Access Control, lesson 9 of 14
Cable and wiring
Lesson 8 worked out how much power each door needs. Cable is how that power, and every signal, actually reaches the door. It is the part nobody sees and nobody can easily change later. Choose it too thin, run it too far or put it in the wrong place, and the faults appear months afterwards. This lesson gives you the few rules that prevent that.
Lose voltage on a cable
Change the cable and the load, and watch what reaches the lock.
The everyday picture
Water a garden with a short, fat hose and the spray is strong. Join four thin hoses end to end and the same tap gives a dribble. Nothing is wrong with the tap. The hose used up the pressure on the way.
Copper wire does the same to electricity. Every foot of wire resists the flow a little. The loss grows with three things: a longer cable, a thinner wire, and a bigger current. It is called voltage drop.
A lock that receives too little voltage holds weakly, buzzes, or fails to release. Try the tool above with 400 feet of thin wire and then change one thing at a time.
Reading a cable
A cable's description packs several facts into a short code, such as "18/2 shielded plenum".
- Thickness. In the United States this is given in AWG, American Wire Gauge. The scale runs backwards: a smaller number is a thicker wire. 18 AWG is thicker than 22 AWG.
- Conductors. The number of separate wires inside the jacket. "18/2" is two wires of 18 AWG.
- Stranded or solid. Stranded wire is many fine threads twisted together and survives bending. Most security cable is stranded.
- Shield. A foil wrap with a bare wire, the drain, that keeps electrical noise out of data wires.
- Fire rating. Printed on the jacket. This one is a legal matter, covered below.
Which cable goes where
| To | Typical cable | Why |
|---|---|---|
| Reader, Wiegand | 22 AWG, 6 conductors, shielded | Power, two data wires, light and beeper. Shield against noise. |
| Reader, OSDP | Twisted pair for data plus a pair for power, shielded | The twist lets the data travel thousands of feet. |
| Lock | 18 AWG, 2 conductors. Thicker on long runs. | Locks draw the most current, so they suffer the most drop. |
| Door position switch | 22 AWG, 2 conductors | Carries almost no current. |
| Request to exit | 22 AWG, 4 conductors | Two for power to the sensor, two for its signal. |
Suppliers sell all four in one jacket, called composite access control cable. One pull to each door, with every wire color-coded, saves a great deal of labour.
Check yourself
A lock at the end of a long cable is getting too little voltage. Which change does not help?
Rules for running cable
The fire rating on the jacket
Many buildings use the space above the ceiling to move air. That space is called a plenum. Ordinary cable jacket gives off thick toxic smoke when it burns, and the air system would spread it through the building. So the electrical code requires plenum-rated cable there, marked CMP on the jacket. Cable marked CMR is for vertical runs between floors. Using the wrong one fails inspection, and the only cure is to pull it all out.
Keep away from AC power wiring
Low-voltage security cable must not share a conduit or box with AC power wiring. Apart from the safety rule, AC power cables and fluorescent lights put electrical noise into data wires. Cross them at a right angle where you must, and keep parallel runs well apart.
Support, seal and label
- Hang cable from its own hooks. Do not lay it on ceiling tiles or tie it to pipes.
- Where a cable passes through a fire-rated wall, the hole must be sealed with approved firestop material.
- Leave a few feet of spare cable coiled at each end, called a service loop, so a damaged end can be cut back and remade.
- Label both ends of every cable with the same name before it is pulled.
Three examples
Simple: one composite cable
A door is 120 feet from the cabinet. One composite cable carries the reader, lock, switch and exit sensor wires. At that length, with a strike drawing 0.4 amps on 18 AWG at 24 volts, the lock loses about 0.6 volts. That is nothing to worry about.
Medium: the lock that buzzes
A magnetic lock at the far end of a warehouse holds weakly. It is 12-volt, draws 0.5 amps, and sits 350 feet away on 22 AWG wire that was left over from the reader. The math says it loses 5.6 volts, almost half of what it was sent.
The cure is any of three changes: 16 AWG wire, a 24-volt supply with the lock set to match, or a small power supply near the door. Changing the lock would change nothing.
Advanced: the ceiling that failed inspection
An installer runs 4,000 feet of ordinary cable above the ceilings of an office floor. The inspector lifts a tile, sees that the ceiling space is an air plenum, reads the jacket, and fails the job. Every foot has to come out.
Before ordering cable, ask the building's engineer one question: is the ceiling space a plenum? If nobody knows, buy plenum-rated cable. The price difference is small beside the cost of pulling a floor twice.
From the field
- Work out the drop for the longest lock run before buying cable. If the longest passes, the rest will.
- Remember the current makes a round trip. A 200-foot run is 400 feet of wire. The tool above already counts both ways.
- Connect the shield's drain wire at the cabinet end only.
- Pull a spare cable to hard places such as gates and outbuildings. The second pull later costs far more than the cable.
- Photograph every open ceiling and wall before it is closed, and keep the photos with the site records.
Common mistakes
- Using thin reader cable for a lock because it was already on the truck.
- Reading AWG the wrong way round and choosing a thinner wire for a longer run.
- Running ordinary cable through a plenum ceiling.
- Sharing a conduit with AC power wiring.
- Leaving cables unlabeled, or labeled at one end only.
Summary
- Wire uses up voltage. Longer, thinner and busier cables lose more.
- A smaller AWG number is a thicker wire.
- Locks need the thickest wire at a door. Switches and sensors need the thinnest.
- Air-handling ceilings need plenum-rated cable, marked CMP.
- Keep low voltage away from AC power wiring, seal holes in fire walls, and label both ends.
Exercises
Answer each one yourself first, then open the answer. The tool at the top will help.
Exercise 1. Which is thicker, 16 AWG or 20 AWG?
Show answer
Exercise 2. Set the tool to 500 feet, 18 AWG, 0.5 amps and 12 volts. Is the result acceptable? Now switch to 24 volts and halve the current, as a dual-voltage lock would.
Show answer
Exercise 3. A reader's cable passes through a fire-rated corridor wall. Name two things that must be done.
Show answer
Exercise 4 (think, don't memorize). A door is 800 feet from the nearest cabinet. List the options and say which you would explore first.