Doors and Locking Hardware, lesson 9 of 10
Accessibility at the door
A door that a person in a wheelchair cannot get through, or that arthritic hands cannot open, is a locked door for that person. United States law sets measurable limits on width, force, hardware and thresholds. This lesson gives you the numbers, shows how to measure them, and explains what they mean for the security equipment you add.
Measure this door
Change the door and watch the four checks. This is an interior door with a closer.
- Clear width at least 32 in
- Handle 34 to 48 in high, no grasping or twisting
- Threshold no more than 1/2 in
- No more than 5 lb to open
The everyday picture
Try your own front door with both arms full of groceries. You cannot grip a round knob, so you lean an elbow on a lever if you have one. You nudge the door with a shoulder, and if the closer is strong you lose. You catch a toe on the threshold. Now you know what a door asks of a body.
For many people that is every door, every day: a wheelchair user, someone on crutches, a person with a weak grip, a parent with a stroller. Accessibility rules turn "easy to use" into numbers anyone can check with a tape measure and a force gauge.
Where the rules come from
The Americans with Disabilities Act is a federal civil rights law. Its technical requirements for buildings are in the ADA Standards for Accessible Design. Building codes also carry accessibility requirements, usually by referring to a companion standard for accessible buildings. The numbers in the two largely agree. States and cities may be stricter, so confirm with the authority having jurisdiction.
The requirements apply to doors on an accessible route: the continuous path a person with a disability can use to reach and move through a building. In a public or commercial building, that is nearly every door a visitor or employee would use.
The numbers to know
| Item | Requirement | How to measure |
|---|---|---|
| Clear width | At least 32 inches | Open the door to 90 degrees. Measure from the face of the door to the stop on the latch side. |
| Hardware height | 34 to 48 inches above the floor | To the operable part of the handle, pull, lock or push bar. |
| Hardware type | Usable with one hand, with no tight grasping, pinching or twisting of the wrist | Try it with a closed fist. Levers, push bars and U-shaped pulls pass. Round knobs do not. |
| Opening force | No more than 5 pounds on interior hinged doors | A push-pull force gauge at the handle, pushing steadily. Fire doors are allowed the minimum force the authority accepts. |
| Closing time | At least 5 seconds from 90 degrees to 12 degrees from closed, for a door with a closer | A watch. Lesson 5 covers the adjustment. |
| Threshold | No more than 1/2 inch high, with a beveled edge on anything over 1/4 inch | A tape or a gauge block at the highest point. |
| Door surface | The bottom 10 inches of the push side is smooth, across the full width | Look for anything a footrest could catch on. |
Clear width surprises people. The door itself stands in the opening when it is open, and the stop narrows the other side. A 36 inch door on standard hinges loses about 1 3/4 inches to the door's thickness and 5/8 inch to the stop, leaving about 33 5/8 inches. A 34 inch door falls just short. That is why 3 feet is the standard commercial door.
Where an existing door is too narrow, swing-clear hinges can help. Their offset shape swings the door completely out of the opening, giving back roughly the thickness of the door.
The 5 pound limit covers the force to keep the door moving, not the first effort to retract the latch. The federal standards set no figure for exterior doors, though some states do. On exterior doors and fire doors, where the closer must be stronger, a power operator is often the practical way to make the entrance usable.
Check yourself
Where is the clear width of a doorway measured?
Space beside the door
A wheelchair user cannot open a door while sitting directly in its path. They need room to pull alongside the handle and to back away as the door swings. This is maneuvering clearance: a level, clear floor area on each side of the door. Its size depends on the direction of approach and on whether the door swings toward or away from the person.
| Approach from the front | Clear floor beside the latch edge | Clear depth in front of the door |
|---|---|---|
| Pull side | 18 inches | 60 inches |
| Push side, door with a closer and a latch | 12 inches | 48 inches |
| Push side, no closer or no latch | None | 48 inches |
Approaches from the hinge side or latch side have their own figures in the standards. The point for a security installer is simple: that floor area and the wall beside the latch are not free space. A bollard, a card reader pedestal, a turnstile cabinet or a trash can placed there can turn a compliant door into a barrier.
