PanelSimulator Academy

Alarm Monitoring, lesson 7 of 10

Supervision and test signals

Lessons 2 and 3 showed how an alarm reaches the center and what it says. But what if nothing arrives? A healthy alarm system and a dead one look the same from the monitoring center: both are silent. Supervision is how a system proves, again and again, that it is still alive. This lesson shows what is checked, how often, and how long a failure can hide.

About 14 minutes. Read lessons 2 and 3 first.

How long would nobody know?

The only path to the center fails. Choose how often the panel checks in, and when the failure happens.

path fails center notices time received sent, not received
Check-in
Center acts
Second path
unnoticed, this time
unnoticed, worst case

The everyday picture

A lone hiker leaves a note with a friend: "I will text you at 6 p.m. every day. If you hear nothing by 8, call the rangers." The texts themselves say almost nothing. Their value is in the one that does not come.

The plan has two settings. How often the hiker checks in decides how long an accident could go unnoticed. How long the friend waits before acting decides how many false scares there are from a dead phone battery or a patch of no signal. Check in every hour and the friend sleeps badly. Check in weekly and the hiker lies in a ravine for six days.

Alarm systems face the same trade, and the trade has a name. Checking that something is still working, and raising a signal when it is not, is called supervision.

Three levels of supervision

A monitored system is supervised at three levels. A failure at any level leaves a hole, so each has its own check.

What is checkedWho checks itHowWhat a failure produces
Wiring to sensorsThe panelA small resistor at the far end of each circuit lets the panel tell a normal loop from a cut or shorted oneA trouble or tamper on that zone
Wireless sensorsThe panelEach sensor sends a brief check-in, typically every hour or so. The panel flags one that stays silent for several hours."Sensor missing" or "low battery" for that zone
The panel's own healthThe panelIt watches its mains supply, tests its battery under load from time to time, and watches its communication pathsAC loss, low battery, communication trouble
The path to the centerThe monitoring centerThe center expects a message from each account within a set period and flags any account that goes quietA "late to test" or "communication failure" signal created at the center

The first three are covered in the Intrusion Detection course. Notice the pattern in the last column. The panel can report its own troubles only while it has a working path. The last row is different: it is the only check made from outside the building, so it is the only one that catches a panel that has lost every path, lost all power or been destroyed.

Test signals and check-ins

You will meet two names for the regular message that proves a path is alive.

  • A periodic test, also called a timer test, is a full signal sent on a schedule: once a day, a week or a month. It was designed for phone dialers, where every call costs time and ties up the line. Lesson 3 gave its Contact ID code as 602.
  • A heartbeat, or poll, is a much smaller message exchanged by internet and cellular communicators, often every few minutes. It costs almost nothing to send.

Both work the same way at the center. The account record holds an expected interval. Each arrival resets a timer. If the timer runs out, the software creates a signal of its own, commonly called late to test, and an operator or a service desk follows it up. No person looks at a test that arrives on time.

Centers usually allow a margin before declaring an account late, because a single missed message is often a brief network fault. That margin adds to the time a real failure stays hidden.

Check yourself

A panel is unplugged and its battery is removed. What tells the monitoring center?

Choosing an interval

The interval sets the longest time a dead path can hide. A path that fails just after a check-in is not missed until the next one is due. Try it in the tool at the top.

Check-inLongest a failure can hideWhere you meet it
Every few minutesMinutesHigh-risk sites, and plans sold as "line security" or with a certificate that demands it
HourlyAbout an hourCommercial internet and cellular communicators. Some fire alarm rules sit near here.
DailyAbout a dayThe usual choice for homes and small shops
Weekly or monthlyA week or a monthOld dialer accounts. Hard to defend today.

The right-hand column is a guide, not a rule. For burglar alarms, the interval is a choice made by the customer, the alarm company and often the insurer. For fire alarms it is set by code. The edition of the national fire alarm code that your state or city has adopted says how quickly a failed path must be detected, and the figure has changed between editions. Recent editions have worked in terms of about an hour for a single path and several hours for each of two paths. Do not rely on memory: read the adopted edition and ask the fire marshal.

A second path changes the picture more than any interval. When one path fails, the panel notices within minutes and reports it over the other. The center knows, and alarms still get through in the meantime.

Trouble signals

A trouble is a signal that says the system is impaired but nothing is in alarm. Troubles are the system asking for a technician. The common ones:

  • AC loss. Mains power has failed and the panel is on its battery. Many panels wait a while, often a random period of up to an hour or more, before reporting it, so that a city-wide outage does not flood the center.
  • Low battery. The standby battery failed its test, or has run down in an outage. A sealed lead-acid battery typically lasts three to five years.
  • Communication trouble. The panel could not get a message confirmed on one of its paths.
  • Sensor trouble. A wireless sensor is missing or its battery is low, or a wired zone has a wiring fault.

