Electricity and Low Voltage, lesson 8 of 12
Batteries
A battery sits in the bottom of a cabinet for years doing nothing, and then one night the whole system depends on it. This lesson explains what the numbers on the label mean, why an old battery lies about its health, and how to test one so that it works on the night it is needed.
Drain a battery and watch its voltage
Change the load, the size, the age and the temperature. The curve shows the voltage of a 12 volt sealed lead-acid battery as it runs down.
The everyday picture
Think of your phone. On the day you bought it, a full charge lasted until bedtime. Three years later it still says 100 percent every morning, and it is dead by mid-afternoon. The gauge is not lying exactly. The tank is full. The tank has become smaller.
Every rechargeable battery behaves this way. It is a fuel tank that shrinks with age, shrinks faster in heat, and gives up less when you empty it quickly. The backup battery in a security cabinet adds one more difficulty: nobody uses it from day to day, so nobody notices it shrinking. You find out during a power cut, unless you test it first.
Batteries you will meet
| Kind | Where you find it | Rechargeable | Typical life |
|---|---|---|---|
| Sealed lead-acid, 12 volts | Alarm panels, access control and fire alarm power supplies | Yes, kept on charge all the time | 3 to 5 years |
| Lithium cells, 3 volts | Wireless sensors, some wireless locks | No | Several years, depending on use |
| Alkaline cells, 1.5 volts each | Battery-powered locks and keypads | No | About a year on a busy door |
| Lithium iron phosphate packs | Newer power supplies made for them | Yes | Longer than lead-acid, at a higher price |
The workhorse is the sealed lead-acid battery, or SLA: a heavy plastic brick with two flat tabs on top. It is sealed, so it can sit on its side and never needs water. Most of this lesson is about it. One warning before going further: a charger built for lead-acid must not be used on a lithium pack unless the maker says it may. Each chemistry needs its own charger.
Reading the label
A typical label reads "12 V 7 Ah". The 12 volts is a nominal figure, a round name for a voltage that really moves between about 10.5 and 13.8. The 7 amp-hours is the size of the tank: amps multiplied by hours.
There is small print. Makers usually measure capacity over 20 hours. A 7 amp-hour battery gave that figure at 0.35 amps for 20 hours. Ask it for 7 amps and it will not last one hour. It will last something like half an hour. Drain a battery fast and you get less out of it. Move the load slider at the top and watch the usable capacity fall.
So the working sum has a margin built in:
- Amp-hours needed = load in amps × hours of backup × 1.25
- For 0.8 amps over 4 hours: 0.8 × 4 = 3.2, and 3.2 × 1.25 = 4 amp-hours.
A 4 amp-hour battery would only just do on its first day. Pick the next size up, 7 amp-hours, so the system still meets its 4 hours when the battery is three years old.
What the voltage tells you
Inside a 12 volt lead-acid battery are six cells of about 2.1 volts each. The voltage at the terminals depends on what the battery is doing at that moment, so one reading means three different things.
| When you measure | Reading on a 12 volt battery | What it means |
|---|---|---|
| On charge, mains on | About 13.5 to 13.8 volts | The charger is working. This says almost nothing about the battery. |
| At rest, off charge for some hours | 12.7 volts or more | Fully charged |
| At rest | About 12.2 volts | Roughly half charged |
| At rest | 11.8 volts or less | Empty |
| Under load, mains off | Falling toward 10.5 volts | Nearly finished. Below this the battery is being damaged. |
These are typical figures. The data sheet for the battery gives the exact ones, and the charge voltage changes a little with temperature. Notice how small the range is. The whole distance from full to empty is about one volt, so a meter that reads to two decimal places is worth having.
Check yourself
With the mains on, you measure 13.7 volts across the battery in a cabinet. What have you learned?
How batteries age
- Time. The plates inside slowly corrode, used or not. Three to five years is a fair life for a standby battery at room temperature.
- Heat. This is the big one. A common rule of thumb is that life halves for every 15°F or so above 77°F. A cabinet above a ceiling in a hot roof space can finish a battery in under two years.
- Deep discharge. Run a lead-acid battery flat and leave it flat, and hard crystals form on the plates. This is called sulfation, and much of the lost capacity never comes back. Good power supplies disconnect the battery at a low voltage to prevent it.
- Cold. Cold does not age a battery, but it holds back capacity while it lasts. Near freezing, expect roughly four fifths of the room-temperature figure.
- Wrong charging. Too high a charge voltage dries the battery out and swells the case. Too low never fills it.
Two batteries together
You saw series and parallel circuits in lesson 2. The same rules apply to batteries.
