Fire Alarm Interface and Life Safety, lesson 1 of 10
Two systems, one building
Almost every building you work in has a fire alarm system as well as your security system. They share walls, ceilings and doors, yet they are built under different rules by different people. This lesson shows why they are kept apart, the one place they are joined, and which one wins when they disagree.
Two systems at one exit door
Pick a situation, then play or step through. The exit door is held by a magnetic lock.
The everyday picture
Think of a road junction with traffic lights. The lights run the junction all day, and drivers obey them. Then a fire engine arrives with its siren on. Everyone stops, whatever color the light shows, and the fire engine goes through.
Nobody rewired the traffic lights to make that happen. The fire engine does not ask the lights for permission, and the lights cannot tell the fire engine to wait. They are separate arrangements with a clear rule about which one comes first.
A building works the same way. The security system runs the doors every day. The fire alarm system is the fire engine. When it speaks, the security system gives way, and nothing the security system does can make the fire alarm wait.
Why they are separate
The two systems have different jobs. A fire alarm system notices a fire and tells people to leave. A security system decides who may come in and notices people who should not be there. One protects lives from a danger inside the building. The other mostly protects property from people outside it.
Because lives depend on it, the fire alarm system is built under much stricter rules. In the United States those rules are found mainly in NFPA 72, the National Fire Alarm and Signaling Code, and in the building and fire codes that each state or city adopts. The details change with the edition and the place, which is why this course keeps sending you to the authority having jurisdiction, or AHJ: the official who decides what the rules mean for one building.
| Fire alarm system | Security system | |
|---|---|---|
| Job | Detect fire, warn people, start the building's fire responses | Control entry, detect intruders, record events |
| Who may work on it | A fire alarm contractor, licensed or certified as the state requires | A security installer, licensed as the state requires |
| Equipment | Every part is tested and listed for fire alarm use | Listed for security use, a different set of tests |
| Wiring | Watched all the time. A broken or grounded wire shows as a fault at the panel. | Some circuits are watched, many are not |
| Changes | Rare. Usually need plans, a permit and a witnessed test. | Frequent. People, schedules and software change every week. |
| Depends on a network or server | Not for its basic job | Often |
Look at the last two rows. A security system is always being changed, and it leans on computers and networks that go down for updates. If the fire alarm were one of its features, every badge change and every software update would be a chance to break it. Keeping the systems separate means a bad day for security is never a bad day for fire safety.
This is also the reason for the firmest rule in this course. A security installer does not open, wire, program, silence or move fire alarm equipment. You work up to an agreed set of terminals, and the fire alarm contractor works on the other side.
Which one wins
When the two systems want different things, life safety comes first. The door in the drawing at the top shows how this is made certain. The fire alarm does not send a request to the access controller. It operates a relay that removes power from the lock. The controller is not asked, so it cannot refuse, and it cannot fail in a way that matters.
Notice the direction. The link runs from the fire alarm to the security system and never back. A security system must not be able to silence a horn, reset the fire panel or hold a door shut against it.
The order of importance that designers use looks like this:
- People can get out. Free egress, covered in the Access Control course.
- The fire alarm's actions happen. Locks release, held-open doors close, elevators return.
- Security is kept as far as the first two allow.
Good design makes the third item cost very little. A door with a mechanical lever on the inside and a fail-secure lock stays locked to the street during a fire alarm, and everyone inside still leaves with one push. Security loses nothing. The trouble starts with locks that need electricity to let people out.
Check yourself
The access control server is offline for an update when the fire alarm sounds. What happens to the magnetic locks on the exits?
