Electricity and Low Voltage, lesson 11 of 12
Low-voltage safety and the electrical code
Security wiring is safer than mains wiring, and the rules for it are lighter. They are lighter for a reason, and only while certain conditions hold. This lesson explains what a power-limited circuit is, which cable may go where, and the installation rules an inspector will look for.
Pick a cable for a space
Choose where the cable runs, then choose the cable. The building shows the route and whether that cable belongs there.
The everyday picture
A garden hose and a fire hose both carry water. Nobody needs training to use a garden hose, because it cannot knock you over however badly you handle it. A fire hose can, so only trained crews use one.
Electrical rules work the same way. Mains wiring can deliver enough energy to kill a person or start a fire, so it must be installed by licensed electricians, in conduit or armored cable, with every splice in a box. Most security wiring is fed from a source that is built so it cannot deliver that much, even into a dead short. Because the source is limited, the rules for the wiring are relaxed. The whole arrangement depends on that limit being real.
What low voltage can still do
At 12 or 24 volts, dry skin has too much resistance for a dangerous current to flow, so shock is not the main risk. Other hazards remain.
- Heat and fire. Lesson 3 showed that power is volts times amps. A battery or a large supply can push many amps through a short circuit at low voltage. A shorted wire glows, and insulation burns. This is why fuses and power limits exist.
- The mains side of the cabinet. Every power supply has 120 volts coming in. The low-voltage label on the door does not apply to those terminals. Turn the circuit off and prove it dead with a meter before touching them, and leave that connection to a qualified person where the law requires it.
- What is behind the wall. Drilling into a mains cable or a water pipe is a far more common injury than shock from security wiring. Look on both sides before you drill.
- Ladders and ceilings. Falls hurt more low-voltage technicians than electricity does.
The code and who enforces it
In the United States the rules for electrical installation are in the National Electrical Code, known as the NEC and published as NFPA 70. It is a model code. It becomes law only when a state or city adopts it, often with local changes, and a new edition appears every three years. So the edition in force depends on where the job is.
The person who interprets and enforces it is the authority having jurisdiction, or AHJ, usually the local electrical inspector. Many states also require a low-voltage license and a permit for security work. This lesson gives the ideas. For any specific requirement, read the adopted code and ask the AHJ.
Power-limited circuits
The code sorts low-voltage circuits into classes by how much power the source can deliver.
| Class | In plain words | Where you meet it |
|---|---|---|
| Class 2 | Low voltage and strictly limited power. Safe from both fire and shock in normal conditions. | Nearly all security wiring: readers, contacts, most locks, keypads, cameras on network power |
| Class 3 | Limited power at a higher voltage. Safe from fire, with some shock risk. | Some audio and paging systems |
| Class 1 | Not limited in the same way. Wired with methods close to ordinary power wiring. | Large supplies without limited outputs, some motor controls |
| Power-limited fire alarm | A separate set of rules, similar in spirit to Class 2 | Fire alarm circuits, in their own red cable |
As a rough guide, a Class 2 source is limited to about 100 volt-amps at up to 30 volts. Volt-amps are simply volts multiplied by amps. The exact limits depend on the voltage and the type of source and are set out in the code's tables. You do not work them out on site. You look at the power supply's label. If it says "Class 2", the maker has built in the limit and a testing laboratory has checked it.
Three consequences follow.
- A big supply, say 24 volts at 10 amps, is not Class 2 as a whole. Access control supplies handle this by splitting their output into several outputs, each limited and marked Class 2. Check the label for each output.
- Never join two Class 2 outputs in parallel to get more current. The pair is no longer limited.
- If the source is not Class 2, the wiring it feeds does not get the relaxed rules, whatever the voltage.
Check yourself
What makes a circuit Class 2?
Will it fit in a Class 2 circuit?
This tool uses a simplified limit: no more than 100 volt-amps and no more than 5 amps from one output. The label on the real supply is the authority.
Add up a group of devices
Cable ratings
Cable jackets burn, and burning plastic makes thick, poisonous smoke. So the code matches the cable to the space. Three kinds of space matter, and you tried them at the top of the page.
- A plenum is a space that carries air for the building's heating and cooling. The most common one is the gap above a dropped ceiling when it is used for return air. Smoke from a cable burning there is delivered to every room, so plenum cable must spread little flame and give off little smoke.
- A riser is a vertical run that passes from one floor to another. Riser cable must not carry fire up the shaft.
