PanelSimulator Academy

Fire Alarm Interface and Life Safety, lesson 2 of 10

How a fire alarm system works

You will never wire a fire alarm system, but you will work beside one on every job and connect to one on many. This lesson gives you enough of its language to read a fire panel's lights, talk to the fire alarm contractor, and understand what is on the other end of the relay.

About 14 minutes. Read "Two systems, one building" first.

Set off the system and watch what it does

Pick an event. The panel's lamps, the horns and the outputs react.

Fire alarm panel Alarm Supervisory Trouble Mains power panel buzzer off batteries smoke detector pull station waterflow switch valve switch detection loop horns and strobes Monitoring station nothing sent Relay modules at rest door release, door holders, elevator recall, fans
kind of signal
are people told to leave?
who is called

The everyday picture

Think of a small school before electricity. A teacher smells smoke and runs to the office. The office rings the hand bell in the corridor, and sends a child to fetch the fire brigade. On the way out, someone closes the doors to the hall.

That is a complete fire alarm system. Someone senses the fire. A central point decides it is real. Everyone is warned. Help is called. A few things in the building are done automatically. A modern system has the same five jobs, done by wire and done in seconds.

The parts

The trade has a name for each job. You will hear these names on every site.

JobTrade nameWhat you will see
Sense the fireInitiating devicesSmoke detectors and heat detectors on ceilings. Red manual pull stations beside exits. Switches on the sprinkler pipes.
DecideFire alarm control panel, or control unitA red or gray locked cabinet with a small display, a few lamps and its own batteries.
Warn peopleNotification appliancesHorns, strobe lights, and speakers that play a voice message.
Call for helpCommunicator to a supervising stationA phone, cell or network link from the panel to a monitoring company, which calls the fire department.
Act on the buildingRelay modules, or control modulesSmall boxes near doors, elevators and air handlers. One of these is where you connect.

A manual pull station is the handle a person pulls when they see a fire. In some countries it is called a call point. Its handle sits roughly 42 to 48 inches above the floor so that most people can reach it, and one is normally found near each exit.

Detectors on a smooth ceiling are commonly spaced about 30 feet apart, but beams, slopes and air vents change that. Their positions are worked out by the fire alarm designer. This is why you never move one.

The warning itself is standardized. An evacuation horn sounds three pulses, a pause, then three pulses again. Strobes flash about once a second for people who cannot hear the horn. In larger buildings, speakers give spoken instructions.

Its own power

A fire alarm panel is fed from a dedicated mains circuit and carries its own batteries. A common requirement is enough battery to run quietly for 24 hours and then sound the alarm for 5 minutes, with more for voice systems. The fire alarm designer does that sum and the authority having jurisdiction checks it. Your equipment never draws from that supply.

Three kinds of signal

A fire panel reports three different kinds of event. Mixing them up is the most common way for a newcomer to sound lost.

SignalIt meansTypical causesWhat happens
AlarmThere may be a fireSmoke or heat detector, pull station, water flowing in the sprinkler pipesHorns and strobes operate, the fire department is called, relays operate
SupervisoryA fire protection system is not readySprinkler valve closed, low air pressure in a dry sprinkler system, fire pump without powerLamp and buzzer at the panel, monitoring company told. No evacuation.
TroubleThe fire alarm system itself has a faultBroken wire, wire touching ground, detector removed, mains lost, weak batteryLamp and buzzer at the panel, monitoring company told. No evacuation.

Only an alarm makes your doors release. A supervisory or trouble signal changes nothing at the door, but it does mean the building is less protected than it should be until someone fixes the cause.

Check yourself

A yellow lamp marked "Trouble" is lit and the panel is beeping. What is the panel telling you?

Wiring that watches itself

In a security system, a cut cable to a reader may go unnoticed until someone complains. A fire alarm system is not allowed to work that way. Every circuit is checked continuously, and a break or a short to ground raises a trouble signal within moments. The trade calls this monitoring for integrity, and older hands call it supervision.

You will hear three circuit names.

  • Initiating device circuit. A pair of wires with ordinary detectors and pull stations along it, and a resistor at the far end. A small current always flows through the resistor. If the current stops, a wire has broken. If it jumps, a device has gone into alarm. The panel knows only which circuit, called a zone.
  • Signaling line circuit. A data loop where each device has its own address, like the readers on a data bus in the Access Control course. The panel polls each device in turn and can say "smoke detector, third floor, east corridor". Most new systems are addressable like this.
  • Notification appliance circuit. The pair that feeds horns and strobes. It is checked with a small reverse current while quiet, then driven hard in alarm.

Relay modules sit on the signaling line circuit as addressed devices. The panel's program decides which alarms operate which relays. That program is sometimes written out as a table called a sequence of operations. Lesson 9 uses it as the test sheet.

