Intrusion Detection, lesson 1 of 12
How an alarm system thinks
An intrusion alarm is a small computer that asks one question all day: is anything open or moving that should not be? This lesson shows the handful of parts every system has and the simple rules the panel follows. Once you can predict what a panel will do, the rest of the course is detail.
Watch one system at work
Pick a situation, then play or step through it.
The everyday picture
Picture a night watchman in a small shop. He sits in a back room with a row of little bells, one tied by a string to each door and window. During the day the bells ring all the time and he ignores them, because the shop is open. At closing time the owner tells him, "I am leaving now." From then on, any bell means trouble. He bangs a gong so the whole street hears, and he telephones for help.
In the morning the owner unlocks the front door. That bell rings too, but the watchman knows this door is the normal way in. He gives the owner half a minute to say the password before he reaches for the gong.
An alarm system is that watchman. The strings are sensors, the back room is the control panel, "I am leaving" is arming, the password is a code, the gong is a sounder and the telephone is the link to a monitoring center.
The parts
- SensorsEach one reports a single fact: this door is open, something warm moved in this room, this glass broke. A sensor never decides anything.
- Control panelA circuit board in a locked metal cabinet, usually in a closet or utility room. Every sensor wire ends here. It holds the rules and makes every decision.
- KeypadWhere people talk to the panel: arm, disarm, see which door is open. It is only a remote control. The brains stay in the cabinet.
- SounderA siren or bell, often with a flashing strobe. It tells the intruder he has been noticed and tells neighbors which building it is.
- CommunicatorThe part of the panel that sends each alarm to a monitoring center over the internet, the cellular network or a phone line.
- Power and batteryA plug-in transformer feeds the panel, and a rechargeable battery in the cabinet carries it through a power cut.
The trade name for the place where one sensor circuit lands on the panel is a zone. Zone 1 might be the front door and zone 2 the hall motion detector. When a sensor reports something, the zone is said to be faulted, tripped or simply open. When everything is closed and still, the zone is normal, and the keypad shows "Ready".
Armed, disarmed and always on
The panel is never switched off. It reads every zone many times a second, day and night. What changes is how it reacts. Arming tells the panel to treat a tripped zone as an alarm. Disarming tells it to stand down. Most panels offer two armed modes.
| Mode | Who is inside | Doors and windows | Motion detectors |
|---|---|---|---|
| Disarmed | Anyone | Watched, not alarmed | Watched, not alarmed |
| Armed stay | People at home or working late | Alarmed | Ignored, so people can move about |
| Armed away | Nobody | Alarmed | Alarmed |
Some zones ignore the arming state altogether. A panic button, a smoke detector and the switch that notices the cabinet door being opened must work at three in the afternoon as well as three in the morning. These are 24-hour zones.
One more idea makes the system livable. The door people use to come and go is set as an entry and exit zone. When it opens while the system is armed, the panel starts a countdown, the entry delay, often 30 seconds, and the keypad beeps. A valid code inside that time disarms the system. No code, and the alarm sounds. Lesson 6, Arming, disarming and entry delay, covers this in full.
Check yourself
A shop is open and the system is disarmed. A customer walks past the motion detector. What does the panel do?
What the panel does all day
Strip away the features and every panel runs the same short loop.
- Read every zone. Is the circuit normal, tripped, or damaged? A cut or shorted cable shows up as a third condition, called trouble. Lesson 7, Wiring and supervision, explains how.
- Look up the zone's type. Entry door, ordinary door or window, interior motion, 24-hour.
- Check the arming state and decide: ignore, start a delay, or alarm.
- Act. Drive the sounder, show the zone on the keypad, and hand a message to the communicator.
- Write it down. Every event goes into a log with the time, the zone and the user who armed or disarmed.
The message that leaves the building is short: an account number, the kind of event and the zone number. The operator at the monitoring center sees it within seconds, follows a written procedure, usually trying to reach the owner first, and then asks the police to attend. The Alarm Monitoring course follows that journey.
Not every event is an alarm. Panels sort what they report into three piles.
| Kind of event | Typical cause | What happens on site | Who needs to act |
|---|---|---|---|
| Alarm | A zone trips while armed, or a 24-hour zone trips | Sounder, keypad shows the zone | Monitoring center, then police or a keyholder |
| Trouble | Low battery, mains power lost, a damaged cable, a failed communication path | Keypad beeps and shows a warning | The owner, then the alarm company |
| Routine | Arming, disarming, a daily test signal | Nothing visible | Nobody, unless it is missing or at an odd hour |
Ask the panel
Set the arming state, then cause an event. Try to predict the answer before you look.
