Doors and Locking Hardware, lesson 8 of 10

Fire doors

Some doors are part of the building's fire protection. They look ordinary, but they were tested in a furnace as a complete assembly, and they keep that protection only while every part stays as tested. This lesson shows how to recognize a fire door, what it must do, and what a security installer may and may not change.

About 15 minutes. Read lessons 1, 3 and 5 first.

Inspect this fire door

Switch faults on and off. These are the things an inspector looks for, and most of them are caused by everyday use.

label, on the hinge edgeof the door and on the frame fire-rated glass latch kick plate closer no faults found

    The everyday picture

    A ship is divided by bulkheads so that a leak floods one compartment and not the whole hull. Every bulkhead has doors, because the crew must get about. If one of those doors is tied open, the bulkhead might as well not be there.

    Buildings are divided the same way, against fire and smoke. Stair enclosures, corridors, shafts and the walls between tenants are built to hold a fire back for a set time. A fire door is the moving part of such a wall. It has one job: to be closed and latched when the fire arrives, and to stay that way.

    A tested assembly

    A fire door is never just the leaf. The trade speaks of a fire door assembly: the door, the frame, the hinges, the latching hardware, the closer, any glass and any seals. Samples of that combination were built into a wall and exposed to a furnace for the rated time, and in the usual United States test then hit with a fire hose stream. The assembly passed as a set.

    That is why substitutions matter. A lock that was never part of a tested assembly, or a hole nobody tested, turns a proven product into an unknown one. The installation standard used throughout the United States for these openings is the National Fire Protection Association's standard for fire doors. Your local code adopts a particular edition of it, and the authority having jurisdiction enforces it.

    Labels and ratings

    You recognize a fire door by its label. It is a small metal plate or an embossed mark, usually on the hinge edge of the door between the hinges, and on the hinge jamb of the frame. It names the testing laboratory and the rating. Hardware carries its own marks: closers, hinges, locks, exit devices and electric strikes for fire doors are all listed products.

    The rating is a time. Doors are generally rated for less time than the wall they sit in, because a door has no furniture piled against it. These pairings are typical. The building code and the drawings decide the real ones.

    Door ratingOften writtenTypical location
    3 hours180 minutesWalls that divide a building into separate fire areas
    1 1/2 hours90 minutesStair enclosures and shafts in 2 hour walls
    1 hour60 minutesStair enclosures and shafts in 1 hour walls
    3/4 hour45 minutesRooms opening off rated construction, such as storage and mechanical rooms
    1/3 hour20 minutesCorridor doors and smoke partitions

    A label may carry more information: a letter S for a door tested to limit smoke leakage, a maximum temperature rise for stair doors, and whether the door was listed with fire exit hardware. If a label is missing or painted over, the door cannot be shown to be rated. Only the listing laboratory, or a shop working under its program, can inspect and relabel it.

    What every fire door must do

    • Close by itself. Every fire door has a closer, or a spring hinge on the lightest doors. It is described as self-closing. A door that normally stands open is automatic-closing: a holder keeps it open and lets go when the fire alarm or a smoke detector operates.
    • Latch by itself. This is positive latching. An active latchbolt must engage every time the door closes. A magnetic lock holds a door shut, but it is not a latch, so it can never be the only thing holding a fire door.
    • Fit closely. The gaps are limited so flame and hot gas cannot pass.
    • Stay intact. No holes, no missing parts, no broken glass, no missing seals.
    WhereUsual maximum clearance
    Between door and frame at the head and jambs1/8 inch
    Between the meeting edges of a pair1/8 inch
    Under the door3/4 inch

    Steel doors are allowed a small tolerance on the 1/8 inch. Check the edition in force. Current editions of the standard also call for every fire door assembly to be inspected and tested at least once a year, with a written record kept for the authority. The tool at the top of this page shows the main items on that inspection.

    Check yourself

    A fire-rated stair door is held shut only by a magnetic lock. The latch was removed because it kept jamming. What is wrong?

    What may not be changed

    The standard allows only a short list of work on a labeled door or frame on site. The usual list is: fitting surface-applied hardware with small drilled holes, drilling the round holes a lock needs for its cylinder and spindle where the door was prepared for that lock, fitting a labeled door viewer, and fixing protection plates near the bottom of the door. Round holes for surface hardware are commonly limited to 1 inch across. Anything more is a field modification, which needs the listing laboratory's permission in advance or must be done in a shop licensed to apply the label.

    For a security installer, that turns into a few firm habits.

