Installation, Commissioning and Maintenance, lesson 10 of 10
Fault finding
Some technicians find faults quickly and others change parts until the problem goes away. The difference is rarely knowledge of the equipment. It is method: a way of asking questions so that every answer removes half of the possibilities. This last lesson gives you that method and shows it working on the kind of fault that has already beaten two other people.
Find the break in as few measurements as you can
A lock is dead. The supply shows 24 volts and the lock shows none. Choose where to put the meter. Three is the fewest that always works.
The everyday picture
Someone thinks of a number between 1 and 100 and you have to find it. You could ask "Is it 1? Is it 2?" and need up to a hundred questions. Or you could ask "Is it more than 50?" and throw away half the numbers with one answer. Seven questions of that kind always find it.
The first way feels like progress, because each question is easy. The second way needs a moment of thought before each question, and finishes ten times sooner.
Fault finding is that game. The fault is hiding somewhere in a chain of parts. Guessing parts one at a time is "is it 1, is it 2". A good test is one whose answer, either way, rules out a large share of the chain.
A method in seven steps
- Pin down the symptom. "The door is broken" is not a symptom. "Door 9 does not release for any card, since Monday, and the reader beeps and shows green" is. Ask what exactly happens, where, when, how often, and since when.
- Ask what changed. Systems that worked yesterday do not fail at random. A power cut, building work, a software update, a new member of staff, a change in the weather: the answer is often in the reply to "what was different on Monday?".
- See it yourself. Reproduce the fault. Descriptions passed along by three people lose the important detail.
- Check the cheap and obvious first. Is it powered? Is it plugged in? Is the fuse whole? Is there a trouble message already on the screen? Is the person's card simply expired?
- Split the chain. Follow the path the signal or power takes, and test near the middle. The next section shows how.
- Change one thing at a time, and test after each change. If you change three things and the fault goes, you do not know which one mattered, and you may have added a new fault that is masked for now.
- Fix the cause, prove the fix, and write it down. A blown fuse is a symptom. Why it blew is the cause. Repeat the original test, then check that nothing nearby was disturbed, as in lesson 7. Record what you found in the service log from lesson 9.
Splitting the chain
Every function in a security system is a chain. For a lock: supply, fuse, relay, terminal, cable, splice, frame, hinge, lock. For a camera picture: camera, cable, switch port, network, recorder, screen. Something goes in at one end and should come out at the other.
The technique is called half-splitting. You know the chain is good at the start and bad at the end. Measure at a point near the middle.
- If the reading is good there, everything before that point is cleared. The fault is in the second half.
- If the reading is bad, the fault is in the first half.
Then split the remaining half again. Each measurement halves the search. A chain of eight points takes three measurements. A chain of sixty-four takes six. Try it in the tool at the top, then try starting from one end and count the difference.
Two refinements make it practical. First, weigh the split by effort: a test point in the cabinet at eye level is cheaper than one above a ceiling, so take the easy reading first when it still removes a good share. Second, weigh it by likelihood: joints, moving parts and anything recently touched fail far more often than the middle of a cable.
The companion technique is substitution. Swap a suspect part with an identical one that is known to work, and see whether the fault moves with the part or stays in place. If two readers are swapped between two doors and the fault stays at the same door, the reader is cleared and the cable or the port is not. A swap is one clean question. Swapping in new parts without that question in mind is guessing with a credit card.
Check yourself
A reader is dead. You swap it with the working reader from the next door. The dead position is still dead and the swapped reader works next door. What is cleared?
Reading the pattern
Before measuring anything, look at how wide the fault is. The shape of a failure points at what the failed things share.
| What has failed | Look first at |
|---|---|
| One device | That device, its cable and its terminations |
| Every device on one controller | That controller, its power and its network connection |
| Every device in one cabinet | The cabinet's supply, its mains circuit and its fuses |
| Everything on one floor or one network switch | The switch, its power and its uplink |
| The whole system, devices still working locally | The server, the database or the main network |
| One person at every door | That person's card or access level, not the doors |
| Every person at one door | The door, not the people |
The event log from "Events, alarms and monitoring" in Access Control is your first instrument here. It tells you when each device went offline, in what order, and what happened just before.
Faults that come and go
An intermittent fault is one that is absent when you arrive. It is the hardest kind, because you cannot split a chain that is working. The approach changes from measuring to collecting evidence.
| The fault appears | Suspect |
|---|---|
| At the same time each day | A schedule in the software, or other equipment that starts then: heating, an elevator, a shift change loading the power supply |
| In rain, or on cold or hot days | Water in a box or conduit, a joint that opens as metal shrinks, a cabinet overheating in the sun |
| When a door moves or slams | A wire flexing in the hinge or door cord, a loose termination, a door contact at the edge of its gap |
| When something nearby switches on | Electrical noise picked up by a cable, or a shared supply dipping |
| More often as months pass | Corrosion, a failing battery, a wearing mechanical part |
Some practical moves:
- Mine the log. List every occurrence with its time. Patterns that nobody noticed in conversation stand out on a list.
