PanelSimulator Academy

Intercom and Visitor Management, lesson 4 of 8

Releasing a door from a call

The call ends with one small act: a switch closes and a lock lets go. Where that switch sits, what it is wired to, and whether the access control system knows about it decide how secure the entrance really is. This lesson shows the three common arrangements and how to pick between them.

About 14 minutes. Read Analog, IP and cloud first. Electric locks, in the Access Control course, is useful background.

Where the switch lives

Choose how the release is wired, then choose what happens.

outside inside, the secure side Relaymodule readyAccess controller Lock power supply Electriclock Locked Door station
  • Lock wiring stays inside
  • Access system records the release
  • No false forced-door alarm

The everyday picture

Think of a garage door with a push button. If the button is inside the garage, only someone already inside can open the door. If the same button were mounted on the outside wall, anybody walking past could press it.

Nobody would do that with a button. Yet the same mistake is easy to make with wires. The wires that open a door are as good as a button. If they end in a box on the outside of the building, the button is outside, however clever the box is.

So the question for every intercom is simple. Where is the switch that releases the lock, and where do its wires run?

The relay

The switch is a relay: a small switch operated by electricity instead of a finger. The intercom energizes it for a few seconds, and its contacts open or close the lock circuit. It is the same part the Access Control course described in How a door decides who gets in.

A relay output has three terminals. C is common. NO, normally open, is not connected to C until the relay operates. NC, normally closed, is connected to C until the relay operates.

LockNeedsWire the lock circuit through
Fail-secure strike or lockPower to releaseC and NO. Operating the relay sends power.
Magnetic lock or fail-safe strikePower to holdC and NC. Operating the relay cuts power.
Door run by an access controllerA request, not powerC and NO, to an input on the controller. The relay carries only a tiny signal.

The intercom relay is usually a dry contact. That means it supplies no power of its own. It only joins two wires. The lock's power comes from a separate supply, and the relay sits in that circuit like a light switch.

Every relay has a contact rating on the data sheet, such as 1 amp at 30 volts DC. The relays inside door stations are small. A lock that draws more than the rating, or a motor-driven latch with a brief surge, will burn the contacts. And every lock is a coil that kicks back when switched off, so fit the suppressor the lock maker supplies, right at the lock.

Three ways to wire a release

Relay inside the door stationRelay module indoorsThrough the access controller
Lock wires run toThe unit on the outside wallA module on the secure sideThe controller, as for any card door
Link to the stationNone neededA data pair or the networkA relay pair, or a software link
If the station is removedThe lock circuit is within reachOnly a data cable is foundOnly a data cable is found
Record of the releaseIntercom onlyIntercom onlyIntercom and access system
SuitsInner doors, low-risk sitesOuter doors without access controlAny door that also has a reader

The first arrangement is the quickest to install, which is why it is common. It is acceptable where the station is indoors or the risk is low. For an outside door that protects something of value, keep the lock circuit inside. Many makers sell a small secure relay module for exactly this purpose. The door station tells it to operate over a data connection, and a loose wire outside cannot imitate that message.

A tamper switch helps in every case. It is a small switch behind the station that changes state when the unit leaves the wall. Wire it to an alarm input or enable it in the software, so that removal is noticed the moment it happens.

Check yourself

An intercom releases a magnetic lock directly. Which relay terminals carry the lock's power?

Working with access control

Most intercom doors also have a card reader. Then two systems want to open one lock, and they must agree.

If the intercom switches the lock directly, behind the controller's back, the controller sees a locked door swing open with no card and no exit request. It reports door forced open, the alarm the Access Control course covered in Events, alarms and monitoring. After a week of these, operators stop reading alarms.

The clean way is to let the controller do the unlocking. Wire the intercom relay to a spare input on the controller, and program that input as a remote release for the door. The controller then unlocks for its usual time, expects the door to open, and writes an event. Check the controller's manual for what it calls this input, and whether its report tells an intercom release apart from an exit request.

On IP systems the same thing can be done in software. The intercom or its management program sends a message to the access system, which unlocks the door and records which operator released it and for which call. This also allows the reverse: a card presented at a reader built into the door station is passed to the controller.

Whatever the method, the intercom is one more way in. It must never change the way out. The exit devices, the fire alarm release and the power-fail behavior you learned in Getting out: egress and life safety stay exactly as they were, and are tested again after the intercom is connected.