Sort the signals

Alarm, supervisory or trouble?

Decide what kind of signal each event produces, then read why.

What this means for your work

  • Keep clear of detectors and strobes. A camera housing, a sign or a cable tray must not shade a detector from smoke or hide a strobe from view.
  • Never share a path. Fire alarm cable has its own conduit, boxes and supports. Your cable does not ride in them or get tied to them.
  • Expect the release to follow the program. In some buildings every alarm releases every listed door. In others, only alarms in certain areas do. Ask the fire alarm contractor which, and get it in writing.
  • Know who may touch the panel. Acknowledge, silence and reset are for the building's trained staff, the fire alarm contractor and the fire department.

Three examples

Simple: the accidental pull

A delivery driver backs a cart into a pull station and the handle drops. The whole building goes into alarm and the exit locks release, as they should. The alarm cannot be cleared from the panel until the pull station itself is reset with its key. Your part is to check, after the panel is reset, that every released door has locked again.

Medium: the yellow lamp after lunch

You spend the morning pulling cable above a corridor ceiling. After lunch the building manager says the fire panel is beeping and shows a trouble on the third-floor loop. You remember your fish tape snagging on something.

You say so at once. The fire alarm contractor finds a detector cable pulled out of its terminal above the ceiling where you worked. It takes ten minutes to fix because you told them where to look. Kept quiet, it could have cost them a day, and the detectors beyond the break may have been dead the whole time.

Advanced: the valve nobody opened

During a renovation, a plumber closes a sprinkler valve to move a pipe. The panel shows a supervisory signal. The monitoring company phones the site, someone says "we know, it's the building work", and the lamp stays lit for three weeks.

Nothing in your system reacts to this, and that is the lesson. A supervisory signal releases no doors and sounds no horns, yet part of the building has no sprinkler protection. If you notice a supervisory or trouble lamp that everyone has learned to ignore, mention it to the building manager. It costs you one sentence.

From the field

  • Look at the fire panel when you arrive and when you leave. If it was quiet in the morning and shows a trouble in the evening, your work is the first suspect.
  • Dust and steam set off smoke detectors. Cutting drywall, sanding and soldering near one need the building's permission and its arrangements first.
  • Red cable is a convention, not a law. Plenty of fire alarm cable is another color. Read the printing on the jacket.
  • A relay module has two sides. The loop side is fire alarm. The contact side is the only part you connect to, and only where agreed.
  • Ask for the device address of "your" relay. Written on your drawing, it saves an hour of hunting at every future test.

Common mistakes

  • Calling every lamp on the panel "an alarm".
  • Assuming a trouble signal will release the doors, or that it does not matter because it did not.
  • Mounting equipment that blocks a strobe or crowds a detector.
  • Silencing a beeping panel to get some peace.
  • Believing that all alarms release all doors without asking how the panel is programmed.

Summary

  • A fire alarm system senses, decides, warns, calls for help and acts on the building.
  • Initiating devices report to the panel. Notification appliances warn people. Relay modules act on doors, elevators and fans.
  • Alarm means possible fire. Supervisory means a protection system is not ready. Trouble means the fire alarm itself has a fault.
  • Every circuit is watched, so damage you cause will show at the panel.
  • Only an alarm operates the relay you connect to, and the panel's program decides which alarms.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. Name the five jobs of a fire alarm system and one device for each.

Show answer
Sense: a smoke detector, heat detector, pull station or waterflow switch. Decide: the fire alarm control panel. Warn: horns, strobes or speakers. Call for help: the communicator to the supervising station. Act on the building: relay modules for doors, elevators and fans.

Exercise 2. In the tool at the top, which two events light the Trouble lamp, and do the horns sound for either?

Show answer
A broken wire and loss of mains power. The horns do not sound for either. The panel buzzes, the monitoring company is told, and the system keeps working as far as it can, on batteries in the second case.

Exercise 3. Why does water flowing in a sprinkler pipe count as an alarm, while a closed sprinkler valve is only supervisory?

Show answer
Water flows when a sprinkler head has opened, which normally means heat from a fire. That is evidence of fire, so it is an alarm. A closed valve is not a fire. It means the sprinklers would not work if one started, so it is reported as a protection system that is not ready.

Exercise 4 (think, don't memorize). A customer asks why the magnetic locks did not release when the fire panel "went off" last night. The panel log shows a low battery trouble at 2 a.m. What do you tell them?

Show answer
The system worked as designed. A trouble signal reports a fault in the fire alarm system and is not a fire alarm, so no horns sound and no relay operates. The beeping they heard was the panel's own buzzer. The right response is to call the fire alarm contractor about the battery. If they want proof that the locks do release on a real alarm, that is a joint test, arranged with the fire alarm contractor.