Electricity and Low Voltage, lesson 10 of 12

Grounding and noise

Some faults follow no pattern. A reader misreads only when the air conditioning starts. A camera picture rolls on humid days. These are usually not broken parts. They are stray currents and unwanted signals, and this lesson shows where they come from and how good wiring keeps them out.

About 14 minutes. Read Using a multimeter first.

Follow the noise along a reader cable

Pick a way of wiring the cable, then play or step through.

signal as thecontroller receives it 120 V power cable alongside building steel and earth foil shield around the pair 0 V 1.8 V Controller Reader Clean signal

The everyday picture

Two people are talking across a table in a quiet room. Every word arrives. Move the same table beside a busy road and words start to go missing. Nobody's voice is broken. The message is simply mixed with sound that does not belong to it. That unwanted sound is noise, and electrical noise does the same to the small signals in a security cable.

Now picture two surveyors measuring the height of a hill. One measures from sea level, the other from the valley floor. Both are careful, and their answers disagree. A height only means something against an agreed zero. Voltage is the same. Every voltage is measured against a reference, and when two devices do not share one, they misunderstand each other. That shared zero is what the trade calls ground.

Three things called ground

The word is used for three different things, and mixing them up causes most of the confusion.

NameWhat it isWhat it is for
Earth groundA connection to the soil itself, through the building's electrical serviceSafety, and a path for lightning and surges
Equipment groundThe green or bare wire that joins metal cabinets and conduit back to the electrical panelIf a live wire touches the metal, the current returns this way and trips the breaker instead of waiting for a person
Signal commonThe negative side of a DC supply, often marked 0 V, COM, GND or with a minus signThe agreed zero that signals are measured against

The first two are about safety and belong to the electrician's work. A metal equipment cabinet that takes mains power must be connected to the equipment ground exactly as its instructions and the electrical code require. The third is the one you handle every day, and it is not automatically joined to the other two. Whether a board's 0 V is tied to its metal case is a design choice the maker has made. Read the manual before joining them yourself.

A shared reference

A reader sends card data to a controller as small voltages on its data wires. The controller judges each one against its own 0 V. If the reader is powered from a separate supply, its idea of zero is unconnected to the controller's. The data wires then carry voltages measured against nothing the controller knows, and the cards misread or do not read.

The fix is one wire. Join the negative of the reader's supply to the controller's 0 V terminal, so both ends share a reference. This is the rule to remember: whenever two devices exchange a signal and are powered from different supplies, their commons must be joined, unless the signal is deliberately isolated, as a relay's dry contact is. Lesson 5 explained dry contacts, and this is why they are so useful. A contact passes no reference at all, so it joins two systems without tying their grounds together.

Where noise comes from

SourceHow it gets inWhat you see
Power cables running alongsideTheir changing magnetic field induces a small voltage in any wire nearbyHum on audio, errors on long data runs
Motors, elevators and variable-speed drivesSharp electrical bursts each time they switchFaults that come and go with machinery
Lighting ballasts and dimmersBursts radiated into cables laid across the fixtureFaults that follow the light switch
Lock coils and relaysThe kick at switch-off, from lesson 7A controller that resets when a door releases
Radio transmittersA long wire acts as an antennaBuzzing on an intercom when a two-way radio keys up
Lightning and power surgesHuge voltages on any cable that runs outdoors or between buildingsDead ports after a storm

Three defenses

  • Distance. Noise fades quickly as cables move apart. Keep signal cables away from power cables, motors and light fixtures, by a foot or more where you can. Where they must cross, cross at a right angle. A parallel run of a hundred feet picks up far more than a crossing.
  • Twisting. In a twisted pair, the two wires swap places every inch or so. Whatever noise lands on one wire lands almost equally on the other. A receiver that looks only at the difference between the two wires sees the noise cancel. This is why data cable is twisted, and why you should keep the twists right up to the terminal.
  • Shielding. A shield is a wrap of foil or braid around the wires. Noise lands on the shield instead of the wires inside. It only works if the noise has somewhere to go, so the shield is connected to ground through a bare wire that runs with the foil, called the drain wire.

Use the cable the equipment maker specifies. If the manual says shielded twisted pair, plain alarm wire will work on the bench and fail in the building.

Ground loops

Here is the trap. If a shield is good, grounding it at both ends sounds better still. It is usually worse. Two ground points in a building are rarely at exactly the same voltage. A difference of a volt or two between one end of a building and the other is common. Join both points with a shield and a current flows along it, all day, pulsing with the building's power. That circulating current is a ground loop, and it puts noise onto the very cable the shield was meant to protect.