Timing and remote release

  • Release time. Set it long enough to reach the handle and no longer. Three to five seconds suits a station beside the door. A gate or a station across a lobby needs more.
  • Momentary, not latched. The relay should drop back by itself. A setting that leaves the door unlocked until someone remembers to relock it has no place on a visitor entrance.
  • Two doors. A vestibule has an outer and an inner door. Use two relays and two buttons, so the operator can let a courier into the vestibule without opening the building.
  • Release from a phone. The person presses a digit during the call. Change the digit or code from the factory value, and allow it only while a call from that door is in progress.
  • Feedback. A tone and a lit symbol at the station tell the visitor to pull now. A door position switch tells the operator the door really closed again.

Check a relay against a lock

Enter the lock's current and the relay's contact rating from the two data sheets.

Can this relay switch this lock?

terminals to use
of the relay's rating

Three examples

Simple: the inner office door

A law firm has an intercom at the door between its waiting area and its offices. The station is indoors, the strike is fail-secure and draws 0.3 amps, and the station's relay is rated at 1 amp. The strike is wired through C and NO with a 12-volt supply and a suppressor at the strike. The arrangement is simple, and it is appropriate for an inner door that is watched by a receptionist.

Medium: the alarms nobody could explain

A clinic adds an intercom to its staff entrance, which already has a card reader. The installer wires the station's relay straight across the strike. From that day, the access system reports "door forced open" a dozen times a day.

Nothing is being forced. Each alarm is a visitor let in by intercom. The relay wires are moved from the strike to a spare controller input, programmed as a remote release. The alarms stop, and every intercom entry now appears in the door's history.

Advanced: the street door of a jewelry workshop

A workshop's only entrance opens onto a public sidewalk. The first quote puts a video station outside with its relay wired to a magnetic lock. The designer rejects it. The lock circuit would end in a box that can be reached from the street.

The revised design uses an IP station whose release goes through the access controller by a software link. The lock, its supply and the controller are all inside. The station's tamper switch is enabled and raises an alarm. A second, inner door forms a vestibule, and each door has its own release, so the outer door is closed before the inner one opens. The exit hardware and fire alarm release on the magnetic lock are tested and signed off as before.

From the field

  • Measure the lock's current, do not trust the label on a lock of unknown age. Compare it with the relay rating before connecting.
  • Listen for the relay. A click with no release is a lock or power problem. No click is a programming or signaling problem.
  • Label the release cable at both ends and note in the handover documents which controller input it lands on.
  • Test the release with the door under load. Lean gently on the door as a visitor would. A strike that binds under pressure looks like an intercom fault.
  • Retest exit and fire release after any change to the lock circuit, however small.

Common mistakes

  • Ending the lock circuit in a station on the public side of an outer door.
  • Wiring the intercom across the lock on a card-controlled door, and living with forced-door alarms.
  • Using NO for a magnetic lock, so the door releases only when the relay is at rest.
  • Switching a heavy lock through a small relay with no suppressor.
  • Leaving the phone release code at its factory value.

Summary

  • A door release is a relay in the lock circuit, or a request to the access controller.
  • Power to release goes through NO. Power to hold goes through NC.
  • On outer doors, keep the lock circuit on the secure side and enable the tamper switch.
  • Where there is a card reader, let the controller unlock, so alarms and records stay true.
  • The intercom adds a way in. It never alters the way out.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. What does "dry contact" mean?

Show answer
A relay contact that supplies no voltage of its own. It only joins or separates two wires. The power for whatever it switches comes from somewhere else.

Exercise 2. A strike draws 0.6 amps. The door station's relay is rated at 0.5 amps. What do you do?

Show answer
Do not connect it directly. The load is 120 percent of the rating. Use the station's relay to operate a larger relay or module that switches the strike, or send the release to an access controller whose lock output is rated for it.

Exercise 3. After an intercom is added, a card-controlled door starts reporting "door forced open" whenever a visitor is let in. Why, and what is the fix?

Show answer
The intercom releases the lock without telling the controller, which then sees the door open with no reason. Move the intercom's relay to a controller input set up as a remote release, or use a software link, so the controller does the unlocking.

Exercise 4 (think, don't memorize). A customer has an outdoor station with a built-in relay and asks whether paying for an indoor relay module is worth it. The door leads to a shared bicycle store. What do you say?

Show answer
Weigh what is behind the door against the cost. A bicycle store is a real target, and the station is outdoors and unwatched, so keeping the lock circuit inside is worth a modest part. If the budget truly cannot stretch, at least enable the tamper switch and route the lock cable so it cannot be reached from behind the station. For an indoor station on a low-value door, the built-in relay would be fine.