Where they touch
The systems are separate, but a building needs them to cooperate in a handful of places. Each meeting point is a small, deliberate connection, and each one has its own lesson in this course.
| Meeting point | What the fire alarm does | What it means for you |
|---|---|---|
| Locked exit doors | Operates a relay that releases chosen locks | Your lock power must accept that relay and obey it |
| Fire doors held open | Releases the holders so the doors swing shut | Your readers and locks must still work on a door that now closes |
| Stairwell doors | Unlocks them from the stair side | The lock must be the right kind, and stay latched |
| Elevators | Sends the cars to a chosen floor | Card readers in the car stop deciding where it goes |
| Voice messages and lockdown | Shares or overrides speakers and signals | A lockdown plan cannot block the way out |
In every row the fire alarm contractor provides a contact or signal, and you connect your own equipment to it. The point where their work stops and yours starts is called the demarcation point. Agree where it is before the job, in writing. It is usually a pair of terminals on a relay.
Whose job is it?
Customers do not see two systems. They see one building and one person with a ladder, so they ask you for things that are not yours to do. Pick a request and see how to answer it.
The customer asks you to...
Three examples
Simple: the detector in the way
You are fitting a camera in a corridor and the best spot on the ceiling is one foot from a smoke detector. The building manager says to shift the detector along a little. You do not. Detector positions come from the fire alarm design, and moving one is fire alarm work that may need approval. You mount the camera where it does not crowd the detector, and you tell the manager why.
Medium: the two-way wish
A security manager wants the two systems "fully integrated". Fire alarms should appear on the security workstation, and a forced door should sound the building's horns to scare off the intruder.
The first half is possible. The fire alarm contractor can provide a spare contact that closes on alarm, and you wire it to an input so the security screen shows an event. The fire panel and its own monitoring remain the official record. The second half is refused. A security event must never sound the fire alarm. People would learn to ignore the horns, and the link would run the wrong way. A separate security sounder does the job.
Advanced: one box, two systems
A small shop has a single panel that handles both burglar alarm and fire alarm. These combination panels exist and are listed for both uses. The owner assumes that, since it is one box, the alarm company's security technician can add a smoke detector while fitting a new door contact.
The box is shared but the rules are not. The fire part is still a fire alarm system: its signals take priority inside the panel, its circuits and batteries follow fire alarm rules, and work on it needs someone qualified for fire alarm, plus whatever permit the city requires. A company that holds both qualifications can do both jobs. A technician who holds only one does only that one.
From the field
- Learn what fire alarm equipment looks like. Red boxes, red cable in many buildings, and devices marked "fire". If you are unsure whether a cable or box is fire alarm, treat it as if it is.
- Get the fire alarm contractor's name on day one. The building manager has it, and there is usually a sticker inside the panel door or beside it.
- Protect detectors from your dust, with permission. Drilling under a smoke detector can set it off. Ask the building who arranges covers or a temporary disable. Do not do it yourself.
- Write the demarcation point on the drawings. "Relay provided and wired by fire alarm contractor. Security installer connects at terminals 1 and 2."
- If you damage a fire alarm cable, stop and report it at once. The panel will show a fault. Hiding it leaves part of the building unprotected.
Common mistakes
- Treating the fire alarm as another input to the access software, so the release depends on the server.
- Opening the fire panel "just to find a spare contact".
- Sharing a power supply, a battery or a cable between the two systems.
- Letting a security event sound fire alarm horns or strobes.
- Assuming one combined panel means one set of rules.
Summary
- Fire alarm and security are separate systems with separate rules, equipment and trades.
- Life safety wins. The fire alarm acts on locks directly and does not ask the security system.
- The link runs one way, from fire alarm to security, usually through one relay.
- Security installers work up to the demarcation point and never on fire alarm equipment.
- The authority having jurisdiction and the fire alarm contractor decide the details for each building.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Give two reasons the fire alarm is not simply built as a feature of the security system.
Show answer
Exercise 2. In the drawing at the top, which cable crosses the dashed line, and who installs the part on the left of it?
Show answer
Exercise 3. A guard asks whether the access system can be set to keep the lobby magnetic locks holding during a fire alarm if a robbery is in progress. What is the answer?
Show answer
Exercise 4 (think, don't memorize). You are running cable above a ceiling and find an unlabeled gray box with a red cable entering it, exactly where your cable tray needs to go. What do you do?