input made for this job.

Fire alarm rules commonly ask for the relay to sit within about 3 feet of the equipment it controls, so that the unwatched wire between them is as short as possible. The fire alarm contractor will know how the local authority reads that. It is the reason the module usually ends up beside your power supply cabinet and not in the fire panel room.

Wired to fail safe

Most lock power supplies have a pair of terminals marked for a fire alarm input. The supply sends a tiny sensing current out of one terminal and expects it back at the other. While the loop is complete, the lock outputs stay on. When the loop opens, the supply switches off the outputs you have chosen.

So the fire alarm contact is wired to be closed in normal times and open in alarm. Step through the first two situations at the top. An alarm and a cut cable look identical to the power supply, and both free the door.

The third situation shows the opposite choice: a contact that is open in normal times and closes to say "release". It works on the bench. But a wire that falls off, a loose screw or a failed module is now silent, and the first anyone knows of it is a door that stays locked during a fire.

What goes wrongContact closed at rest (right)Contact open at rest (wrong)
Fire alarm soundsLock releasesLock releases, if everything is intact
Cable between relay and supply is cutLock releases. Someone notices the same day.Nothing happens. Lock will not release in a fire.
A terminal screw works looseLock releasesNothing happens. Lock will not release in a fire.
Cable is crushed and its two wires short togetherLock will not release. Protect the cable and test it.Lock releases

The last row is honest about the weak spot. No two-wire loop covers every fault, which is why the cable is kept short and protected, and why the link is tested on a schedule. Some fire alarm contractors and authorities ask for the relay to be held energized in normal times, so that a dead module also drops out. Follow their lead.

Check yourself

Where should the fire alarm relay's contact be connected?

Telling the controller as well

The release must not depend on the controller, but the controller should still know about it. Otherwise it reports every released door as forced open. Many relay modules have a second set of contacts, and many power supplies have a "fire alarm active" output. Wire one of those to a controller input, and set the software to log the event and quiet the door alarms. This is a copy for information only. The power is already off.

Which doors, and for how long

Not every lock in the building belongs on the release. Removing power from a fail-secure lock would do nothing useful, and a door with a free inside lever lets people out already.

  • Released: locks on exit routes that need electricity to let people out, mainly magnetic locks, plus delayed and controlled exits and any stair doors that must unlock. Later lessons cover those.
  • Usually left alone: fail-secure strikes and locks on doors with a mechanical inside lever or push bar.
  • Decided by the authority having jurisdiction: everything in between. Give them a door list and let them mark it.

Ask two more questions and write down the answers. First, which alarms operate the relay: any alarm in the building, or only some? Second, when do the doors lock again? Codes generally expect released locks to stay released until the fire alarm panel has been reset, and silencing the horns is not a reset. Some power supplies relock by themselves when the contact closes again. Others can be set to stay off until a person presses a reset button at the cabinet. The authority may prefer one or the other.

Can the contact carry it?

A relay module's contact is small. Its data sheet gives a rating, often around 2 amps at 30 volts DC for a simple load and less for a coil such as a lock. There are two ways to use it. Try both.

Check the load on the fire alarm contact

total lock current
current through the fire alarm contact

The first method is the normal one. The contact carries only the supply's sensing current, a few thousandths of an amp, however many locks hang on the outputs. When several cabinets must release, each has its own input. They are fed either from one contact each, or from one contact through a small listed relay that repeats it, as the supply's instructions describe.

Three examples

Simple: one glass entrance

A shop has two magnetic locks on its entrance, fed from one power supply. The fire alarm contractor mounts a relay module beside the cabinet and programs it to operate on any alarm. You run two wires, about two feet long, from the contact to the supply's fire alarm input, and set the supply so both lock outputs drop when the loop opens. At the joint test, a pull station is operated and both doors swing free.

Medium: the door that relocked too soon

During a test in an office, the horns are silenced so people can hear each other, and the lobby locks snap back on while the panel still shows an alarm. The fire alarm contractor checks the program. The relay had been set to follow the horns, so it returned to rest when they were silenced.

They change the program so the relay stays operated until the panel is reset. Nothing on your side was wrong, but it was your test that found it. This is why the test includes the sentence "silence the horns and check the doors again".

Advanced: three cabinets and a software shortcut

A building has lock power supplies on three floors. To save cable, the first installer landed the fire alarm contact on one controller input and wrote a software rule: "when input 8 is active, unlock all doors". It passed its first test.

Two years later a network switch fails. The controllers on floors two and three no longer hear the first one. An alarm on that day would have released one floor only. The repair is to do it properly: the fire alarm contractor adds a relay module at each cabinet, each wired straight to its supply's fire alarm input. The software rule is kept for logging only. Then all three floors are tested with the network unplugged, to prove that the release no longer needs it.

From the field

  • Read the power supply's instructions for the fire alarm input. Some want a closed contact, some can be set either way with a jumper, and a few expect a voltage. Set it to release on an open loop.
  • Label both ends. "Fire alarm release. Do not disconnect." Add the relay module's address if the fire alarm contractor gives it to you.
  • Pull one wire off as a test. With the fire alarm contractor's agreement, lift your wire at your own terminal. The locks must drop. If they do not, the wiring is the wrong way round.
  • Check which outputs follow the input. On many supplies each output has its own switch for this. One missed switch is one door that stays locked.
  • Do not put the removable jumper back. Supplies ship with a wire link across the fire alarm input so they work on the bench. Once the real loop is on, that link goes in the bin.

Common mistakes

  • Making the release a software rule in the controller or server.
  • Using a contact that closes on alarm, so a broken wire goes unnoticed.
  • Leaving the factory link across the fire alarm input.
  • Running lock current through a contact that is too small for it.
  • Connecting to the horn circuit to "borrow" an alarm signal. That circuit belongs to the fire alarm system and is not yours to tap.
  • Releasing when the horns sound and relocking when they are silenced.

Summary

  • A fire alarm relay module offers a dry contact close to your lock power supply.
  • The contact is closed at rest and opens on alarm, so an alarm and a broken wire both release the locks.
  • It acts on lock power directly. The controller is told separately, for the record.
  • The fire alarm contractor owns the module and its program. You own the wire from the agreed terminals onward.
  • Which doors release, on which alarms, and when they relock are settled with the authority having jurisdiction and written down.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. What is a dry contact, and why does it suit a link between two separate systems?

Show answer
A pair of terminals that are simply joined or not joined, with no voltage of their own. The receiving equipment supplies the small current. No power passes between the systems, so a fault on the security side cannot disturb the fire alarm loop.

Exercise 2. Six magnetic locks draw 0.5 amps each. What current would pass through a contact wired in series with all of them, and is a contact rated 2 amps enough?

Show answer
6 times 0.5 is 3 amps, which is more than 2 amps, so no. Locks are coils, which makes it worse. Use the power supply's fire alarm input, where the contact carries only a sensing current.

Exercise 3. After the horns are silenced during a real alarm, should the released doors lock again?

Show answer
No. Silencing only quiets the horns while the alarm condition remains. Released doors generally stay released until the fire alarm panel is reset by someone authorized to do it.

Exercise 4 (think, don't memorize). You take over a site and find the fire alarm contact wired to a controller input, with a software rule that unlocks the doors. It passed last year's test. What do you tell the customer?

Show answer
That it works only while the controller, its program and possibly the network are healthy, and a fire is exactly the day they may not be. A test on a good day does not prove it. Recommend rewiring so the contact removes lock power at the supply, keeping the controller input for logging, and doing the work and the retest together with the fire alarm contractor. Until then, tell the building owner about the weakness in writing.