Installation, Commissioning and Maintenance, lesson 3 of 10

Pulling and supporting cable

"Cable and wiring" in Access Control told you which cable to buy. This lesson is about getting it from the cabinet to the device without hurting it. Cable is damaged far more often on the day it is pulled than in the twenty years that follow, and the damage usually stays hidden until the system is live.

About 14 minutes. Read "Cable and wiring" in Access Control first.

Above the ceiling, seen from the side

Pick how the cable was run, then play or step along it from the cabinet to the reader.

ceiling space corridor closet light fitting power fire wall Cabinet Reader 18 lb pulling force Supported

The everyday picture

Picture a garden hose. Drag it round the sharp corner of a brick wall and it kinks. The kink may spring back, but that spot is now weak and the flow is never quite the same. Leave the hose lying across the driveway and sooner or later a car drives over it.

A cable is a hose for signals, and more delicate. Inside the jacket the wires sit in a precise arrangement. A hard pull stretches them. A sharp bend crushes them together. Either one changes how the cable carries data, and nothing shows on the outside.

So the craft has two halves: pull gently along a smooth route, then hold the cable up and out of harm's way for good.

Pathways

A pathway is whatever carries or holds cable between two points. You will meet five kinds.

PathwayWhat it isWhere it suits
J-hooksOpen hooks fixed to the structure, with a wide, smooth saddleAbove a lift-out ceiling. Cheap, quick and easy to add to later.
Cable trayAn open metal ladder or basket hung from the structureMain routes carrying many cables. Usually installed by others and shared.
ConduitA closed pipe, metal or plasticExposed runs, outdoors, underground, through concrete, and wherever the specification demands it
Surface racewayA slim channel with a snap-on cover, fixed to the wall faceFinished rooms where the wall cannot be opened
SleeveA short piece of conduit through a wall or floorEvery crossing of a fire-rated wall, later sealed with firestop

Plan the route on the drawing, then walk it. Look for the things a drawing leaves out: a beam that hangs lower than the ceiling, a duct filling the corridor, a wall that goes all the way up to the deck. Measure the real route, not the straight line. Then add the rise and fall at each end and a service loop of a few spare feet.

One vertical route has its own name. A riser is a path between floors, often a stack of closets with sleeves through each floor. Every hole through a floor is a fire barrier and must be sealed again.

Pulling without damage

Three numbers govern a pull. All three are on the cable's data sheet.

  • Pulling tension. The most force the cable can take. For ordinary four-pair network cable the published limit is 25 pounds. That is less than most people expect: about the pull needed to lift a full bucket of water with one hand. Thin security cable is no stronger. Check the data sheet.
  • Bend radius. The tightest curve allowed. A common rule for four-pair network cable is a radius of at least four times the cable's diameter. A cable a quarter inch thick must not bend tighter than a 1-inch radius, which is a curve about the size of a soda can.
  • Length. A network cable run is limited to about 328 feet end to end, as "Cable and wiring" explained. That is measured along the real route, with the loops.

The practice that keeps you inside those numbers:

  • Let the cable leave the box or reel freely. Cable sold in a pull box feeds out of a hole in the side. Cable on a reel must turn on an axle. Lifting loops off the side of a reel puts a twist in every turn, and the twists become kinks.
  • Pull by hand, steadily. If it sticks, stop and find out why. Never answer a stuck cable with more force.
  • Put a person at every corner on a long pull, feeding the cable round by hand so that it does not saw across an edge.
  • Leave a pull string behind. Pull a light nylon line in with the cable and tie it off at both ends. The next cable along that route is then a ten-minute job.
  • Label both ends before the pull, and again after cutting to length. An unlabeled cable is found with the toner from lesson 2, at the cost of an hour.

Check yourself

A cable stops moving halfway through a pull. What do you do?

How full may a conduit be?

A conduit packed solid cannot be pulled through, and the cables inside cannot shed heat. The electrical code's general rule for a conduit holding three or more cables is that they fill no more than 40 percent of its inside area. That looks wasteful until you try to pull the last cable round a bend.

The sum uses areas, not widths. The area of a round cable is 0.785 times its diameter squared. The tool does it for you, using the inside areas of common thin-wall steel conduit, known as EMT.

Conduit fill

Take the cable's outside diameter from its data sheet. Composite access cable is often about 0.4 inches. Network cable is about 0.22 to 0.25.

total cable area
of the conduit filled
smallest conduit that passes

Two more conduit rules of thumb. Keep the bends between pull points to no more than the equivalent of four right angles, 360 degrees in all, and fewer if you can. And put a pull box wherever the run is long or turns often. Both make the difference between a pull and a fight.

Support and protection

Once the cable is in, it has to stay undamaged for the life of the building.

