Electricity and Low Voltage, lesson 9 of 12
Using a multimeter
Electricity is invisible, so a technician without a meter is guessing. A multimeter answers three questions: how much pressure is here, is this path complete, and how much is flowing. This lesson shows how to set it, where to put the probes and what the display is telling you.
Set the dial, place the probes
Choose a dial setting and something to measure. Some combinations are right, some tell you nothing and some harm the meter.
The everyday picture
Suppose a garden hose is not working and you want to know why. There are three things you can check.
You can screw a pressure gauge onto the tap. Nothing flows through the gauge. It just reports the push that is available. You can cut the hose and splice in a flow meter, so that every drop passes through it. Or you can turn the water off, disconnect the hose and blow through it to see whether it is blocked.
Those are the three jobs of a multimeter. Measuring voltage is the pressure gauge: touch two points and read the push between them. Measuring current is the flow meter: the circuit must be opened and the meter put in the gap. Measuring resistance is blowing through the empty hose: it only works with the power off.
Around the meter
A digital multimeter, often written DMM, has four parts you use every time.
- The display. A number, a unit and sometimes a small symbol.
- The dial. It chooses what the meter measures.
- The jacks. The black lead always goes in COM, which means common. The red lead goes in the jack marked V and Ω for nearly everything. It moves to the jack marked A only for measuring current.
- The leads. Two flexible wires ending in pointed probes. Most faults blamed on a meter are a broken lead.
| Mark on the dial | Measures | Use it for |
|---|---|---|
| V with a straight line | DC volts | Power supplies, batteries, locks, readers, panels |
| V with a wavy line | AC volts | Transformers and wall outlets |
| Ω | Resistance in ohms | End-of-line resistors, coils, cable loops |
| Sound waves | Continuity, with a beep | Is this wire or contact a complete path? |
| A | Current in amps | What a device really draws |
Most modern meters are auto-ranging: you choose volts and the meter picks the scale. On an older meter you pick the range yourself, starting with the highest and working down.
Three measurements
Voltage: across, with the power on
Touch one probe to each of two points and the meter shows the voltage between them. Nothing is disconnected. The meter barely disturbs the circuit, because its own resistance is enormous, typically around ten million ohms. This is the measurement you will make most, and it is the gentlest on the meter.
Resistance and continuity: power off, part isolated
On the ohms setting the meter pushes a tiny current from its own battery through whatever is between the probes and works out the resistance. Any other voltage in the circuit ruins the reading and can damage the meter. So switch the power off, and lift at least one wire of the part you are testing so that you measure that part alone and not a path around it.
Continuity is the quick version. The meter beeps when the resistance is low, usually under a few tens of ohms, so you can test a wire without looking at the display.
Current: in line, red lead moved
To measure current, the current has to flow through the meter. Switch the power off, open the circuit at one point, move the red lead to the A jack and connect the meter across the gap. Then switch on. On this setting the meter is almost a plain piece of wire. That is why touching the probes across a supply on the amps setting is a short circuit, and why the meter has a fuse inside.
A clamp meter avoids all of this. Its jaws close around one wire and sense the current from outside. For DC, it must be a clamp made for DC.
Check yourself
You want to check the value of an end-of-line resistor at a door contact. What must you do first?
Reading the display
| You see | It means |
|---|---|
| A minus sign on DC volts | The red probe is on the more negative point. Useful: it tells you which wire is positive. |
| OL on ohms | Over limit. No path between the probes: an open switch or a broken wire. |
| 0.3 Ω with the probes held together | The resistance of the leads themselves. Subtract it from small readings. |
| A small m, k or M beside the unit | Thousandths, thousands or millions. 2.2 kΩ is 2,200 ohms. 450 mA is 0.45 amps. |
| Near 0 volts across a closed switch | Normal. A good contact drops almost nothing. |
| Full supply voltage across an open switch | Normal, and proof that the rest of the loop is complete. |
| A few stray volts on a wire connected to nothing | A ghost voltage picked up from nearby cables. It vanishes as soon as any load is connected. |
Pick the setup for a job
Before the probes touch anything, say to yourself what you want to know. The question decides the setup.
What do you want to find out?
