Electricity and Low Voltage, lesson 5 of 12
Switches and contacts
Lesson 2 showed that opening a series circuit in one place stops the current. A contact is a part built to do exactly that. Almost every signal in a security system is a contact opening or closing: a door moved, a button was pressed, a sensor saw someone. This lesson explains the words used to describe contacts, which are few but easy to get backwards.
Operate a switch
Pick a kind of contact, then press and release it. Watch which lamp has a complete circuit.
The everyday picture
Think of a drawbridge on a road. When the bridge is down, the road is complete and traffic flows. When the bridge is up, there is a gap and traffic stops. Engineers say the bridge is closed when it is down, because the gap is closed.
A switch is a drawbridge for current. Inside it, two pieces of metal either touch or do not. When they touch, the gap is closed and current flows. When they part, the gap is open and current stops. This is the opposite of a door or a water valve, where "open" lets things through, and it trips up nearly everyone at first.
Open, closed and "normally"
The pieces of metal that touch are called contacts. A contact that is touching is closed: the circuit is complete. A contact that is apart is open: the circuit is broken.
Every switch has a resting state, the way it sits on the shelf with nothing pressing it, no magnet near it and no power applied. The trade describes contacts by that resting state, using the word "normally".
- Normally open, written NO: apart at rest. Operating the switch closes it.
- Normally closed, written NC: touching at rest. Operating the switch opens it.
- Common, written C or COM: the terminal shared by both. Current enters at C and leaves by whichever contact is closed.
"Normally" does not mean "usually" or "while the system is running". It means "at rest". A contact can be normally open and yet spend its whole working life held closed. Keep the two ideas apart: the name tells you the type of contact, and the state tells you what it is doing at this moment.
| Contact | Also called | At rest | When operated | Typical use |
|---|---|---|---|---|
| Normally open | NO, Form A, "make" | Open | Closes | Doorbell button. Trigger for a controller input. |
| Normally closed | NC, Form B, "break" | Closed | Opens | Exit button that cuts power to a magnetic lock. Tamper and alarm loops. |
| Changeover | C with NO and NC, Form C | C joined to NC | C joined to NO | Relay outputs, where the installer picks the side needed. |
Poles, throws and action
Two more words describe how much a switch can do. A pole is one separate circuit that the switch controls. A throw is one position that a pole can connect to. They are shortened to four-letter names you will see in every catalog.
| Name | Spelled out | Terminals | What it does |
|---|---|---|---|
| SPST | Single pole, single throw | 2 | Makes or breaks one circuit. Sold as either NO or NC. |
| SPDT | Single pole, double throw | 3: C, NO, NC | Sends one circuit one way or the other. This is the changeover contact. |
| DPST | Double pole, single throw | 4 | Makes or breaks two separate circuits together. |
| DPDT | Double pole, double throw | 6 | Two changeover contacts moved by one action. One can cut lock power while the other signals the controller. |
The last word is about what happens when you let go. A momentary switch springs back to rest, like a doorbell button. A maintained switch stays where you put it until you move it back, like a light switch. A panic button that must be reset with a key is maintained. An exit button is momentary.
Check yourself
A push button marked NO is wired in series with a buzzer and a supply. Nobody is touching the button. What is the buzzer doing?
Dry and wet contacts
A dry contact is a contact that brings no voltage of its own. It is only two terminals that are either joined or not, electrically separate from the device that operates them. Whatever circuit you connect across it supplies the voltage and does the sensing.
Most signaling between security systems is done this way. A motion sensor's alarm output, a door contact, a request-to-exit button and the fire alarm relay that releases the locks are all dry contacts. The advantage is that two systems from different makers, running on different voltages, can signal each other without their power being joined.
An output that supplies voltage when it is active is the opposite. It is often called a wet contact or a powered output. A siren output that puts out 12 volts in alarm is one. Controller inputs are generally built to watch a dry contact, and feeding voltage into them can give false readings or damage them. When a manual says an input "requires a dry contact", it means: connect nothing here that brings its own voltage.
Open or closed right now?
The name of a contact and its present state are different things. For each case, decide whether current can pass at this moment.
Five contacts
Choose open or closed for each, then read the reason.
Ratings and door contacts
Every contact has a limit
The data sheet gives the most voltage a contact may switch and the most current it may carry. A heavy toggle switch may handle several amps. The contact in a door sensor or a small push button is made for signaling and may handle only a fraction of an amp. Use signal contacts to tell a controller something, and let the controller's relay do the heavy switching. Lesson 6 covers relays.
