Access Control, lesson 11 of 14
Events, alarms and monitoring
Lesson 4 said the controller writes a record of everything it does. That record runs to thousands of lines a day. Almost all of them are ordinary. A few need a person to act within minutes. This lesson teaches you to tell them apart, and to set a system up so that the important ones are not buried.
Take the monitoring desk
Eight events from one site. Decide what each one needs, then read why.
The everyday picture
A ship keeps a logbook. Every change of course, every weather reading and every visitor is written down with the time. On most days nobody reads it. After an accident it is the first thing investigators ask for.
The ship also has alarms: bells for fire, flooding and collision. The log records. The alarms interrupt. A good ship has few alarms, and the crew trusts every one of them.
An access control system has both. Each line in its log is an event. An event that needs a person to act is an alarm.
What an event contains
Every event answers four questions.
| Question | Example | Where it comes from |
|---|---|---|
| When | 02:14:07, Tuesday | The controller's clock |
| Where | Server room door | Which reader or input reported it |
| Who | Omar H., or nobody | The card number, matched to the list |
| What | Door forced open | The controller's reasoning, from lesson 1 |
Notice that some events have no "who". A forced door has no card attached. That is exactly why it matters.
Events you will see
| Event | What it means | Usually |
|---|---|---|
| Access granted | A valid card opened a door | Record only |
| Access denied | A card was refused, with the reason | Record. Alarm if repeated. |
| Door held open | The door stayed open past its time limit | Low-priority alarm |
| Door forced open | The door opened with no grant and no exit request | High-priority alarm |
| Tamper | A reader was pulled off the wall or a cabinet was opened | High-priority alarm |
| Device offline | A reader or controller stopped answering | Alarm. Priority depends on the door. |
| Power trouble | AC power failed or a battery is low | Alarm. The battery clock is running. |
| Duress | Someone entered a special PIN meaning "I am being forced" | Highest priority, shown silently |
Handling an alarm
Good monitoring software walks an operator through four steps, and records each one.
- Acknowledge. The operator shows they have seen it. The clock on response time stops here.
- Assess. Look before acting. If a camera covers the door, the software can show its picture beside the alarm. Check the events just before: was there a valid card ten seconds earlier?
- Respond. Follow the written instruction for that alarm at that door: send a guard, phone the department, or call the police.
- Close. Write what was found. "Delivery driver propped door, spoken to" is a useful record. An empty box is not.
The written instructions matter most at 3 a.m., when the operator is alone and tired. Decide the response to each alarm in daylight, in advance.
Check yourself
A door forced open alarm arrives. What should the operator do first after acknowledging it?
Too many alarms
An operator who sees two hundred door held open alarms a day stops reading them. This has a name, alarm fatigue, and it is how real break-ins are missed: the one alarm that mattered looked like all the others.
The cure is never to mute the alarms. It is to remove their causes.
- List which doors produce the most alarms. A handful of doors usually produce most of them.
- For each, find out why. A closer that does not latch, a held-open time too short for a loading door, a missing exit sensor.
- Fix the door, adjust the setting for that door only, or change how people use it.
- Give each alarm type a priority, so that a forced server room door never waits behind a propped break room door.
Reports and records
- History report. Everything at one door, or by one person, between two dates. This is the report asked for after a loss.
- Muster report. In an evacuation, a list of who badged in and has not badged out, so that wardens know who to look for.
- Operator log. What the people using the software did: who changed a level, who cleared an alarm. The watchers are recorded as well.
Two things make records trustworthy. Every controller and camera must share the same clock, set automatically from the network. And records must be kept for a period the organization has decided, then deleted.
Remember what these records are: a history of where named people went. They are personal information. Only people with a reason should be able to read them, and they should be used for security and safety, not for timing staff breaks unless staff have been told.
Three examples
Simple: who went into the stockroom?
Stock is missing on Wednesday morning. The manager runs a history report for the stockroom door from Tuesday 5 p.m. to Wednesday 8 a.m. It shows three entries: two by the cleaner at the usual time and one at 11:40 p.m. by a card belonging to a member of staff. That is a fact to ask about, not a verdict. Cards can be borrowed.
Medium: two hundred alarms a day
A site's operators have learned to click away held-open alarms without reading. One night a real forced-door alarm sits unread for forty minutes. The review finds that three doors produce 80 percent of the alarms: a loading door, a break room door and a door with a failing closer.
The loading door's time is lengthened during deliveries, the closer is replaced, and break room staff are asked not to prop the door. Alarms fall to about fifteen a day, and operators start reading them again.
Advanced: six minutes apart
After a theft, the access log says the door opened at 02:14. The camera recording shows nobody at the door at 02:14. It shows someone at 02:20. The two systems' clocks had drifted six minutes apart, because the controller was never set to take its time from the network.
The evidence is still usable, but every statement now needs an explanation, and the other side's lawyer will ask what else is wrong. Setting every device to the same time source takes minutes during installation.
From the field
- Set up automatic time on every controller, server and camera before leaving site, and check that they agree.
- Name doors as people say them. "Stockroom, rear" helps an operator. "Rdr 2-14 Pnl B" does not.
- Trigger each alarm type once during handover and watch the operator handle it.
- Count alarms per door every month. The top five are next month's repair list.
- Agree the record-keeping period in writing with the customer.
Common mistakes
- Treating every event as an alarm, so that nothing stands out.
- Switching off a noisy alarm instead of fixing its cause.
- No written response for each alarm type.
- Clocks that disagree between the access system and the cameras.
- Treating a card's event as proof of who the person was.
Summary
- Every event records when, where, who and what. An alarm is an event that needs a person to act.
- Forced doors, tamper, repeated denials and power trouble deserve attention. Single grants and denials are records.
- Handle an alarm in four steps: acknowledge, assess, respond, close.
- Reduce alarms by fixing their causes, and rank the rest by priority.
- Records need a common clock, a retention period, and limits on who may read them.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. Which three signals does a controller use to decide that a door was forced? Lesson 1 covered this.
Show answer
Exercise 2. The same card is denied "outside schedule" at the front door at 6:55, 6:56 and 6:58 a.m. Staff hours start at 7. Alarm or not?
Show answer
Exercise 3. In an evacuation, the muster report lists nine people still inside. The wardens count everyone at the assembly point. Give one reason the list could be wrong.
Show answer
Exercise 4 (think, don't memorize). A manager asks for a weekly report of how long each employee spends away from their desk, taken from door events. How do you respond?