Terminations

Lesson 3 got the cable from the cabinet to the device without hurting it. Now each wire has to end somewhere: a screw terminal, a connector or another wire. A door has a few dozen of these terminations and a building has thousands. Each takes under a minute to make, and one poor one can cost a day to find. This lesson shows how to make them all the same, and all good.

About 14 minutes. Read lesson 3 first.

One wire, one terminal, up close

Pick how the wire was prepared, then play or step through.

D0D1spare tug edge of the terminal bare copper: 1/4 inch Sound

The everyday picture

Think of a chain. Nobody inspects the steel in the middle of a link. Chains break where one link meets the next. The same is true of anything made from parts: a garden hose leaks at the fittings, a zipper fails at the ends.

A cable is the steel and the terminations are the joins. Copper inside a jacket almost never fails by itself. A wire held by half its strands, or clamped on its insulation, or touching its neighbor, fails often, and usually not on the day it was made. Heat, cold and a slamming door work on it for months first.

That delay is what makes terminations special. You cannot see a bad one by looking at the system. You can only make each one properly, the same way, every time.

Stripping

Stripping means removing insulation to expose the copper. It has two stages, and each has one way to go wrong.

  • The outer jacket. Most security cable has a thin thread under the jacket called a ripcord. Nick the jacket at the end, pull the ripcord back to split it, and trim. This avoids cutting round the cable with a knife, which scores the insulation of the wires inside. Remove only as much jacket as you need to spread the wires to their terminals.
  • The individual wire. Use the stripper notch marked with the wire's size. A notch one size too small bites into the copper. A nicked conductor has a weak spot that snaps after a few bends. On stranded wire, a wrong notch cuts off some of the strands, and the wire now carries less current than its size suggests.

How much to strip depends on the terminal. Many terminal blocks have the strip length printed or molded beside them. For the small terminals on controllers and readers it is commonly about a quarter of an inch. The test is simple: when the wire is fully in, no bare copper shows outside the terminal, and no insulation is under the clamp.

Landing a wire

To land a wire is to fix it in its terminal. The sequence is the one in the drawing at the top.

  1. Strip to the right length. Twist the strands lightly in the direction they already turn, so that none stands apart.
  2. Open the terminal fully. Push the wire in until the insulation meets the edge.
  3. Tighten until snug. Some equipment gives a torque figure. Follow it. Too loose and the wire works free. Too tight and the screw cuts through fine strands or cracks the block.
  4. Tug the wire, firmly, once. If it moves, do it again.

A few rules go with that.

  • One wire per terminal, unless the terminal is made for two. Two wires of different sizes under one screw are never both held.
  • Do not coat the end with solder before putting it under a screw. Solder is soft. It slowly flows under pressure and the joint loosens.
  • Use a ferrule on fine stranded wire. A ferrule is a small metal tube crimped over the bare end. It turns a brush of strands into one solid pin, and no strand can escape. Twin ferrules take two wires into one terminal properly.
  • Shield drain wire: land it at the cabinet end only, on the point the manufacturer names. At the device end, cut it back and insulate it.
  • Parts that belong at the device stay at the device. The suppressor goes across the lock's wires at the lock. An end-of-line resistor goes at the last sensor, not in the cabinet where it protects nothing.

Check yourself

A wire is fully inserted and the screw is tight, but a little insulation is under the clamp. What is the likely result?

Joining wires

Sometimes a wire must meet another wire: a device with short factory leads, a resistor, a damaged end. A crimp is a metal sleeve squeezed onto the wire so hard that the two become one piece. Done with the right tool it is as good as the wire. Done with pliers it is a loose tube.

ConnectorWhat it doesTypical use
Butt spliceJoins two wires end to end inside an insulated sleeveExtending a lock's leads to the field cable
Gel-filled spliceA small cap that pierces the insulation when squeezed. The gel keeps moisture out.Joining thin sensor wires, 22 to 18 AWG, without stripping
Ring or fork terminalGives the wire a flat end to go under a screw head or onto a studBattery and ground connections
FerruleTurns stranded wire into a solid pinAny small screw terminal
Lever connectorA reusable block. Lift the lever, insert the wire, close.Joints that will be opened again for testing
Solder and heat-shrink sleeveA soldered joint under a sleeve that shrinks tight when heatedOutdoor and vibration-prone joints, where the specification allows

Insulated crimp connectors are color-coded by wire size. Red fits 22 to 18 AWG, blue fits 16 to 14 and yellow fits 12 to 10. A red connector on a 14 AWG wire will not go on. A blue one on a 22 AWG wire goes on easily and falls off later.

Use a ratcheting crimp tool. It will not release until the crimp is complete, so every joint gets the same force. Then tug each side.

Make every joint somewhere it can be reached again: in the device's back box, a junction box or the cabinet. A joint buried in a wall is a fault with no address.

Network plugs and jacks

A network cable has eight wires in four twisted pairs, and each wire has a fixed position. Nearly all new work in the United States uses the pattern called T568B. Hold the plug with the clip away from you and the contacts up. Pin 1 is on the left.