What will the panel do?
The system is
and this happens
Exact behavior is set in programming and differs between panels. A tamper while disarmed, for instance, is a quiet trouble on some systems and a full alarm on others. The pattern, though, is the same everywhere: zone type plus arming state gives the response.
Power and the cabinet
The panel runs on low voltage. A typical small United States panel is fed by a plug-in transformer that turns 120 volts into about 16.5 volts AC, and the board makes roughly 12 volts DC for sensors, keypads and the sounder. A sealed 12-volt battery in the bottom of the cabinet, often 4 to 7 amp-hours, is kept charged and takes over the instant the mains fail.
How long the battery must last, called standby time, depends on the standard the system is built to and on local rules. Several hours is a common minimum for a burglar alarm, and longer where fire devices share the panel. Check the panel's listing and ask the authority having jurisdiction. The sums work exactly as in the Access Control lesson Power supplies and batteries: add the current of everything connected, multiply by the hours, and add a margin.
The cabinet has a tamper switch, a small spring switch that opens when the door is opened or the cabinet is pulled off the wall. Sounders and many sensors have one too. Mount the cabinet inside the protected area, somewhere an intruder must pass a sensor to reach.
Three examples
Simple: a one-bedroom apartment
The apartment has one door, a living room and a balcony door. The system is a panel in the hall closet, a keypad by the front door, a contact on each door and one motion detector in the living room. At night the tenant arms in stay mode: both doors are alarmed, and she can walk to the kitchen without setting anything off. Leaving for work, she arms away and the motion detector joins in.
Medium: the shop that alarmed every morning
A bakery's alarm sounded most mornings as the first baker arrived. He always entered by the rear door because it is next to the ovens. The rear door had been programmed as an ordinary door, so the panel alarmed the instant it opened. The front door, which nobody used at 4 a.m., had the entry delay.
The fix took five minutes of programming and a second keypad: the rear door became an entry and exit zone with a keypad beside it. The lesson is to ask how people really use the building before deciding zone types.
Advanced: the alarm nobody received
A warehouse was broken into on a holiday weekend. The sounder ran, the log showed the correct zone, and nobody came. The panel's only path to the monitoring center was the building's internet connection, and the network switch it used had no battery. The intruder cut power at an outdoor disconnect first. The panel carried on from its own battery and tried to report through a network that was already dark.
The redesign added a cellular communicator inside the cabinet as a second path, powered from the panel's battery, and a "communication failure" trouble that the monitoring center watches for. A system is only as alive as its weakest power source and its only path out.
From the field
- Read the keypad before touching anything. "Not ready" with a zone number tells you which door is ajar faster than walking the building.
- Write the date on every battery with a marker when you fit it. Sealed batteries in alarm cabinets commonly last three to five years, and nobody remembers when the last one went in.
- Name zones the way the customer talks. "Rear door by ovens" is better than "Zone 4". The operator reads that name to the police.
- Tell the monitoring center before you test, and tell them again when you finish. Then check that the test signals actually arrived.
- Leave the transformer where it cannot be unplugged for a vacuum cleaner. Many have a tab for a retaining screw. Check that the outlet is not controlled by a wall switch.
Common mistakes
- Thinking a disarmed system is off. It still watches every zone, and its 24-hour zones are fully live.
- Giving the entry delay to the door the installer used, not the door the staff use.
- Mounting the panel in the garage or by the front door, where an intruder reaches it before any sensor sees him.
- Relying on a single communication path that shares the building's unprotected power.
- Treating a trouble beep as a nuisance and silencing it for weeks.
Summary
- Sensors report facts. The control panel decides. The keypad is a remote control.
- The panel always watches. Arming changes how it reacts, not whether it looks.
- Zone type plus arming state gives the response: ignore, delay, or alarm.
- 24-hour zones such as panic and tamper alarm in every state.
- An alarm matters only if it gets out: a sounder on site, and a powered path to people who will act.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Name the part that decides whether an open door is an alarm.
Show answer
Exercise 2. A family arms in stay mode and goes to bed. Someone gets up for a glass of water and walks past the hall motion detector. What happens, and why?
Show answer
Exercise 3. A keypad shows "Trouble: AC loss". Is the building protected right now? What should the owner check?
Show answer
Exercise 4 (think, don't memorize). A customer asks for the control panel to go on the wall right beside the front door, "so it is easy to get to". What do you say?