- In series, positive of one to negative of the next, the volts add and the amp-hours stay the same. Two 12 volt 7 amp-hour batteries make 24 volts at 7 amp-hours. This is how every 24 volt cabinet is built.
- In parallel, positive to positive and negative to negative, the amp-hours add and the volts stay the same. The same two batteries make 12 volts at 14 amp-hours.
Batteries joined together must be the same type, size and age. Replace them as a set. One tired battery in a pair drags the new one down with it.
Testing, step by step
- Read the date. Most batteries carry a date code, and a good installer writes the install date on top in marker. Past four or five years, replace it whatever it reads.
- Look. A swollen case, cracks, white crust on the tabs or a smell of rotten eggs all mean replace it now.
- Measure on charge. About 13.5 to 13.8 volts for a 12 volt battery, double that for a 24 volt pair. This checks the charger.
- Switch off the mains and watch. With the system running on the battery, the voltage should settle and hold steady above 12 volts for several minutes. A battery that drops quickly toward 11 has lost its capacity.
- Use a battery tester if you have one. It applies a known load for a few seconds and judges the result.
- Restore the mains and write it down. Date, voltage on charge, voltage under load. Next year's reading means more beside this year's.
Some systems, fire alarms above all, must run for a stated number of hours on battery. Those figures come from the code and the authority having jurisdiction, not from this lesson. Find the required hours first, then size and test against them.
Keep or replace?
Five batteries, five sets of evidence. Decide each one.
You are on a service visit
All five are 12 volt sealed lead-acid batteries.
Three examples
Simple: the 24 volt cabinet that read 12
A new access control supply needs 24 volts of backup. The apprentice fits two 12 volt batteries and links plus to plus and minus to minus, because that looked tidy. The supply reports a battery fault. The pair is in parallel and gives 12 volts. Moving one link, so that the positive of the first battery goes to the negative of the second, puts them in series. The supply now sees 24 volts and starts charging.
Medium: "it measured fine last month"
A store loses power for an hour and its alarm system dies after ten minutes. The service report from a month earlier says "battery 13.6 V, OK". That reading was taken with the mains on, so it was the charger's voltage. The battery was six years old. With the mains off, it falls to 10.8 volts within a minute. A new battery goes in, and the report form gains two boxes: the date code, and the voltage under load.
Advanced: batteries that die every eighteen months
A warehouse keeps replacing the batteries in one cabinet. The cabinet is mounted high on a wall under a metal roof, where summer air reaches 110°F. By the rule of thumb, that heat alone cuts life to about a quarter. The technician also measures the charge voltage and finds 14.4 volts, well above the battery's data sheet figure, so the charger is cooking it as well.
The fix has two parts. The power supply is replaced, and the cabinet is moved down to an air-conditioned office wall 30 feet away, with the cable sized for the longer run. The next set lasts four years.
From the field
- Write the install date on every battery with a paint marker, large enough to read from the cabinet door.
- Take rings and watches off. A small battery can push hundreds of amps through a short circuit. A ring across the terminals gets red hot in a second.
- Connect the battery last and disconnect it first when working in a cabinet, and never let the loose leads touch each other.
- Replace wireless sensor batteries when the low-battery signal first appears. A lithium cell holds a steady voltage for most of its life and then falls quickly, so the warning comes late.
- Take old lead-acid batteries back to your distributor. They are recycled, not thrown in the trash.
Common mistakes
- Measuring the battery with the mains on and calling it healthy.
- Sizing a battery to the exact amp-hours of the sum, with nothing left for age.
- Replacing one battery of a pair and leaving its old partner.
- Fitting a much larger battery than the power supply's charger was built for, so it takes days to recharge after an outage.
- Leaving a flat battery connected for weeks after a long outage and expecting it to recover.
Summary
- Amp-hours are amps multiplied by hours. Add a quarter for aging, then pick the next size up.
- A battery gives less than its label when drained fast, when cold and when old.
- Voltage on charge tests the charger. Voltage under load, with the mains off, tests the battery.
- Heat and deep discharge shorten life the most. Three to five years is normal.
- Series adds volts. Parallel adds amp-hours. Match the batteries and replace them together.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Two 12 volt 18 amp-hour batteries are wired in series. What voltage and capacity does the pair give?
Show answer
Exercise 2. A system draws 1.5 amps and must run for 4 hours without mains. Which standard battery size do you choose from 4, 7, 12 and 18 amp-hours?
Show answer
Exercise 3. A battery has been disconnected on a shelf overnight and reads 12.2 volts. Roughly how full is it?
Show answer
Exercise 4 (think, don't memorize). A customer wants 24 hours of backup on a door controller instead of 4, and suggests swapping the 7 amp-hour battery for a 40 amp-hour one. What needs checking before you agree?