Codes, Standards and Privacy, lesson 3 of 10
The building and fire codes
Four documents decide what you may do to a door on the way out of a building. This lesson shows what each one is for, how they divide the work between them, and how to find the part that applies to the door in front of you.
One upper floor, seen from above
Pick a situation, then play or step through it.
The everyday picture
Think of leaving a parking garage on foot. First you walk between the cars, by any path you like, to a door with a sign over it. Behind that door is a bare concrete stair with nothing in it that can burn. At the bottom, another door lets you out to the sidewalk.
You passed through three different kinds of space. The first is where people spend their time. The second is a protected shaft built only for leaving. The third is the last few steps to the street. The codes treat the three differently, and a door's rules depend on which of them it stands in.
Four documents
| Document | What it is for | You open it when |
|---|---|---|
| International Building Code (IBC) | How a building is designed and built: its use, its size, its exits and its fire-rated walls and doors | The job is new construction or an alteration that needs a permit |
| International Fire Code (IFC) | How a building is kept safe once people are using it, and what existing buildings must still provide | The building is already occupied, or the fire marshal is the one asking |
| NFPA 101, Life Safety Code | Getting people out, in new and existing buildings. It is organized by the kind of use. | The site is a hospital or care home, or your state has adopted it |
| NFPA 80 | Fire doors: how they are installed, what may be attached or changed, and how they are inspected | The door or frame has a fire label |
The first three overlap on purpose. The IBC and IFC share most of their wording on exits, and NFPA 101 reaches similar answers by a different route. Which of them is law where you are standing is the adoption question from lesson 2. Many places adopt the IBC and IFC. Some adopt NFPA 101 as well, and healthcare sites must usually meet it whatever the city chose.
The way out has three parts
The codes call the whole route from any spot in a building to the street the means of egress. In recent editions of the IBC and the IFC it has its own chapter, chapter 10, and that chapter is where most of your door questions are answered. It has three parts, shown in the plan above.
- Exit access. The rooms, aisles and corridors people cross to reach an exit. This is most of the building.
- Exit. The protected part: an enclosed stair, or a door straight to the outside. Its walls and doors are fire rated so that it stays usable while the floor burns.
- Exit discharge. The path from the exit to the street or another safe open space, which the codes call the public way.
Every door along that route must open in the way "Getting out: egress and life safety" described: one motion, no key, no special knowledge. A door that is not on any route, such as a closet, is far less restricted.
Use and number of people
Before the code tells you anything about a door, it asks two questions about the space behind it.
The first is the occupancy classification: what the space is used for. The IBC sorts uses into lettered groups, and each group has its own rules.
| Use | Examples | What tends to change at the door |
|---|---|---|
| Assembly | Theaters, restaurants, places of worship, gyms | Panic hardware, strict limits on any locking |
| Business | Offices, banks, clinics for walk-in patients | The most room for electrified locks |
| Educational | Schools through twelfth grade | Panic hardware, special rules for classroom locks |
| Institutional | Hospitals, nursing homes, jails | People who cannot leave unaided, so locking is allowed under tight conditions |
| Mercantile | Shops and stores | Delayed egress often permitted on some exits |
| Residential | Apartments, hotels, dormitories | Unit entry doors, often fire rated |
The second is the occupant load: how many people the code assumes are in the space. It is worked out from the floor area and the use, and it is not a head count on a quiet Tuesday. The load decides how many exits a room needs, how wide they are, which way the doors swing and whether they need panic hardware. The architect's drawings usually state both the classification and the load. Ask for them.
Check yourself
An office tenant turns a large open room into a training hall with rows of chairs. Why might the rules for its doors change, although the doors are the same?
Fire doors
Some walls are built to hold back fire for a set time. That time is the wall's fire-resistance rating. A door in such a wall has to carry a rating too, or the wall has a hole in it. A rated door is tested and labeled as a complete assembly: door, frame, hinges, latch and closer together. The label is on the hinge edge of the door and on the frame.
NFPA 80 is the standard for these doors. Three of its ideas matter on every job.
- The door must close by itself and latch by itself. A fire door that is open, or closed but unlatched, does nothing. This is called being self-closing and positive latching. It is the reason a magnetic lock alone is never enough on a fire door.
- What you attach must be labeled for fire doors. That includes electric strikes, electrified locks and power transfer hinges.
- What you cut is tightly limited. NFPA 80 allows only small preparations on site. Anything beyond that, such as boring a wire path through the core of a door, has to be done under the door manufacturer's label program or with the listing laboratory's permission.