Measure while it is working
A voltage reading with nothing drawing current can be badly misleading. A long thin cable, a corroded splice or a tired battery all show full voltage until current flows, and then sag. Lesson 3 showed why: the volts lost in a resistance are amps multiplied by ohms, and with no amps nothing is lost.
So measure at the device, with the device connected and doing its job. For a lock, put the probes on the lock's own terminals and have someone trigger it. The reading at that moment is the one that matters. Compare it with the reading at the power supply. The difference is what the cable is costing you.
Staying safe
- Mains voltage is a different world. Meters carry a category rating, printed near the jacks as CAT II, CAT III and so on with a voltage, that states where they are safe to use. Never use an unrated or damaged meter on mains wiring, and leave mains measurements alone unless you are trained and permitted to make them.
- Prove the meter before you trust a zero. Measure a source you know is live, then your circuit, then the known source again. A dead reading from a meter with a broken lead has hurt many people.
- Look at the leads. Cracked insulation or a loose probe goes in the trash.
- Put the red lead back in the V jack the moment a current measurement is finished.
Three examples
Simple: the reader that would not light
A new reader stays dark. On DC volts, with the probes on the reader's power terminals, the display shows −12.3. The supply is fine. The minus sign says the red probe is on the negative wire, so the two power wires are swapped at the terminal block. The technician swaps them and the reader lights.
Medium: full voltage, weak lock
A magnetic lock at the end of a long run holds so weakly that a firm pull opens the door. The technician lifts the wires off the lock and measures 12.5 volts across them, which looks fine. That reading was taken with no current flowing. With the lock reconnected and holding, the same two terminals read 9.1 volts. The cable is losing 3.4 volts under load. The cable is too thin for its length, and the cure is from Access Control lesson 9: heavier wire, 24 volts or a supply closer to the door.
Advanced: finding a short with half the walking
A zone that should measure 2,200 ohms reports trouble. At the panel, with the zone wires lifted, the meter shows 38 ohms. That is far too low for the resistor and too high for a short right at the panel. Something is joining the wires partway along the 300-foot run.
Instead of inspecting the whole route, the technician goes to a junction box near the middle, separates the splice and measures both ways. Toward the door the meter reads 2,200 ohms: that half is healthy. Toward the panel it reads 19 ohms with the panel end still lifted. The fault is in the first half. One more split finds a staple through the cable above the corridor door. Three measurements replaced an afternoon on a ladder.
From the field
- Touch the probes together first on ohms or continuity. A beep and a reading under an ohm proves the leads and the meter's battery.
- Measure at the terminals of the device, not at the nearest convenient splice. The fault is often between the two.
- Write readings down as you go. "About twelve" from memory is useless an hour later. 11.4 on the work order is evidence.
- Carry spare meter fuses of the exact type printed on the meter. A meter that reads zero amps on everything has a blown fuse.
- Use fine probe tips or clips on small terminal blocks, and never push a probe into a connector so hard that it spreads the contact.
Common mistakes
- Leaving the red lead in the A jack and then measuring voltage, which shorts the supply through the meter.
- Measuring resistance on a circuit that is still powered.
- Measuring a resistor or contact without lifting a wire, and reading a path through the rest of the system instead.
- Using DC volts on an AC source, seeing nearly zero, and declaring it dead.
- Trusting a voltage reading taken with the load disconnected.
Summary
- Voltage is measured across two points with the power on.
- Resistance and continuity are measured with the power off and the part isolated.
- Current is measured in line, with the red lead in the A jack, or with a clamp.
- OL means no path. A minus sign means the probes are reversed.
- Measure at the device while it is working, and prove the meter before trusting a zero.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. On the ohms setting, across a door contact with the door closed and the wires lifted, the display shows OL. What does that tell you?
Show answer
Exercise 2. The display shows −24.1 on DC volts. What is the voltage, and which wire is the red probe touching?
Show answer
Exercise 3. A lock is rated at 0.5 amps. Your meter, in line with it, shows 480 mA. Is something wrong?
Show answer
Exercise 4 (think, don't memorize). A colleague measures a lock's current, then goes straight to the power supply to check its voltage. There is a small flash at the probes and the supply's output light goes out. What happened, and what will the meter do the next time someone measures current with it?