Readers, buttons and operators
- Reach. Anything a person must touch, such as a reader, keypad, intercom button or exit button, belongs within reach of a seated person. For an unobstructed reach the standards give a range of 15 to 48 inches above the floor. Mount readers so the part the card touches is no higher than 48 inches, and keep the floor in front clear.
- One hand, no twist. The rule for door hardware applies to your devices too. A button that needs a fingertip pressed hard into a small recess fails. A large push plate passes.
- Time. A door that relocks 3 seconds after a card is read gives a wheelchair user no chance. Access systems can give selected cardholders a longer unlock time. The Access Control lesson "Access levels and schedules" shows where such settings live.
- Seeing and hearing. A reader that only beeps tells a deaf user nothing, and one that only changes color tells a blind user nothing. Choose devices that do both.
- Power operators. A low-energy operator opens the door slowly when someone presses a push plate. On a controlled door, the reader must unlock the door before the operator starts, and the lock must suit it: electric latch retraction on an exit device, or an electric strike. Wire them in sequence, so the operator never pushes against a locked door.
Pass or fail?
Six things you find on a survey
Decide each one, then read why.
Three examples
Simple: the reader at eye level
An installer mounts a new reader at 56 inches because "that is where people look". A seated user cannot reach it. The reader is moved down so its center is at 44 inches, which also suits standing users well. The plate left behind covers the old holes. Mounting heights belong on the drawings, not in the installer's habits.
Medium: the door that was too narrow by a hair
An older clinic has 34 inch doors to its consulting rooms. Measured open at 90 degrees, the clear width is 31 5/8 inches. Replacing frames in finished walls would be costly and disruptive.
Swing-clear hinges move each door out of the opening and recover about 1 3/4 inches, giving roughly 33 3/8 inches. The hinge preps are the same template, so the change takes minutes per door. You check that the opened door now clears the wall and any closer arm before ordering a set.
Advanced: security and access at the main entrance
An office wants its heavy exterior entrance locked at all times with card entry. The door needs a size 5 closer to latch against wind, and it takes 12 pounds to open. Staff with limited strength already struggle.
You design the entrance as one system. A low-energy operator opens the door. Outside, the reader sits at 42 inches, beside a push plate, on a clear, level landing with the reader outside the swing of the door. A valid card retracts the latch electrically, and the push plate then triggers the operator. Inside, a push plate does the same in one step, and the push bar still opens the door by hand if power fails. Unlock and hold-open times are long enough to roll through. The door stays secure, and nobody has to fight a 12 pound closer to get in.
From the field
- Own a door force gauge. It costs little, fits a pocket, and ends arguments about whether a door is "a bit stiff".
- Measure clear width with the door at 90 degrees, not fully open and not from the leaf size on the drawing.
- Check both sides of the opening for clear floor. Look for furniture, displays and your own equipment beside the latch.
- Try every device with a closed fist. If you cannot work it that way, neither can some users.
- Record what you measured. A door that passed on handover day is a useful fact when it is questioned later.
Common mistakes
- Mounting readers and exit buttons above 48 inches.
- Turning up a closer to make a door latch without measuring the opening force afterward.
- Placing a pedestal, bollard or cabinet in the clear floor area beside the latch.
- Leaving the unlock time too short for someone who moves slowly.
- Adding a second device, such as a separate deadbolt or a keypad lock, at a height or of a type that fails the hardware rule.
Summary
- Clear width is at least 32 inches, measured from the open door's face to the stop.
- Hardware sits 34 to 48 inches high and works with one hand, without grasping or twisting.
- Interior doors open with no more than 5 pounds and take at least 5 seconds to close to 12 degrees.
- Thresholds are no higher than 1/2 inch, and the floor beside the latch stays clear.
- Readers, buttons and unlock times are part of the door, and follow the same thinking.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. A 36 inch door is 1 3/4 inches thick and the stop is 5/8 inch. What is the clear width on standard hinges?
Show answer
Exercise 2. A wheelchair user approaches a door head-on from the pull side. How much clear floor is needed beside the latch edge, and why?
Show answer
Exercise 3. Your force gauge reads 9 pounds on an interior office door that is not a fire door. Name three things to check before weakening the closer spring.
Show answer
Exercise 4 (think, don't memorize). A customer wants a full-height turnstile at a staff entrance for security. What accessibility question must you raise, and what are the usual answers?