    • Electric strikes. Use a strike listed for fire doors, in a frame that is permitted to be cut for it. Fire-rated strikes are fail-secure, so the latch stays held when power is lost. Where a door must also unlock for re-entry, the answer is an electrified lock or trim, not a fail-safe strike.
    • Wiring through the door. A channel through a door for wire, called a raceway, is drilled at the factory or by a licensed shop. Order the door with it, or send the door away. Do not core it on site.
    • Hold-opens. Wedges, hooks, kick-down stops and hold-open closer arms have no place on a fire door. Use a holder that the fire alarm releases.
    • Replacements. Replace like with like: listed hinges of steel with bearings, a listed closer, a listed lock with at least the latch throw shown on the door label.
    • Old holes. When hardware is removed, its holes are filled with steel fasteners or with the same material as the door, as the standard directs. An open hole is a path for flame.
    • Plates and signs. Kick plates up to 16 inches above the bottom of the door can be fitted on site. Taller plates must be labeled. Signs are limited in size and are stuck on, not screwed.

    May you do this on site?

    Six requests on a labeled door

    Decide each one, then read why. Rules differ a little between editions, so treat these as the usual answers.

    Three examples

    Simple: the wedge

    The door from an office corridor to the stairs is wedged open every day for air. It is a 90 minute door. Open, it protects nothing, and the stair fills with smoke first in any fire.

    Staff are not being careless. The door is in their way. The fix that lasts is an electromagnetic holder on the wall, wired to release on fire alarm, so the door stands open legally and closes when it matters. The wedge goes in the trash.

    Medium: card access without cutting

    A customer wants a reader on a labeled storeroom door in a steel frame. The quick idea is an electric strike. The frame's label and the maker's documents do not show it as prepared for one, and cutting a rated frame on site is a field modification.

    You choose a route that needs no cutting beyond what is allowed. The existing cylindrical lock is replaced with a listed electrified lock of storeroom function that fits the same prep. Power reaches it through a listed power transfer hinge in place of the middle hinge, and the door is ordered or sent out for its raceway. Every part is listed, the latch still latches, and the labels stay valid.

    Advanced: the annual inspection report

    A hospital's inspection lists forty failed openings and the facilities manager asks you to price repairs. Reading the report, the faults fall into groups. Twelve doors do not latch from a slow close: closers and hinges, as lessons 2 and 5 covered. Nine have clearances over 1/8 inch at the latch edge: hinge shimming, or listed edge and gasket products where the gap cannot be closed. Eight have open holes from removed hardware. Six have painted labels. Five have hardware that was never listed.

    You sort them by who may do the work. Adjustment, listed replacement parts and hole filling are yours. The painted labels and anything needing new cuts go to a labeling service. You give the manager a schedule with the stair and corridor doors first, and a record of each repair for next year's inspector.

    From the field

    • Look for the label before you take out a drill. Check the hinge edge of the door and the hinge jamb. If either has one, stop and plan.
    • Photograph both labels at survey. The rating, the laboratory and the serial number answer most questions from the supplier.
    • Test latching from fully open and from a few inches. A fire door that needs a push to latch has failed.
    • Carry a gap gauge. Measure the clearances instead of judging them by eye.
    • Never paint a label, and mask it when others paint.

    Common mistakes

    • Treating a magnetic lock as the latch on a fire door.
    • Cutting an electric strike into a rated frame without checking the frame's listing.
    • Fitting a fail-safe strike on a fire door, so the door is unlatched whenever power is lost.
    • Coring a wire path through a labeled door on site.
    • Leaving open holes after removing old hardware.
    • Fitting unlisted hardware because it "looks the same".

    Summary

    • A fire door is a tested assembly of door, frame and hardware. Change a part and it may no longer be what was tested.
    • Labels on the door edge and the frame give the rating, from 20 minutes to 3 hours.
    • It must close by itself, latch by itself, fit within tight clearances and stay intact.
    • Only a short list of work is allowed on site. More than that needs permission or a licensed shop.
    • For access control, choose listed electrified hardware that keeps the latch working.

    Exercises

    Answer each one yourself first, then open the answer.

    Exercise 1. Where do you look for the labels on a fire door assembly?

    Show answer
    On the hinge edge of the door, usually between the hinges, and on the hinge jamb of the frame. Sometimes the frame label is on the head. Hardware has its own marks.

    Exercise 2. You measure 1/4 inch between a fire door and the strike jamb, and 1/2 inch under the door. Which one is a problem?

    Show answer
    The 1/4 inch at the jamb, which is twice the usual 1/8 inch limit. The 1/2 inch under the door is within the usual 3/4 inch limit.

    Exercise 3. Why are electric strikes for fire doors fail-secure?

    Show answer
    A fire door must stay latched in a fire, and fires often take the power with them. A fail-secure strike keeps holding the latch without power. A fail-safe strike would release it, and fire pressure could push the door open. People still leave freely, because the inside lever or push bar retracts the latch mechanically.

    Exercise 4 (think, don't memorize). A building owner says "it is only a twenty minute door, so the rules hardly matter". How do you answer?

    Show answer
    The rating changes how long the assembly resists fire, not whether the rules apply. A 20 minute corridor door mostly exists to hold back smoke in the first minutes, which is when people are escaping, and it can only do that if it is closed, latched and unbroken. It still needs its label, a closer, a working latch and proper clearances, and it is still inspected. A wedged 20 minute door and a wedged 3 hour door protect exactly the same amount: nothing.