NFPA 80 also calls for fire doors to be inspected and tested every year, with a written record. A wedge, a missing latch or an unlabeled strike is exactly what that inspection is looking for.
Locks the codes allow on the way out
The means of egress chapter lists a small number of locking arrangements by name. If what you want to build is not one of them, it is not allowed on an exit route. The Access Control course described how each one behaves. Here is how the code frames them.
- Released by a sensor. The usual magnetic lock, with a motion sensor, a manual release and release on fire alarm and loss of power.
- Released by the door hardware. An electric lock that lets go when the bar or lever on the door is operated, through a switch inside that hardware.
- Delayed egress. Release after a short, signed delay.
- Controlled egress. Doors that stay locked until staff release them, for certain healthcare uses.
- Stair doors locked from the stair side. Permitted in many buildings so long as they can be unlocked, without unlatching, when needed.
Each arrangement is allowed only in certain occupancies and comes with a list of conditions. The lists differ between the IBC and NFPA 101, and they have been rewritten in almost every recent edition. Read the section in the edition your jurisdiction adopted, and do not rely on memory or on this page for the conditions.
Which document do I open?
Seven questions, four documents
Pick the document you would reach for first.
Three examples
Simple: the strike in the labeled frame
You are asked to add an electric strike to a storeroom door off a corridor. The frame has a fire label. You check the strike's data sheet: it is not labeled for fire doors. Fitting it would cut a pocket in a rated frame and void the label.
You order the fire-rated version of the strike, confirm it is fail-secure as rated strikes are required to be, and note the label details in the job file for the next annual door inspection.
Medium: the conference room that grew
A company knocks two rooms into one to make a hall for all-staff meetings and asks for a card reader on its only door. On the old drawings each room was a small office. The new room holds enough people that the code may now treat it as an assembly space, which can mean a second exit, doors that swing outward and panic hardware.
You do not design the reader until the architect confirms the new occupant load. The answer changes the hardware you are allowed to electrify.
Advanced: card access on the stair doors
The owner of a tall office building wants card readers on the stair side of every stair door, so that people cannot wander between tenants' floors. The doors are fire doors in an exit enclosure. From the floor into the stair they must always open freely. From the stair back onto a floor, locking is the question.
The code generally permits it under conditions. The doors must still latch. They must be able to be unlocked together from a point the fire department uses, and many jurisdictions also require them to unlock when the fire alarm sounds. The exact conditions depend on the building's height and the adopted edition. The design uses fire-rated, fail-safe electrified locks, and the drawings go to the fire marshal before anything is ordered.
From the field
- Read the code summary sheet. The first pages of an architect's drawing set normally state the adopted codes, the occupancy classification and the occupant loads. It saves hours.
- Photograph every label. Door label and frame label, before you quote. A painted-over label still counts, and scraping one off does not make the door unrated.
- Check that the door closes and latches when you leave. Added seals, cables and strikes are the usual reasons it stops.
- Order doors prepared for electrified hardware from the factory wherever you can. It is cheaper than arranging label service later.
- Name the arrangement in your submittal. Use the code's own words for the locking arrangement. Reviewers look for them.
Common mistakes
- Treating every door alike, without asking what use and how many people are behind it.
- Fitting a magnetic lock as the only thing holding a fire door shut.
- Drilling a fire door for wiring on site.
- Quoting a locking arrangement from memory of an older edition.
- Forgetting the fire code still applies after the building permit is closed.
Summary
- The IBC governs how a building is built, the IFC how it is kept, NFPA 101 how people get out, and NFPA 80 the fire doors.
- The means of egress runs from exit access, through the exit, to the exit discharge.
- Occupancy classification and occupant load decide what a door must do.
- A fire door is a labeled assembly that must close and latch by itself, and may be altered only within narrow limits.
- Only the locking arrangements the code names are allowed on an exit route, each with conditions that vary by edition.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Name the three parts of the means of egress, in the order a person passes through them.
Show answer
Exercise 2. Why is a magnetic lock, with nothing else, not acceptable on a fire door?
Show answer
Exercise 3. A shop has been open for ten years. The fire marshal visits and finds a bolt on the rear exit. Which code is the marshal most likely enforcing?
Show answer
Exercise 4 (think, don't memorize). A customer shows you a web page that lists the conditions for delayed egress and says, "We meet all six, so order the locks." What do you do before ordering?