PanelSimulator Academy

Intercom and Visitor Management, lesson 7 of 8

Emergency and assistance stations

Some intercoms are not for visitors at all. They are for a person who is stuck, frightened or hurt, and who needs to reach a human being with one press. This lesson covers help points in parking lots and on campuses, the stations in areas of refuge, and the one inside every elevator car. The equipment is familiar. The standard it is held to is much higher.

About 14 minutes. Read Analog, IP and cloud first.

Where a call for help goes

Choose where the call comes from, and whether anyone is at the desk.

elevator stair Elevator car Area of refuge Parking help point Security desk Monitoringcenter off site, 24 hours
answers the call
shown to the operator

The everyday picture

Think of the red cord beside a hospital bed. The patient does not dial, does not look anything up and does not explain where they are. One pull, and a light comes on at the nurses' station showing which bed. If the nurse at that station is busy, the call does not vanish. It keeps showing until somebody deals with it.

An emergency station is a red cord for a building. It has one obvious control. It says where it is without being asked. And it is never allowed to ring at an empty desk.

Three kinds of station

Help pointArea of refuge stationElevator car station
WhereParking structures, campuses, transit platforms, trailsA protected landing, usually at a stair or elevator lobby, on upper and lower floorsInside every passenger elevator car
Who uses itAnyone who feels unsafe, is hurt or needs helpA person who cannot use the stairs and is waiting to be helped outPassengers in a stopped car
Why it is thereThe owner's choice, to make people saferGenerally required by the building codeRequired by the elevator safety code
Answered byCampus or site security, or a monitoring centerA central point approved by the fire departmentStaff on site, or a monitoring service at all hours

The middle row is the important one. A help point is good practice. The other two are legal requirements, enforced by inspectors, and their details are set by code and by the authority having jurisdiction, not by the owner or the installer.

What every one must do

Whatever the kind, a station that people depend on in an emergency shares a set of features that an ordinary door intercom may lack.

FeatureWhat it meansWhy
One press, hands-freeA single large button starts the call. Nothing to hold or dial.The caller may be injured, panicking or unable to grip
Says where it isThe operator sees the station's name and location as the call arrivesThe caller may not know, or may not be able to speak
Seen as well as heardLights or text show "call placed" and "help is coming"For callers who are deaf or hard of hearing, and for noisy places
Never unansweredIf the first point does not answer in a set time, the call moves on by itselfDesks are empty at night
Watches itselfA broken cable or dead station raises a trouble signalA fault found during an emergency is found too late
Runs without mains powerBattery or generator backup, for the time the code statesEmergencies and power cuts arrive together

The fifth row has a trade name: supervision. A supervised system checks its own wiring and devices all the time and reports a fault at the main panel. On an ordinary intercom, a dead station is found when a visitor complains. On an emergency system that is not good enough.

The automatic move to another answering point is called rollover. Try it in the tool at the top: set the desk to empty and watch where each call ends up.

Check yourself

An emergency station's cable is cut by a contractor on Monday. On a properly designed system, when is the fault discovered?

Areas of refuge

In a fire, elevators are generally taken out of normal use and people leave by the stairs. A person in a wheelchair on the sixth floor cannot. Building codes answer this with the area of refuge: a space protected from fire and smoke, usually at a stair landing or an elevator lobby, where a person can wait for firefighters to help them down.

Waiting is only safe if someone knows you are there. So the codes generally require a two-way communication station at each of these spaces, and in many buildings at the elevator landing on each floor above or below the exit level. The details vary with the edition of the code and the type of building, so the project's code consultant or the authority having jurisdiction must confirm where stations go. The usual requirements look like this:

  • Each station connects to a central point, such as the fire command center or main lobby, at a location the fire department approves.
  • If that point is not attended at all times, the call automatically goes on to a monitoring location or to 911.
  • The station gives both audible and visible signals, and has instructions posted beside it.
  • The space is marked with a sign that can also be read by touch.
  • The wiring is supervised, protected so that it survives a fire for a period, and backed up by standby power.

These systems are close relatives of the fire alarm. In many places they must be installed under a permit, by a licensed contractor, with listed equipment. Ask before you quote.

Elevators

Every passenger elevator car has a communication device, required by the elevator safety code that states adopt. The passenger presses one button, marked with a phone symbol and raised lettering. The call goes to people who can send help. If nobody on site answers within a short time, it is forwarded to a service that is staffed around the clock. The person answering must be able to tell which building and which car the call is from, without the passenger saying so.