- Provoke it. With the circuit monitored, flex the cable gently at each joint, tap the device, open and close the door hard. This is the wiggle test. A reading that jumps has found the place.
- Leave an instrument behind. Many meters can record the lowest and highest value seen. Left on a supply overnight, the minimum reading shows a dip you would never catch by watching.
- Ask the users to note the time when it happens, and what they were doing.
The fault "nobody else could find" has usually survived because of an assumption nobody checked. Each person assumed the cable was fine because it was new, or the supply was fine because its light was on. When you inherit such a fault, write down what has actually been measured and what has only been believed. The fault lives in the second list.
What would you do first?
Five calls, your first move
Pick the step that removes the most uncertainty for the least effort.
Three examples
Simple: the lock with no power
Door 9's strike does not release. The supply output reads 24 volts and the strike's terminals read nothing during a valid card. There are six accessible points between them. The technician measures at the cabinet's field terminal, in the middle of the chain: 24 volts when the card is presented. The whole cabinet is cleared in one reading. Next, the junction box above the door: 24 volts. Then the frame side of the power hinge: 24. The door side of the hinge: nothing. A conductor has broken inside the hinge from years of flexing. Four readings, fifteen minutes, one part.
Medium: the reader that was not faulty
A reader at a side door stops reading cards. A technician replaces it. The new one does not work either, so a third is ordered. A second technician, called in, swaps the suspect reader with the one at the next door instead. The suspect reader works there. The good reader fails at the side door.
The fault stayed with the position, so both readers are cleared. Half-splitting the reader's cable finds 12 volts at the controller and 7 at the reader: a joint in the ceiling had corroded. One swap asked a clean question and saved a third reader.
Advanced: the door that unlocked itself
For months a laboratory door has occasionally failed to relock, a few times a week, at no fixed time. Over that period the lock, the controller board and the power supply have each been replaced. The fault continues.
A new technician starts by listing what is known. From the log she extracts thirty occurrences. They are not at fixed times, but nearly all fall in working hours, and none at night or on weekends. She asks the building engineer what runs only in working hours near that door. The freight elevator. She stands at the cabinet with a meter on the door's request-to-exit input and has the elevator called. As its motor starts, the input flickers.
Above the ceiling, the exit sensor's cable shares a tray with the elevator's power feed for forty feet, and its shield drain wire was never landed. Each motor start put a pulse on the cable that the controller read as someone leaving. The repair is a landed drain wire and a cable moved to its own hooks. Three parts were changed over those months, and none of them had been tested first.
From the field
- Write down each test and its result as you go. After an hour you will not remember whether you checked the fuse or only meant to.
- Trust measurements over statements, including your own from yesterday. "It has power" means someone measured it, at the device, under load.
- Put back what you changed if it made no difference. Otherwise you end with a system that differs from the records in ways nobody can list.
- Check your instrument on a known source before believing a zero, as lesson 2 said.
- Take a break when stuck. Explaining the fault aloud to a colleague, or to nobody, often shows the assumption you skipped.
Common mistakes
- Replacing parts before testing anything.
- Starting at one end of a long chain and working along it.
- Changing several things at once.
- Accepting a vague symptom and hunting for the wrong fault.
- Never asking what changed.
- Stopping at the symptom: replacing the fuse and leaving.
- Declaring it fixed without repeating the test that failed.
Summary
- Define the symptom exactly, ask what changed, and see the fault yourself.
- Check the cheap and obvious, then split the chain in the middle. Each test should halve the search.
- Swap with a known-good part to ask one clean question. Change one thing at a time.
- The width of a failure points to what the failed parts share.
- For faults that come and go, gather times and conditions, provoke the fault, and leave an instrument recording.
- Fix the cause, repeat the test, and record it.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. A chain has 16 accessible test points between a known good start and a known bad end. About how many measurements does half-splitting need?
Show answer
Exercise 2. All six doors on one controller stop working at 2:14 p.m. The other controllers are fine. Where do you look first, and where do you not look?
Show answer
Exercise 3. A fuse on a lock output has blown. You replace it and the door works. Is the job finished?
Show answer
Exercise 4 (think, don't memorize). You are the third technician sent to a fault. The first two each replaced a part and reported it fixed, and it came back. Before you touch anything, what do you do?