PinWire color, T568BPinWire color, T568B
1White with orange stripe5White with blue stripe
2Orange6Green
3White with green stripe7White with brown stripe
4Blue8Brown

Two details decide whether the cable carries fast data:

  • Keep the twist. The twist is what protects the signal. Untwist each pair no more than half an inch before the contact. An inch of straight wire can be enough to fail a certification test.
  • Clamp the jacket, not the wires. The plug's strain relief must grip the outer jacket, so a tug on the cable does not reach the contacts.

Fixed cable in walls and ceilings has solid conductors and should end in a jack or a patch panel, where each wire is pressed into a slotted contact with a punch-down tool. A short flexible patch cord then joins the jack to the device. Where a camera leaves no room for a jack, use a plug made for solid cable. Use the same pattern at both ends, and test every cable with the tester from lesson 2.

Labeling

A label answers one question for a stranger: where does the other end of this go? Good labels share four habits.

  • The same name at both ends, on the drawings and in the software.
  • Printed, wrap-around, and placed within a few inches of the end, where it can be read without moving other cables.
  • A fixed pattern, so that anyone can read a label they have never seen.
  • No personal names and no "new" or "temp". Those are out of date within a month.

Build a cable label

One common pattern: where the cable starts, which door, which device. Your company or the project specification may set a different one. Follow it.

Inside the cabinet, dressing means arranging the wires neatly. Bring cables in along the sides, turn them at right angles, leave a little slack at each terminal and keep power wires apart from data wires. A dressed cabinet is easier to fault-find, and it tells the next technician that the hidden work was probably done with the same care.

Three examples

Simple: landing a reader

A reader cable has six wires and a drain. The technician strips 2 inches of jacket with the ripcord, strips a quarter inch from each wire, crimps a ferrule on each and lands them in order from the wiring sheet: power, ground, the two data wires, light and beeper. The drain goes to the cabinet's ground point. Each wire gets a tug. The cable label sits just outside the bundle, facing out. Ten minutes, and nobody will open that cabinet about this door again.

Medium: the door that alarms on windy days

A rear door reports "forced open" a few times a month, always in bad weather, and nobody is ever there. The door contact tests fine. So does the cable. In the cabinet, the wire on that input looks perfect. A tug pulls it straight out.

It had been stripped too short, so the clamp closed on insulation with a few strands touching. When wind shook the door and the wall, the contact broke for an instant. Restripping one wire ended three months of false alarms. The tug test at installation would have found it in two seconds.

Advanced: one loose wire, six dead readers

Six readers share one data cable, running from each reader to the next. At every reader, the incoming and outgoing wires were twisted together and forced into one terminal. One afternoon all the readers past the third go offline.

At reader three, one of the two wires has worked out of the terminal. The reader itself still works, because its own wire is held. Everything downstream has lost its path. The repair is a twin ferrule on each pair of wires, at all six readers, not just the one that failed. The lesson is about shared paths: a termination that carries other devices' signals deserves the best joint on the job.

From the field

  • Tug every wire you land. It is the cheapest test in the trade.
  • Terminate with the power off. A bare end that brushes the next terminal on a live board can end a controller.
  • Cut back and insulate every unused conductor at both ends. Loose spare wires find something to touch.
  • Keep offcuts out of the cabinet. A single strand of copper lying across a circuit board is a fault waiting for the door to slam.
  • Take a photo of each finished cabinet with the door open. It goes in the handover records and settles later arguments.

Common mistakes

  • Stripping with cutters or a knife and nicking the copper.
  • Leaving bare copper showing outside the terminal.
  • Clamping on the insulation.
  • Forcing two wires into a terminal made for one.
  • Crimping with pliers, or using the wrong color of connector for the wire.
  • Untwisting network pairs an inch or more to make them easier to handle.
  • Labeling one end, or labeling after the cabinet is full.

Summary

  • Systems fail at the joins. Make every termination the same way.
  • Strip with the right notch, to the length the terminal asks for: no copper outside, no insulation inside.
  • One wire per terminal, snug, then tug. Ferrules tame stranded wire.
  • Crimp with a ratcheting tool and the right color: red, blue, yellow from thin to thick.
  • Network cable: T568B, half an inch of untwist at most, jacket under the clamp.
  • The same printed label at both ends, matching the drawings.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. Which color of insulated crimp connector fits an 18 AWG lock wire?

Show answer
Red. Red covers 22 to 18 AWG.

Exercise 2. In the T568B pattern, which colors are on pins 1 and 2, and which on pins 3 and 6?

Show answer
Pins 1 and 2 are white-orange and orange. Pins 3 and 6 are white-green and green. The green pair is split around the blue pair, which sits on pins 4 and 5.

Exercise 3. Why should the end of a stranded wire not be coated with solder before it goes under a screw terminal?

Show answer
Solder is soft and slowly gives way under the screw's pressure, so the joint loosens over time. A crimped ferrule gives a solid end without that problem.

Exercise 4 (think, don't memorize). You open a cabinet installed by someone else. Every wire is the same color, nothing is labeled, and spare conductors hang loose. You have been asked only to add one door. What do you do about the rest?

Show answer
Do your own door to the proper standard, labeled at both ends. Do not start pulling at or rearranging the existing wiring: you would own every fault that followed. Photograph the cabinet before you touch it. Insulate any loose bare ends you find, because they are a hazard to your work as well. Then tell the customer in writing what you saw and what it would take to trace and label it. The old work is theirs to decide on, and the photo shows what you inherited.