Centers usually handle troubles by phoning or emailing the customer in business hours, and by telling the alarm company. A trouble that nobody follows up is a failed supervision system with extra steps.

Who notices first?

Seven faults. For each, decide who finds out, and how.

Panel, center, or nobody?

The last answer in that list, "nobody, until someone tests", is why supervision is never the whole story. No check-in can tell that a motion sensor is now facing a wall of boxes, or that the center's record holds the wrong address. Only a person testing can. Most alarm companies advise a user test every month and a technician's inspection every year. Fire alarm systems have inspection and testing schedules set by code.

Three examples

Simple: the daily test that did not come

A shop's cellular communicator sends a test at 3 a.m. each day. On Tuesday no test arrives. By mid-morning the center's software has flagged the account, and the service desk phones the owner. A contractor had switched off a breaker on Monday afternoon, and the panel's battery ran flat overnight. The shop was unprotected for part of one night, and it was found within a day. Without the test, it would have been found at the next break-in.

Medium: the monthly dialer

A church hall has an old dialer that tests on the first of each month. The phone company replaces the copper line with a fiber service on the 3rd, and the dialer's tones no longer get through. The keypad shows a trouble light that nobody reads. The center's timer does not expire until early the following month.

For four weeks the hall had a siren and nothing else. The fix is a cellular communicator with a daily check-in, and a sounder on the keypad that makes troubles hard to ignore.

Advanced: a fire panel between editions

A company takes over the fire alarm monitoring for an older office building. The existing communicator is a dialer on two phone lines, testing once a day, which met the code edition in force when it was installed. The city has since adopted a newer edition, and one of the two phone lines has been disconnected by the tenant.

The technician does not guess. She reads the adopted edition, phones the fire marshal's office, and learns what the city accepts for existing systems and what a replacement must meet. The building gets a listed dual-path communicator supervised at the intervals the marshal's office confirms in writing. The record of that conversation goes in the job file.

From the field

  • Make sure the center's expected interval matches the panel's. A panel testing weekly on an account set for daily produces a late signal every day, and people learn to ignore it.
  • Set the test time away from the top of the hour, if the panel lets you. Thousands of panels testing at exactly midnight slow each other down.
  • Prove the supervision works. During commissioning, disconnect the path and wait for the center to flag it. Note how long it took.
  • Date every battery with a marker when you fit it.
  • Leave the customer a one-page monthly test: call the center, go on test, trip a door, a motion sensor and a smoke detector, and ask what arrived.

Common mistakes

  • Treating "no signals" as "no problems".
  • Leaving a monthly test interval on a single-path account.
  • Turning off test signals to save cellular data fees.
  • Letting late-to-test and trouble signals pile up unanswered.
  • Assuming supervision checks sensors' coverage. It checks that they answer, not what they can see.

Summary

  • Supervision means regular proof that a part is working, with a signal when the proof stops.
  • The panel supervises its wiring, sensors, power and paths. The center supervises the panel by expecting check-ins.
  • The check-in interval sets how long a dead path can hide. A second path cuts that to minutes.
  • Fire alarm intervals come from the adopted code edition and the local authority.
  • Troubles need follow-up, and only testing by a person proves the whole chain.

Exercises

Answer each one yourself first, then open the answer.

Exercise 1. A single-path account checks in once a day, and the center acts at the first missed check-in. What is the longest a path failure can go unnoticed, ignoring any margin?

Show answer
About 24 hours: the path fails just after a check-in and is not missed until the next one is due. Set the tool at the top to "Daily" and slide the failure to the left to see it.

Exercise 2. The same account is changed so the center acts only after two missed check-ins. What is the worst case now?

Show answer
About 48 hours. Waiting for a second miss adds one whole interval.

Exercise 3. Why do many panels delay reporting an AC loss?

Show answer
Most power cuts are short and end by themselves, and a wide outage would make thousands of panels report in the same minute. A delay, often randomized, lets brief cuts pass unreported and spreads out the rest. The panel is on its battery in the meantime.

Exercise 4 (think, don't memorize). A customer says, "The system has not sent a single signal in three years. That shows how reliable it is." How do you answer?

Show answer
Silence shows nothing. A working system and a dead one are equally quiet. Three years with no test signals, no openings or closings and no troubles would in fact be alarming, since batteries age and networks change in that time. Ask what the check-in interval is and when a test last arrived, then run a full test with the center on the phone. Reliability is shown by regular signals that arrive on time, not by their absence.