The usual practice for security cabling is to ground the shield at one end only, normally at the controller, and to cut the drain wire back and insulate it at the device end. Some systems call for something different, so follow the maker's instructions where they say so. Step through the diagram at the top to compare the two.

Cables that run between buildings need more. The two buildings have separate grounds, and lightning can lift one of them by thousands of volts for an instant. Fiber, which carries no electricity at all, is the cleanest answer. Where copper must be used, fit surge protectors made for that kind of circuit at each end and ground them as their instructions say.

Check yourself

A shielded reader cable has its drain wire connected to ground in the controller cabinet. What should happen to the drain wire at the reader?

Match a symptom to a cause

Noise faults feel random until you ask one question: what else in the building changes when the fault appears?

What is the system doing?

Check first
The lasting fix

Three examples

Simple: the reader on its own power supply

A reader 400 feet from its controller is given a local 12 volt supply to avoid voltage drop. It lights, beeps at a card and nothing reaches the controller. Only the two data wires were run back. The technician finds a spare wire in the cable and joins the local supply's negative to the controller's 0 V terminal. With a shared reference, cards read at once.

Medium: the hum that came with the new monitor

A door intercom develops a steady hum after a desk station is moved to a new outlet across the lobby. The intercom cable's shield was grounded at both ends, and the two outlets are on different circuits with slightly different grounds. A meter on AC volts between the lifted drain wire and the desk station's ground terminal shows 1.4 volts. That is the loop. The drain wire is cut back and taped at the desk end, and the hum stops.

Advanced: errors every forty minutes

A warehouse controller reports communication errors on one reader line in bursts, day and night, roughly every forty minutes. Nothing in the security system runs on that schedule. The technician asks the building engineer what does. A rooftop compressor cycles at about that interval, fed by a power cable in the same cable tray where the reader line lies for 120 feet. The reader cable is unshielded.

The fix has three parts. The run is replaced with the shielded twisted pair the maker specifies. It is moved out of the tray and supported on its own hooks a couple of feet away. Its shield is grounded at the controller only. The errors stop. The clue was never in the security system. It was in the building's own rhythm.

From the field

  • Ask what else was happening. Time of day, weather, machinery and lights are the best clues to a noise fault.
  • Sleeve the unused drain wire. A bare drain wire folded back in a device box will find a terminal or the metal box sooner or later and make a second ground.
  • Carry the shield through splices. At a junction, join drain wire to drain wire and insulate it, so the shield is continuous from end to end.
  • Do not lay cable on light fixtures. It is the shortest route across a ceiling and the noisiest.
  • Leave the equipment ground alone. Never remove a green wire or a grounding pin to cure a hum. Fix the loop on the signal side.

Common mistakes

  • Grounding a shield at both ends, or at neither.
  • Powering a device locally and forgetting the common wire back to the controller.
  • Untwisting several inches of pair to make a neat termination.
  • Tying signal cable to a power cable or conduit because it is a convenient support.
  • Replacing a board three times for a fault that follows the elevator.

Summary

  • Ground can mean earth, the safety wire or the signal's zero reference. Know which one you are talking about.
  • Devices that exchange signals need a shared common, unless a dry contact isolates them.
  • Noise comes from power cables, motors, lights, coils, radios and lightning.
  • Distance, twisting and shielding keep it out. Use the cable the maker specifies.
  • Ground a shield at one end, usually the controller. Two grounds make a loop.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. Why does a twisted pair pick up less noise than two straight wires side by side?

Show answer
Because the wires keep swapping places, each one is exposed to the noise source equally. The same unwanted voltage appears on both, and a receiver that reads the difference between them cancels it.

Exercise 2. A signal cable has to cross a bundle of power cables above a ceiling. How should it cross?

Show answer
At a right angle, and with as much space as the ceiling allows. A crossing exposes only a few inches of the cable. Running alongside exposes the whole length.

Exercise 3. A fire alarm relay gives the access controller a dry contact. Do the two systems need their commons joined for it to work?

Show answer
No. A dry contact is only a switch. The controller sends its own small current out through the contact and back, so the whole loop belongs to the controller. That isolation is exactly why dry contacts are used between systems.

Exercise 4 (think, don't memorize). A site has a camera on a metal pole 200 feet from the building, connected by copper network cable. After every thunderstorm, the camera or the switch port fails. Lightning has never struck the pole. What is happening, and what would you propose?

Show answer
A nearby strike does not need to hit the pole. It lifts the ground voltage around the pole far above the building's ground for an instant, and the copper cable is the only path joining the two, so the surge runs along it into the equipment at both ends. The best proposal is fiber to the pole, which carries no electricity, with the camera powered locally. If copper must stay, fit surge protectors rated for that kind of circuit at both ends and ground them as their instructions require.