Access Control, lesson 7 of 14
Getting out: egress and life safety
Access control is about who may come in. The law cares far more about who can get out. This lesson covers the one rule that overrides every security wish, and the few carefully limited exceptions to it.
Watch people leave a room
Pick a situation, then play or step through. The room is seen from above.
The everyday picture
Think of a movie theater. To get in, you need a ticket and someone checks it. To get out, you push a bar on a door and you are in the street. Nobody checks anything. In the dark, in a hurry, with a child on your arm, the door still opens with one push.
That arrangement exists because of fires in which crowds reached locked or confusing exits and could not get through. Every rule in this lesson was written after such a fire. This is why inspectors do not bargain over them.
Getting out of a building is called egress. The promise that you always can is called free egress.
The rule and what it means
In the United States the rule appears in the International Building Code and in NFPA 101, the Life Safety Code. In plain words, a door on an exit route must open from the inside:
- With one motion. Push a bar or turn a lever. A lever and then a separate bolt is two.
- Without a key, a card, a code or a tool.
- Without special knowledge. A stranger must be able to work it at first sight.
- Without tight gripping or twisting. This is why exits have levers and bars, not round knobs.
Where many people gather, such as assembly halls and schools, the code goes further and requires panic hardware: a bar across the door that releases the latch when a body presses against it.
What this means for the locks you know
| Lock | How people get out | Does egress depend on electricity? |
|---|---|---|
| Electric strike | Lever or push bar pulls the latch back | No |
| Electrified lock or push bar | Inside lever or bar always works | No |
| Magnetic lock | Power to the magnet must be cut | Yes, so extra devices are required |
This is the strongest argument for locks that leave the inside handle mechanical. A fault in the controller, the network or the software cannot trap anyone.
What the fire alarm does
The fire alarm system and the access control system are separate, and the fire alarm outranks it. A cable from the fire alarm panel runs to the power supplies that feed the locks. When the alarm sounds, a relay opens and power to the chosen locks is cut directly. The access controller is not asked.
- Magnetic locks on exit routes release.
- Stairwell doors unlock from the stair side in many buildings, so that people who meet smoke can get back onto a floor. The doors stay latched to hold smoke back.
- Doors with mechanical inside handles do not need to change. People could already get out.
Note what the alarm does not do. It does not need to unlock doors from the outside on ordinary rooms. A fail-secure storeroom stays locked to the corridor while everyone inside leaves by the handle.
Check yourself
The access control server has crashed. Which door might now trap someone inside?
Special arrangements
The codes allow a small number of exceptions to instant free egress. Each one is permitted only in certain kinds of building, comes with a list of conditions, and needs the approval of the authority having jurisdiction.
| Arrangement | What happens | Typical use |
|---|---|---|
| Delayed egress | Pushing the bar starts a loud alarm and a 15-second countdown, then the door releases. Fire alarm or power loss releases it at once. A sign on the door explains this. | Shop stockrooms, to deter theft |
| Controlled egress | Doors stay locked and staff release them. They unlock on fire alarm and power loss. | Hospital units where patients could come to harm by wandering |
| Sensor release | A magnetic lock released by a motion sensor, with a push button and fire alarm release as backup. | Glass entrance doors |
| Interlock | Two doors in a row where only one may be open at a time. | Clean rooms and high-security entrances |
Treat every row of this table as "ask first". The conditions change between code editions and between cities.
Would this door pass?
Six doors, your call
Decide whether each door meets the free egress rule, then read why.
Three examples
Simple: the chained back door
A shop owner is tired of stock leaving by the rear exit and has put a chain through the push bar. This is the single most common violation inspectors find, and the most dangerous. The legal ways to get the same result are an alarm on the door that sounds when it is opened, or, where the code allows it, a delayed egress lock.
Medium: who left the server room?
A company wants a record of everyone who leaves its server room, so it asks for a reader on the inside and a lock that needs a card to exit. That fails the rule: leaving would need a card.
The answer is to keep the inside reader but leave the lever free. Staff are told to badge out. If someone leaves without badging, the door opens anyway and the controller records a door forced open. The record is kept and nobody can be trapped.
Advanced: the hospital corridor
A hospital unit cares for patients with dementia who may walk out and come to harm. Free egress would endanger the very people the building serves. The codes recognize this and allow controlled egress here, with conditions: staff can release the doors, the doors unlock on fire alarm and on loss of power, and the building has sprinklers or a full detection system.
The design is drawn up with the hospital's safety officer and approved by the AHJ before any hardware is ordered. An installer who fits it on a contractor's say-so is taking a risk that is not theirs to take.
From the field
- Walk the exit route as a stranger would. From any room to the street, can you get out without a card, a key or an explanation?
- Test the fire alarm release with the fire alarm company present. Trigger it and check that every lock on the list really lets go.
- Wire exit buttons to cut lock power directly. A button that only asks the controller to unlock is not a safety device.
- Get approvals in writing for any special arrangement, and keep a copy at the site.
- When a customer asks for something unsafe, offer the legal way to reach the same goal. There nearly always is one.
Common mistakes
- Believing fail-secure means people are locked in. It describes the outside of the door.
- Requiring a card to exit.
- Adding a second bolt or latch to an exit door.
- Connecting the fire alarm to the access software and not to the lock power.
- Installing delayed or controlled egress without approval.
Summary
- From the inside, an exit door opens with one motion and no key, card or special knowledge.
- Locks that leave the inside handle mechanical cannot trap anyone.
- Magnetic locks depend on electricity to release, so they need a sensor, a direct push button and fire alarm release.
- The fire alarm cuts lock power directly and outranks the access system.
- Delayed egress, controlled egress and interlocks are exceptions that need approval.
Exercises
Answer each one yourself first, then open the answer.
Exercise 1. List the motions needed to leave through a door that has a lever handle and a separate thumb-turn bolt above it. Does it meet the rule?
Show answer
Exercise 2. During a fire alarm, should a fail-secure storeroom door unlock from the corridor?
Show answer
Exercise 3. A delayed egress door is pushed at the same moment the fire alarm sounds. How long before it opens?
Show answer
Exercise 4 (think, don't memorize). A daycare center wants to stop small children opening the front door and running into the parking lot. What would you propose, and who would you speak to?