- Everything else on a single floor is general purpose.
| Space | Communications cable | Class 2 cable | Fire alarm cable |
|---|---|---|---|
| Plenum | CMP | CL2P | FPLP |
| Riser | CMR | CL2R | FPLR |
| General purpose | CM | CL2 | FPL |
The marking is printed along the jacket every couple of feet. A higher rating may always stand in for a lower one: plenum cable can go anywhere, riser cable can go in risers and general spaces, and general cable only in general spaces. Not every ceiling is a plenum. Where the return air travels in ducts, the ceiling space is not one. If you cannot tell, ask the building engineer, or use plenum cable.
Rules for the installation
- Keep apart from power wiring. Class 2 cable does not share a conduit, box or enclosure with mains or Class 1 conductors unless a barrier separates them or the code specifically allows it. A lock cable pulled through the same conduit as a 120 volt circuit is a violation, and it defeats the power limit that made the cable safe.
- Support the cable from the building. Use hooks, rings or straps fixed to the structure. Cable may not lie on ceiling tiles, and it may not be tied to conduit, pipes, ducts or the wires that hold up the ceiling.
- Seal what you open. A hole through a fire-rated wall or floor must be closed again with a listed firestop system that suits that wall and that cable.
- Work neatly. The code asks for a neat and workmanlike installation. Inspectors read tidy, supported, labeled cable as a sign that the hidden parts were done properly too.
- Remove abandoned cable. Old cable that is no longer connected and not tagged for future use is generally required to come out, because it adds fuel to the ceiling.
- Use listed equipment as its instructions say. A listing mark covers the product only when it is installed the way the maker describes.
Three examples
Simple: cable on the ceiling tiles
A small office job fails inspection. The reader cables were thrown across the top of the dropped ceiling and rest on the tiles. Nothing is electrically wrong. The inspector's concern is that cable lying on the ceiling comes down with it in a fire, across the path of the firefighters. The crew returns, fixes hooks to the structure every few feet and lifts the cable onto them.
Medium: riser cable in a return-air ceiling
An installer pulls 2,000 feet of CMR cable above an open-plan office, because that was the box in the van. The ceiling has no return ducts, only grilles, which means the whole space is a plenum. The marking on the jacket gives it away at inspection. There is no fix except replacement with CMP cable. The lesson cost two days and two boxes of cable, and it would have cost one question to the building engineer.
Advanced: the lock cable in the power conduit
On a parking gate, an existing conduit carries a 120 volt feed to the gate motor. It runs exactly where the new card reader cable needs to go, and there is room in it. Sharing it is tempting and wrong. If the insulation of either cable were damaged, mains voltage could reach the reader cable and everything connected to it, including a reader that people touch.
The technician lays out the choices for the customer: a separate conduit for the low-voltage cables, or having an electrician advise whether any arrangement the code allows applies here. The customer pays for the second conduit. It also keeps the reader's data away from the motor's electrical noise, as Grounding and noise explained.
From the field
- Read the jacket before you pull. Check the printed rating against the space, every box, every job.
- Call the inspector early. A five-minute question before the job starts is cheaper than any answer you get at final inspection.
- Photograph every firestop you install, with the wall and the product label in the picture. It answers questions months later.
- Treat every unknown wire as live until your meter says otherwise, and check the meter on a known source first, as lesson 9 showed.
- Keep the supply's instruction sheet in the cabinet. It states which outputs are Class 2, and inspectors ask.
Common mistakes
- Assuming that any circuit at 12 or 24 volts is Class 2.
- Using general or riser cable in a ceiling that carries return air.
- Pulling low-voltage cable into a conduit or box that holds mains wiring.
- Leaving a hole in a fire-rated wall, or filling it with ordinary foam.
- Starting work without checking whether the job needs a permit or a license.
Summary
- Low-voltage rules are lighter because the power source is limited. The limit is in the listed supply, not in the voltage.
- A Class 2 source is marked on its label. Do not parallel outputs.
- Match the cable to the space: plenum, riser or general. A higher rating may replace a lower one.
- Keep low-voltage cable out of power conduits and boxes, support it from the structure, and firestop every penetration.
- The adopted code and the AHJ have the final word.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. A cable jacket is printed CL2R. In which of the three kinds of space may it be used?
Show answer
Exercise 2. Six magnetic locks draw 0.5 amps each at 24 volts. How many volt-amps is that, and does it fit the rough 100 volt-amp guide for one Class 2 output?
Show answer
Exercise 3. You open a ceiling tile and see no ductwork leading to the return grilles, only open space. What does that suggest, and which cable do you pull?
Show answer
Exercise 4 (think, don't memorize). A colleague says: "It is only 12 volts, so the code does not care how I run it." Give two reasons that is wrong.