Installation, Commissioning and Maintenance, lesson 9 of 10
Preventive maintenance
A security system is tested hardest on the day it is handed over, and then mostly ignored. It keeps appearing to work while its batteries age, its lenses gather dust and its doors sag. This lesson shows what to check, how often, and how a short regular visit prevents the failure that would otherwise arrive on the one night the system is needed.
Let the years pass
Move the slider, and compare a system left alone with one visited every year. The figures are an illustration of the pattern, not measurements.
The everyday picture
A car that is never serviced runs well for a surprisingly long time. The oil darkens, the brake pads thin and the tires lose their tread, and each morning it still starts. Then one wet evening it needs to stop quickly, and that is the moment all three matter at once.
Nobody services a car because it has broken down. They service it so that it does not. The mechanic changes parts that are still working, on a schedule, because the cost of finding out the other way is too high.
A security system is the same kind of machine with one difference that makes it worse. Most of it sits idle, waiting. A battery that has lost its capacity and a sounder that has seized give no sign until the event they were bought for.
What wears out
Preventive maintenance is planned work done to stop faults. Corrective maintenance is repair after a fault. You will always do some of the second. The aim is to move as much as possible into the first, where it is cheaper and happens at a time you chose.
| What changes | Examples | How it stays hidden |
|---|---|---|
| Chemistry | Standby batteries lose capacity with age and heat. "Power supplies and batteries" in Access Control gave three to five years as a typical life. | The charger light stays green and the resting voltage looks healthy |
| Dirt | Dust and cobwebs on camera domes, grime on reader faces, grit between a magnetic lock and its plate | It builds too slowly for a daily user to notice |
| Mechanical wear | Hinges drop, closers leak and weaken, strikes drift out of line, screws loosen with vibration | People adapt. They learn to pull the door shut and stop reporting it. |
| The building | New shelving blocks a camera. A tree grows across a detector's view. A room changes use. | The system is unchanged, so nothing alarms |
| Software and data | Updates missed, disks filling or failing, clocks drifting, people who left years ago still holding access | Everything appears normal on the screen |
A maintenance visit
A visit is a small version of commissioning. It has a list, prepared before arrival, and it follows the same three rules from lesson 7: test at the device, check the result at the far end, write it down.
- Ask first. Talk to the people who use the system. "Is there anything that annoys you?" finds the door that needs a shove and the camera that goes dark at night.
- Read the history. Look through the event log for trouble messages, repeated alarms from one door, and devices that drop offline.
- Tell the monitoring center, and place the account on test before causing any alarm.
- Look, clean, tighten. Open each cabinet. Look for dust, damp, insects, scorch marks and swollen batteries. Clean lenses and domes with the cloth and fluid the maker allows.
- Measure. Supply voltage, voltage at a sample lock while working, battery voltage with the mains off and the system running. Compare each with the figure on the commissioning sheet.
- Operate. Each door, each sensor, each sounder, as the test sheet lists them.
- Check the software. Backup taken and restorable, recording going back as many days as promised, clocks right, updates applied as agreed with the customer.
- Close out. Take the account off test. Leave the system as you found it or better. Write the report.
The comparison with commissioning figures is what turns a visit from a look-round into a measurement. A lock that had 23.4 volts at handover and has 21.0 today still works. Something has changed, and you have found it a year before the customer would.
Check yourself
Which of these can only be found by going to the device?
Checks by device
What do you check on a...
How often?
There is no single correct interval. It depends on how hard the equipment works, how harsh its surroundings are and what a failure would cost. The contract, the maker's instructions and sometimes a regulation set the minimum. The table shows a common pattern for an ordinary commercial site. Treat it as a starting point.
| Interval | Typical tasks | Who |
|---|---|---|
| Daily or weekly | Glance at the alarm and trouble list. Confirm cameras are showing pictures and recording. | The customer's own staff |
| Monthly or quarterly | Backup check. Review of who has access. Test signal to the monitoring center, if not automatic. | Customer's administrator |
| Once or twice a year | The full visit described above: clean, measure, operate every device, update software | Service technician |
| Every few years, by age | Replace standby batteries. Review whether the system still fits the building. | Service technician with the customer |
Raise the frequency where it earns its cost: a gate that cycles hundreds of times a day, cameras beside a dusty loading dock, a door protecting something critical. Where a security system is tied to life safety, such as locks released by the fire alarm, the fire code and the authority having jurisdiction may require tests at set intervals. Ask.