How a door contact works
The usual door contact has two halves. The half on the frame holds a reed switch: two thin metal strips sealed in a small glass tube. The half on the door holds a magnet. When the door is shut, the magnet pulls the strips together. When the door opens, the magnet moves away and the strips spring apart.
A naming trap
The alarm trade often names a door contact by its state with the door shut and the magnet in place, because that is the "normal" state of a protected door. A contact sold as "closed loop" or "normally closed" is closed while the door is shut. Take the same part out of its bag, with no magnet near it, and it is open. Both descriptions are honest. They use different meanings of normal.
So read the data sheet for the words "with magnet" or "door closed", and prove it with a meter and the magnet before you mount anything.
Why alarm loops rest closed
Alarm and tamper circuits are designed so that the contact is closed in the safe state and opens to report. The reason is that a broken wire or a loose terminal also opens the loop. The panel sees the fault as soon as it happens. In a loop that rests open, a broken wire changes nothing, and nobody learns that the sensor stopped working. Lesson 7 shows how a resistor adds further checks.
Three examples
Simple: the doorbell
A doorbell button is SPST, normally open and momentary. At rest the circuit is broken and the bell is silent. Press it and the contact closes, current flows and the bell sounds. Let go and a spring opens it again.
Medium: the exit button on the wrong terminal
A magnetic lock needs power to hold. Its exit button is meant to break that power when pressed, so the button's normally closed contact goes in series with the lock. An installer lands the wires on C and NO instead. Now the lock has no power at rest, and the door swings free. It locks only while someone holds the button in.
Nothing is faulty. The wire is on the wrong side of a changeover contact. Moving it from NO to NC puts it right. A meter on continuity across the two terminals, with the button at rest, would have shown the mistake before power was applied.
Advanced: voltage where a dry contact was expected
An intercom has a terminal marked "door release" that puts out 12 volts while its button is held. A technician wants that press to open a controlled door, so the terminal is wired to the access controller's request-to-exit input. The input reads erratically, and a week later it stops working.
The input was built to watch a dry contact. It supplies its own small sensing voltage and looks for the loop to close. The intercom's output is wet. It pushed 12 volts into a circuit that expected none.
The fix is a small relay between the two. The intercom's 12 volts energizes the relay's coil. The relay's contact, which is dry and connected to nothing but its own two terminals, goes to the controller input. Each system now sees only what it was designed for.
From the field
- Prove a contact with a meter before you trust its label. Set the meter to continuity, test at rest, operate the switch and test again.
- Test contacts with the power off and at least one wire lifted. Otherwise the meter may be reading through the rest of the circuit.
- Write down which terminals you used. "C and NC" on the door schedule saves the next technician ten minutes.
- Mind the gap on door contacts. Each model has a stated distance within which the magnet will hold it. Steel doors shorten that distance, so use a contact made for steel.
- Buy exit buttons with both NO and NC contacts. One part then suits either kind of lock.
Common mistakes
- Reading "closed" as "blocked". A closed contact is the one that lets current through.
- Reading "normally" as "most of the time" instead of "at rest".
- Assuming a door contact marked NC is closed on the bench with no magnet near it.
- Connecting a powered output to an input that requires a dry contact.
- Switching a lock's full current through a small signal contact, which then welds shut or burns open.
Summary
- Closed means touching, so current flows. Open means apart, so it stops.
- NO and NC describe a contact at rest, with nothing operating it.
- A changeover contact has C, NO and NC. C is joined to NC at rest and to NO when operated.
- Poles are separate circuits. Throws are the positions each can connect to.
- A dry contact carries no voltage of its own. Inputs that expect one must not be fed voltage.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. What does SPDT stand for, and how many terminals does such a switch have?
Show answer
Exercise 2. A cabinet has a tamper switch with C, NO and NC terminals. The closed lid holds its plunger pressed in. You want the loop to be closed while the lid is shut. Which two terminals do you use?
Show answer
Exercise 3. You put a voltmeter across the two terminals of a dry contact that is not yet wired to anything. What does it read with the contact open, and with it closed?
Show answer
Exercise 4 (think, don't memorize). A designer proposes door contacts that are open while the doors are shut and close when a door opens, "to save power". What is the weakness of this, compared with a loop that rests closed?