Recent editions of the elevator code go further for passengers who cannot hear or speak. They call for a way to exchange text with the trapped passenger, and for video so that the person answering can see into the car. Whether a given elevator needs this depends on when it was installed or modernized and which edition the state has adopted. The elevator contractor and the elevator inspector are the people to ask.

For the security installer, the practical lesson is about boundaries. The device in the car belongs to the elevator. The traveling cable that carries it belongs to the elevator contractor. Your part is usually the path from the elevator machine room onward: a network connection, a phone line or a cellular communicator, and its backup power.

Count the stations

A first count for a budget takes four numbers. Treat the result as a starting point for the conversation with the authority, not as the answer.

First estimate for one building

refuge stations
stations in total
calls to test each month

Three examples

Simple: the parking structure

A three-level parking structure has had two assaults in a year. The owner fits a help point beside each stair door on each level, six in all. Each is a bright post with a blue light on top, a single button and a camera. A press calls the security office, flashes the blue light and brings up the nearest parking camera on the operator's screen. The station announces its own location: "Level 2, north stair".

Medium: the office that closes at six

A five-story office building has area of refuge stations that ring a master station at the lobby desk. The fire inspector asks one question: who answers at 2 a.m.? Nobody does. The guard leaves at 6 p.m.

The system is given a communicator that, after 30 seconds without an answer at the desk, forwards the call to a monitoring center. The center's operator hears the caller, sees the building address and station name, and calls the fire department. The inspector tests it by pressing a station with the desk empty and timing the answer.

Advanced: the silent passenger

A hospital modernizes four elevators. The old car phones are voice only. During planning, a staff member who is deaf describes being stuck in a car for forty minutes with a speaker she could not hear, not knowing whether anyone was coming.

The modernization follows the current elevator code. Each car gets a screen that shows messages and yes-or-no questions the passenger can answer with buttons, and a camera the answering staff can view. Calls go first to the hospital's own security room, which is staffed at all hours, with rollover to an outside service as a backstop. The security integrator supplies the network path and the workstation, with battery backup matched to the elevator contractor's requirement. The elevator contractor supplies everything in the car and shaft. The two agree in writing where one scope ends and the other begins, and they test together with the inspector present.

From the field

  • Test every station by placing a real call, on a schedule the owner writes down. Record the date, the station and who answered.
  • Test rollover with the desk truly unattended. Many systems pass every test except the one that matters at night.
  • Check the location text at the answering end. "Station 14" helps nobody. "4th floor, east stair" does.
  • Tell the monitoring center before you test, and tell them when you finish, so a test is not dispatched as a real emergency.
  • Check cellular signal in the machine room and the garage before relying on a cellular communicator there.

Common mistakes

  • Using ordinary door intercoms where the code calls for a listed, supervised emergency system.
  • Letting emergency calls ring at a desk that is empty at night, with no rollover.
  • Leaving stations off backup power.
  • Treating elevator car communication as part of the security job without the elevator contractor.
  • Installing help points and never testing them, so the first real caller finds the dead one.

Summary

  • Emergency stations serve a person in trouble: one press, hands-free, location known.
  • Help points are the owner's choice. Refuge and elevator stations are required by code.
  • A call must always reach a person, by rollover to a place that is staffed at all hours.
  • Supervision and backup power keep the system honest between emergencies.
  • The authority having jurisdiction and the elevator contractor decide the details. Ask early.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. What is an area of refuge, and why does it need a communication station?

Show answer
A space protected from fire and smoke where a person who cannot use the stairs waits for help. The station lets them tell someone they are there and hear that help is coming. Without it, nobody knows which floor to go to.

Exercise 2. A seven-floor building has two refuge stations on each floor except the exit level, three elevator cars and four parking help points. How many stations is that?

Show answer
Six floors x 2 = 12 refuge stations. Add 3 elevator cars and 4 help points: 12 + 3 + 4 = 19 stations. Enter 7, 2, 3 and 4 in the tool above to check.

Exercise 3. What does "supervised" mean for an emergency communication system?

Show answer
The system continuously checks its own wiring and stations. A cut cable, a short or a dead station produces a trouble signal at the main panel straight away, so the fault is repaired before anyone needs the station.

Exercise 4 (think, don't memorize). A property manager wants to save money by having refuge stations call the building engineer's mobile phone. What are the weaknesses, and what would you propose?

Show answer
One person sleeps, travels, silences a phone, loses signal and takes vacations. A mobile call also does not show which station is calling, and the arrangement is unlikely to satisfy the fire department's requirement for an approved, constantly attended point. Propose the approved central point on site with automatic rollover to a monitoring center staffed at all hours. The engineer can be sent a notice as well, but never as the only path.