The log and the report
Keep a service log for each site: date, who attended, what was checked, readings taken, parts changed, and anything left outstanding. It does three jobs. It shows the customer what they paid for. It lets the next technician see that the same door has needed adjusting three visits running, which means the real fault is still there. And it turns single readings into a trend: a number moving slowly in one direction is the earliest warning you will get.
End each visit with a short report in plain words, sorted by urgency: what was fixed, what needs fixing soon and what it will cost, and what to plan for next year. Update the device schedule and as-built drawings from lesson 8 if anything changed. Records that fall out of date quietly stop being used.
Three examples
Simple: the battery in year four
On the yearly visit to a small office, the technician reads the date written on the cabinet battery: four years old. With the mains switched off, the voltage falls steadily while two doors are operated. The battery is replaced the same day for the price of a lunch, and the new date is written on it. Nothing dramatic happened, which is the result maintenance is for.
Medium: the camera that watched a shelf
A warehouse suffers a theft at its rear door. The camera covering the door was recording perfectly: a clear, sharp picture of the side of a storage rack, installed eight months earlier directly in front of it. No fault was ever raised, because the camera had none.
A maintenance visit catches this in seconds if each camera's current view is compared with a reference image, a snapshot saved at commissioning showing what the camera is supposed to see. Without that comparison, a technician checks that there is a picture and moves on.
Advanced: the trend at Door 22
A hospital's log records the voltage at each lock, while energized, at every visit. Door 22 read 23.6 volts at handover, then 23.1, then 22.2, then 20.9. Every reading was inside the lock's working range, and every visit the door was marked as passed.
A technician who reads the row, not just the last cell, sees a steady fall. The supply voltage has not changed, so resistance is growing somewhere along the run. A search finds a splice above a washroom ceiling going green with damp. It is remade in a sealed connector and the reading returns to 23.5. The door never failed. Had it done so, it would have been a ward door that would not lock, discovered by a nurse.
From the field
- Write the installation date on every battery with a marker, and replace by age as well as by test.
- Watch each door close by itself from fully open and from a few inches. If it does not latch both times, that is today's most important finding.
- Clean domes gently. Blow the grit off first. A dry cloth dragged across a dusty dome scratches it, and scratches flare at night.
- Review the list of people with access with the customer. Leavers who still have live cards are a maintenance finding like any other.
- Leave a dated sticker in the cabinet with your name. The next person knows when it was last opened and by whom.
Common mistakes
- Treating "no faults reported" as "no faults".
- Judging a battery by its voltage while the charger is on.
- Checking that a camera has a picture without checking that it is the right picture.
- Testing from the screen and never walking to the doors.
- Adjusting the same door every visit without asking why it keeps moving.
- Taking readings and not comparing them with earlier ones.
- Leaving the monitoring account on test.
Summary
- Idle equipment fails silently. Maintenance finds the failure before the event does.
- Batteries, dirt, mechanical wear, changes to the building and neglected software are the five things to look for.
- A visit is a small commissioning: ask, read the log, look, clean, measure, operate, record.
- Compare every reading with the commissioning baseline and the last visit. Trends warn early.
- Set the interval by use, surroundings and consequence, and check for required intervals where life safety is involved.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. What is the difference between preventive and corrective maintenance?
Show answer
Exercise 2. A lock's voltage, measured while energized, was 23.8 volts two years ago, 23.0 last year and 22.1 today. The supply output is unchanged at 24.1. The lock works. What do you do?
Show answer
Exercise 3. Why is a reference image useful on a camera maintenance visit?
Show answer
Exercise 4 (think, don't memorize). A customer says, "The system has worked for three years without a single visit. Why should I pay for maintenance now?" How do you answer honestly?