  • Hang it from the structure. Cable must not rest on ceiling tiles or the ceiling grid, and must not be tied to pipes, ducts, sprinkler lines or another trade's conduit. Space J-hooks about 4 to 5 feet apart so the cable hangs in gentle curves.
  • Do not overfill a hook. Each has a rated number of cables. A fat bundle crushes the cables at the bottom.
  • Fasten gently. Use hook-and-loop straps, or cable ties left loose enough to slide. A tie pulled tight dents the jacket and squeezes the pairs. Staples through or tight across a cable are the classic cause of the short you met in lesson 2.
  • Protect cable where it passes through metal. A hole drilled in a steel stud has a sharp edge. Fit a plastic bushing or grommet. Where a cable passes through a wood stud close to the face, fit a steel nail plate so a drywall screw cannot reach it.
  • Keep your distance from power. Stay out of the electrician's conduits and boxes, cross power cables at a right angle, and keep clear of light fittings and motors.
  • Seal every hole in a fire wall or floor with a firestop system approved for that wall and that kind of cable. Many sites allow only a licensed firestop installer to do it. Ask.
DamageHow it happensHow it shows up later
Stretched pairsPulling too hardA network link that drops or runs slowly
KinkTwist from a reel, or a tight cornerIntermittent data errors, a broken conductor months later
Cut jacketDragging over a stud edge or tray lipA short to metalwork, or water getting in outdoors
Crushed cableTight ties, staples, an overfull hookShorts and noisy video
HeatLying on a light fitting or steam pipeBrittle, cracked insulation after a few years

Outdoors and underground, use cable made for it. Ordinary indoor cable soaks up water in a buried conduit, and every buried conduit fills with water sooner or later.

Three examples

Simple: one door down the corridor

A reader is 90 feet from the closet along a corridor with a lift-out ceiling. The technician fixes J-hooks to the structure every 4 feet, lays the composite cable in them, drops it inside the wall to the back box and coils 3 feet of spare above the ceiling at each end. With the rise and fall, the cut length is about 110 feet. The labels went on before the pull.

Medium: the camera that got worse

A camera worked on the day it was installed. Six months later its picture breaks up and the link drops several times a day. A tester shows that the cable passes a simple wiremap test. Lifting tiles along the route finds the cause: at one corner the cable was hauled tight round a steel beam flange, and a later contractor's bundle is now lying on top of it.

All eight wires still connect, which is why the simple test passes. The pairs have been flattened, and the cable no longer carries fast data cleanly. The only cure is a new cable, with a hook at the corner to give it a proper curve.

Advanced: the full conduit

A parking garage needs six more cameras. One existing 3/4-inch conduit runs across the deck and already holds four network cables. Six more would make ten. At 0.23 inches each, ten cables have an area of about 0.42 square inches, which is 78 percent of the conduit. It will not pass the rule, and it will not physically pull.

The options are a second conduit, or a different design: one cable to a small outdoor-rated switch at the far end, feeding all six cameras locally. The second is often cheaper than drilling new conduit across concrete. A fill sum done at the desk decided the architecture.

From the field

  • Pull the longest run first. If you run short of cable, you want to find out on the run you cannot join.
  • Never splice a cable inside a wall or ceiling to save a pull. If a run is short, pull a new one.
  • Tape the cable's end before the pull so that it does not snag, and cut off the last foot afterwards. That foot took all the abuse.
  • Read the footage marks printed on the jacket at both ends and subtract. That is the true length of the run, for the records and for the voltage drop sum.
  • Close every ceiling tile you open, with clean hands. Fingerprints on tiles are what the customer remembers.

Common mistakes

  • Laying cable on the ceiling tiles because it is quicker than fixing hooks.
  • Tying cable to sprinkler pipe or another trade's supports.
  • Pulling harder when the cable sticks.
  • Cinching cable ties until the jacket dents.
  • Leaving the hole through a fire wall open "until later".
  • Cutting cable to the exact length, with no service loop.
  • Using indoor cable in an underground conduit.

Summary

  • Most cable damage happens during the pull, and stays hidden.
  • Respect the data sheet's pulling tension and bend radius. For four-pair network cable that is 25 pounds and four times the diameter.
  • Three or more cables may fill at most 40 percent of a conduit.
  • Support cable from the structure every 4 to 5 feet, never from tiles, pipes or ducts.
  • Fasten loosely, protect at sharp edges, seal fire walls, and leave a pull string and a service loop.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. A network cable is 0.24 inches thick. Using the four-times rule, what is the tightest bend radius allowed?

Show answer
0.24 times 4 is 0.96 inches, so about 1 inch. Check the data sheet, which may ask for more.

Exercise 2. Five composite cables, each 0.40 inches thick, are to go in a 1-inch EMT conduit with an inside area of 0.864 square inches. Does that pass the 40 percent rule?

Show answer
No. One cable is 0.785 times 0.16, which is 0.126 square inches. Five are 0.63 square inches, or 73 percent of the conduit. Four tenths of 0.864 is only 0.35 square inches, enough for two of these cables. Five need a 1 1/2 inch conduit, which allows 0.81. Try it in the tool.

Exercise 3. Name three things a cable above a ceiling must not rest on or be tied to.

Show answer
Any three of: the ceiling tiles, the ceiling grid and its hanger wires, sprinkler pipes, water pipes, air ducts, light fittings, and another trade's conduit or supports.

Exercise 4 (think, don't memorize). A new cable passes every test on the day it is pulled. Why might it still have been damaged by the pull, and what habit protects you?

Show answer
Stretching and kinking weaken a cable without breaking it. A simple continuity or wiremap test only proves that the wires connect, so the damage shows up later as a marginal link, or as a conductor that finally breaks after months of vibration and temperature change. The protection is in the method, not the test: free-running cable, hand pulls, a person at every corner, proper supports. On network cable, a tester that measures performance, not just continuity, catches more of it.